سيتم إشعارك عبر البريد الإلكتروني عند توفر هذا المنتج
- الوصف
- Reviews
- الشحن والدفع
Configured for programmable control execution and Ethernet-based I/O communication in the Modicon M580 PAC platform, the Schneider Electric BMEP582040 (BMEP582040 Processor Module) provides processor, memory, local I/O management, remote I/O scanning, and distributed device communication through integrated Ethernet interfaces.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMEP582040 |
| Brand | Schneider Electric |
| Series | Modicon M580 |
| Product Type | Processor Module |
| Origin | US |
| Weight | 0.849 kg |
| Operating Temp | 0 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Power Consumption | 270 mA at 24 VDC |
| Local Discrete I/O Capacity | 2048 I/O |
| Local Analog I/O Capacity | 512 I/O |
| Application-Specific Channels | 72 |
| Remote I/O Stations | 8 |
| Distributed Equipment | 64 |
| Program Memory | 8 MB process program RAM |
| Data Memory | 768 kB process data RAM |
| Safety Program Memory | 2 MB |
| Safety Data Memory | 512 kB |
| Flash Storage | 4 GB |
| Ethernet Interfaces | 1 service port + 2 device network ports |
| USB Interface | 1 USB Type Mini-B |
| Communication Services | DIO scanner, RIO scanner |
| Processor Performance | 30 Kinst/ms at 65% Boolean + 35% fixed arithmetic; 40 Kinst/ms at 100% Boolean |
| Application Tasks | 64 event tasks, 2 auxiliary tasks, 1 cyclic/periodic master task, 1 periodic fast task |
| Protection Rating | IP20 |
| Vibration Resistance | 3 gn |
| Shock Resistance | 15 gn |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| Operating Altitude | 0 to 2000 m; 2000 to 5000 m with derating |
| Rack Power Supply | Internal power supply via rack |
| Cybersecurity Functions | Embedded firewall, IPSec, TLS, HTTPS, SNMP logging, Syslog, audit trail, firmware signature, password protection, port hardening |
| Certifications | CE, UL, CSA, RCM, EAC, Merchant Navy, UKCA |
| Standards | IEC 61131-2, IEC 61010-2-201, UL 61010-2-201, CSA C22.2 No 61010-2-201, IACS E10, EN/IEC 61000-6-5, EN/IEC 61850-3 |
Ethernet and M580 Control Architecture
The BMEP582040 separates service and device-network communication through dedicated Ethernet interfaces. The processor supports DIO and RIO scanner functions, up to 64 distributed devices, and up to 8 remote I/O stations. Local processing capacity includes 2048 discrete I/O and 512 analog I/O channels.
The processor uses rack-based internal power and communicates with associated Modicon M580 modules through the backplane architecture. The memory structure includes process program and data RAM, safety program and data areas, and expandable 4 GB flash storage.
For Ethernet-based control networks, configuration should account for device addressing, network topology, scanner assignments, and firmware compatibility. The stated processor capacity supports Ethernet device communication without treating the service port as an equivalent substitute for the dedicated device network ports.
Frequently Asked Questions
Q: Does the BMEP582040 require an external DC power connection?
A: No. The processor receives its operating power through the rack internal power supply. The specified processor consumption is 270 mA at 24 VDC.
Q: How many Ethernet interfaces are integrated into the processor?
A: The module provides 1 Ethernet TCP/IP service port and 2 Ethernet TCP/IP device-network ports. A separate USB Type Mini-B interface is also provided.
Q: What local and remote I/O capacity is specified?
A: The processor supports 2048 discrete and 512 analog local I/O channels, together with up to 8 remote I/O stations and 64 distributed devices.
Field Installation Guidelines
- Install the processor in the designated Modicon M580 rack position and verify correct mechanical engagement with the backplane.
- Confirm that rack power is removed before inserting or removing the processor unless the applicable M580 installation procedure explicitly permits the operation.
- Route Ethernet communication cables separately from high-current power and switching conductors where practical to reduce electromagnetic coupling.
- Maintain appropriate shield termination and bonding practices for the selected Ethernet cabling system.
- Verify Ethernet port assignments before commissioning. Keep service, device-network, and other dedicated communication functions aligned with the configured M580 architecture.
- Check processor, rack, I/O, and communication-module firmware compatibility before firmware replacement or system modification.
- Provide the specified environmental conditions, including 0 to 60 deg C operating temperature and IP20 installation protection.
- Use the processor status LEDs to identify RUN, ERR, I/O, DL, BACKUP, Ethernet, safety-mode, maintenance-mode, and forced-I/O states during commissioning and troubleshooting.
الدفع: تحويل مصرفي (T/T)، ويسترن يونيون.
ميناء الشحن: شيامن.
مدة التجهيز: عادةً من يوم إلى 3 أيام عمل بعد تأكيد الدفع (وفقًا لتوافر المخزون).
التوصيل worldwide: نشحن قطع الأتمتة الصناعية إلى العملاء حول العالم. تُدرج تكلفة الشحن ضمن عرض السعر الخاص بطلب عرض الأسعار (RFQ).
الأسئلة الشائعة
الأسئلة الشائعة حول عروض الأسعار والشحن والضمان والإرجاعانقر على طلب عرض سعر في صفحة المنتج وأرسل إلينا رقم القطعة والكمية المطلوبة وبلد الوجهة. سيرد فريق المبيعات لدينا بتوفر المنتج حاليًا وسعره ووقت التسليم التقديري.
تُجهَّز المنتجات المتوفرة عادةً بعد الدفع وتأكيد الطلب. تُشحن معظم الطلبات من مستودعنا في الصين، مع أن موقع الشحن قد يختلف حسب المخزون الحالي.
نعم. نشحن قطع الأتمتة الصناعية إلى العملاء في جميع أنحاء العالم. تعتمد تكلفة الشحن ومدة النقل على الوجهة ووزن الطرد وحجم المنتج ومتطلبات الاستيراد المحلية.
نستخدم عادةً خدمات شركات الشحن الدولية مثل DHL وFedEx وUPS وغيرها. ويمكن اختيار شركة الشحن وفقًا للوجهة وسرعة التسليم وحجم الشحنة ومتطلبات العميل.
تخضع منتجاتنا عمومًا لضمان لمدة 12 شهرًا. كما يمكن إرجاع المنتجات المؤهلة بموجب سياسة استرداد الأموال خلال 30 يومًا. يُرجى التواصل مع فريقنا قبل إرجاع أي منتج لتأكيد الشروط المعمول بها وتعليمات الإرجاع.
قد يعجبك أيضًا
منشورات المدونة
أخبار الأتمتة الصناعية، والأدلة التقنية، وتحديثات المنتجات.