{"product_id":"schneider-electric-bmxart0814-modicon-x80-analog-input-module","title":"Schneider Electric BMXART0814 Modicon X80 Analog Input Module","description":"\u003cp\u003eConfigured for temperature, voltage, resistance, and thermocouple measurement in the Modicon X80 platform, the \u003cstrong\u003eSchneider Electric BMXART0814\u003c\/strong\u003e (\u003cstrong\u003eBMXART0814\u003c\/strong\u003e analog input module) provides eight isolated low-level analog input channels with 15 bits + sign resolution. It supports RTD, thermocouple, resistance, and voltage input ranges with external cold junction compensation by Pt100 probe.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXART0814\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog input module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Inputs\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Level\u003c\/td\u003e\n\u003ctd\u003eLow level\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Isolation\u003c\/td\u003e\n\u003ctd\u003eIsolated between channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Types\u003c\/td\u003e\n\u003ctd\u003eVoltage, resistance, RTD, thermocouple\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Input Resolution\u003c\/td\u003e\n\u003ctd\u003e15 bits + sign\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA\/D Conversion\u003c\/td\u003e\n\u003ctd\u003eSigma delta, 16 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Ranges\u003c\/td\u003e\n\u003ctd\u003e+\/- 40 mV, +\/- 80 mV, +\/- 160 mV, +\/- 320 mV, +\/- 640 mV, +\/- 1.28 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResistance Inputs\u003c\/td\u003e\n\u003ctd\u003e400 Ohm and 4000 Ohm, 2-wire, 3-wire, or 4-wire\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRTD Inputs\u003c\/td\u003e\n\u003ctd\u003eCu 10, Ni 100, Ni 1000, Pt 100, Pt 1000\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eThermocouple Types\u003c\/td\u003e\n\u003ctd\u003eB, E, J, K, L, N, R, S, T, U\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCold Junction Compensation\u003c\/td\u003e\n\u003ctd\u003eExternal by Pt100 probe\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Read Cycle\u003c\/td\u003e\n\u003ctd\u003e400 ms with temperature probe; 200 ms with thermocouple\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Mode Rejection\u003c\/td\u003e\n\u003ctd\u003e120 dB at 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDifferential Mode Rejection\u003c\/td\u003e\n\u003ctd\u003e60 dB at 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDigital Filtering\u003c\/td\u003e\n\u003ctd\u003eFirst order\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMeasurement Resolution\u003c\/td\u003e\n\u003ctd\u003e0.1 deg C for supported temperature inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Wiring Resistance\u003c\/td\u003e\n\u003ctd\u003eUp to 500 Ohm depending on sensor and wiring configuration\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Connection\u003c\/td\u003e\n\u003ctd\u003e40-way, 2 connectors\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003e150 mA at 3.3 VDC; 50 mA at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.165 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5 to 95% at 55 deg C, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIP Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVibration Resistance\u003c\/td\u003e\n\u003ctd\u003e3 gn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShock Resistance\u003c\/td\u003e\n\u003ctd\u003e30 gn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Altitude\u003c\/td\u003e\n\u003ctd\u003e0 to 2000 m; 2000 to 5000 m with derating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRecalibration\u003c\/td\u003e\n\u003ctd\u003eInternal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOpen Circuit Detection\u003c\/td\u003e\n\u003ctd\u003eSupported for specified RTD and thermocouple inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Indication\u003c\/td\u003e\n\u003ctd\u003eRUN, channel diagnostic, ERR, and I\/O LEDs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCertifications\u003c\/td\u003e\n\u003ctd\u003eCE, EAC, UL, CSA, Merchant Navy, RCM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStandards\u003c\/td\u003e\n\u003ctd\u003eIEC 61131-2, IEC 61000-6-4, IEC 61000-6-2, EN 61010-2-201\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtective Treatment\u003c\/td\u003e\n\u003ctd\u003eStandard version\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eThe module specifications identify eight isolated inputs, low-level input operation, 15 bits + sign resolution, and a 150 mA current consumption at 3.3 VDC. The environmental ratings and physical weight are specified as IP20, 0 to 60 deg C operating temperature, and 0.165 kg net weight.\u003c\/p\u003e\n\u003ch3\u003eI\/O Density and Signal Conditioning\u003c\/h3\u003e\n\u003cp\u003eThe BMXART0814 provides eight analog channels within a Modicon X80 module. The input circuitry accepts multiple low-level voltage ranges, resistance configurations, RTD types, and thermocouple types. Channel-to-channel isolation separates the individual input circuits. The module applies first-order digital filtering and provides common-mode rejection of 120 dB and differential-mode rejection of 60 dB at 50\/60 Hz.\u003c\/p\u003e\n\u003cp\u003eFor temperature measurement, cold junction compensation is performed externally using a Pt100 probe. The specified measurement and temperature-drift values vary according to the selected sensor or input range. Internal recalibration and open-circuit detection are provided for the supported sensor types.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How many analog channels does the BMXART0814 provide?\u003cbr\u003eA: It provides 8 analog input channels with channel-to-channel isolation.\u003c\/p\u003e\n\u003cp\u003eQ: What power consumption is specified for the module?\u003cbr\u003eA: The module consumes 150 mA at 3.3 VDC and 50 mA at 24 VDC.\u003c\/p\u003e\n\u003cp\u003eQ: How is cold junction compensation implemented?\u003cbr\u003eA: Cold junction compensation is external and uses a Pt100 probe.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eInstall the module in the compatible Modicon X80 rack and secure the module mechanically before connecting field wiring.\u003c\/li\u003e\n\u003cli\u003eUse the specified 40-way connector arrangement for electrical connections.\u003c\/li\u003e\n\u003cli\u003eSeparate low-level analog and thermocouple wiring from high-current power and switching conductors where practical.\u003c\/li\u003e\n\u003cli\u003eMaintain correct sensor wiring configuration for 2-wire, 3-wire, or 4-wire resistance and RTD measurements.\u003c\/li\u003e\n\u003cli\u003eApply shield termination according to the installation grounding scheme and avoid creating unintended ground loops.\u003c\/li\u003e\n\u003cli\u003eFor thermocouple channels, use the appropriate thermocouple wiring and verify the external Pt100 connection required for cold junction compensation.\u003c\/li\u003e\n\u003cli\u003eConfirm the selected input range and sensor type before commissioning each channel.\u003c\/li\u003e\n\u003cli\u003eObserve the IP20 enclosure limitation and install the module inside an enclosure providing the required environmental protection.\u003c\/li\u003e\n\u003cli\u003eKeep ambient operating temperature within 0 to 60 deg C and account for altitude derating above 2000 m.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":52999007371549,"sku":"BMXART0814","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/BMXART08142.jpg?v=1789969869","url":"https:\/\/www.6gcontrols.com\/ar\/products\/schneider-electric-bmxart0814-modicon-x80-analog-input-module","provider":"6G Controls","version":"1.0","type":"link"}