{"product_id":"schneider-electric-bmxehc0800-modicon-x80-high-speed-counter-module","title":"Schneider Electric BMXEHC0800 Modicon X80 High-Speed Counter Module","description":"\u003cp\u003eThe \u003cstrong\u003eSchneider Electric BMXEHC0800\u003c\/strong\u003e is a high-speed counter module for the Modicon X80 automation platform. It provides 8 counting channels with a maximum counting frequency of 10 kHz and supports single-mode and dedicated two-phase counting configurations. The module accepts 24 VDC input signals and processes counting, frequency measurement, and encoder-related signals for PLC control applications.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eProduct Function and Counting Capabilities\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe BMXEHC0800 processes high-speed input pulses that may exceed the practical counting capability of standard PLC digital inputs. It supports several counting functions, allowing the controller to monitor pulse events, measure frequency, and track incremental changes in position or movement.\u003c\/p\u003e\n\u003cp\u003eSupported counting functions include:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eForward and reverse counting.\u003c\/li\u003e\n\u003cli\u003e32-bit up-counting.\u003c\/li\u003e\n\u003cli\u003eDown-counting.\u003c\/li\u003e\n\u003cli\u003eModulo (loop) counting.\u003c\/li\u003e\n\u003cli\u003eEvent counting.\u003c\/li\u003e\n\u003cli\u003eFrequency measurement.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe module supports a maximum counting frequency of 10 kHz. Its 5 ms cycle time is a separate timing parameter and should not be interpreted as the maximum input pulse period.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eInput Signals and Sensor Compatibility\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module operates with 24 VDC Type 3 inputs. Compatible signal sources include 2-wire and 3-wire proximity sensors rated for 19.2-30 V, as well as incremental encoders with 10-30 V push-pull outputs.\u003c\/p\u003e\n\u003cp\u003eThe guaranteed logic thresholds define the input signal recognition limits:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eLogic 1: 11-30 VDC, with an input current greater than 2 mA at U \u0026gt;= 11 V.\u003c\/li\u003e\n\u003cli\u003eLogic 0: 5 VDC, with an input current below 1.5 mA.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThese thresholds help determine whether a connected sensor or encoder provides sufficient voltage and current for reliable signal recognition.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eElectrical Connection and Power Requirements\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe BMXEHC0800 uses one 20-pin connector for field signal connections. Its internal power consumption is specified separately for the 3.3 VDC backplane bus and the 24 VDC sensor supply.\u003c\/p\u003e\n\u003cp\u003eThe stated current consumption is 200 mA from the 3.3 VDC bus and 80 mA from the 24 VDC sensor supply. These values should be considered separately when checking the power budget of the X80 rack and the connected sensor circuit.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eInstallation and Environmental Conditions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module is designed for installation in a Modicon X80 module rack and is secured using two screws. Its IP20 enclosure protects the electronic components against contact with fingers and solid objects of the specified size, but does not provide protection against water ingress.\u003c\/p\u003e\n\u003cp\u003eThe operating temperature range is 0 to 60 deg C, with a relative humidity range of 10-95%, non-condensing. The specified insulation voltage is 1500 V for 60 seconds.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXEHC0800\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eHigh-Speed Counter Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Family\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAutomation Platforms\u003c\/td\u003e\n\u003ctd\u003eModicon M340 \/ Modicon M580\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Counting Frequency\u003c\/td\u003e\n\u003ctd\u003e10 kHz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n\u003ctd\u003e2 single-mode; 3 dedicated two-phase mode\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Type\u003c\/td\u003e\n\u003ctd\u003eHigh-speed, 24 VDC Type 3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage Limits\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e4.5 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGuaranteed Logic 1 Voltage\u003c\/td\u003e\n\u003ctd\u003e11-30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGuaranteed Logic 1 Current\u003c\/td\u003e\n\u003ctd\u003eGreater than 2 mA at U \u0026gt;= 11 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGuaranteed Logic 0 Voltage\u003c\/td\u003e\n\u003ctd\u003e5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGuaranteed Logic 0 Current\u003c\/td\u003e\n\u003ctd\u003eLess than 1.5 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSensor Compatibility\u003c\/td\u003e\n\u003ctd\u003e19.2-30 VDC 2-wire\/3-wire proximity sensors\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEncoder Compatibility\u003c\/td\u003e\n\u003ctd\u003e10-30 V push-pull incremental encoders\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCounting Functions\u003c\/td\u003e\n\u003ctd\u003eForward\/reverse, 32-bit up-counting, down-counting, modulo, event counting, frequency measurement\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCycle Time\u003c\/td\u003e\n\u003ctd\u003e5 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInsulation Voltage\u003c\/td\u003e\n\u003ctd\u003e1500 V for 60 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Connection\u003c\/td\u003e\n\u003ctd\u003e1 x 20-pin connector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBackplane Current Consumption\u003c\/td\u003e\n\u003ctd\u003e200 mA at 3.3 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSensor Supply Current Consumption\u003c\/td\u003e\n\u003ctd\u003e80 mA at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e10-95%, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Weight\u003c\/td\u003e\n\u003ctd\u003e0.113 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoating\u003c\/td\u003e\n\u003ctd\u003eStandard version\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEAN\u003c\/td\u003e\n\u003ctd\u003e3595863910131\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEU Directives\u003c\/td\u003e\n\u003ctd\u003e2014\/35\/EU; 2014\/30\/EU\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the maximum counting frequency of the BMXEHC0800?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The module supports a maximum counting frequency of 10 kHz. This allows it to process pulse signals from compatible proximity sensors and incremental encoders for high-speed counting applications.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Which sensors and encoders can be connected to the BMXEHC0800?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: It supports 2-wire and 3-wire proximity sensors operating at 19.2-30 VDC and incremental encoders with 10-30 V push-pull outputs. The connected signal source must also meet the specified logic voltage and current thresholds.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What power requirements should be considered when installing this module?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The BMXEHC0800 requires 200 mA from the 3.3 VDC backplane bus and 80 mA from the 24 VDC sensor supply. Both values should be included when checking rack power capacity and sensor supply requirements.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":68121699942685,"sku":"BMXEHC0800","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/BMXEHC0800.jpg?v=1794997160","url":"https:\/\/www.6gcontrols.com\/az\/products\/schneider-electric-bmxehc0800-modicon-x80-high-speed-counter-module","provider":"6G Controls","version":"1.0","type":"link"}