{"product_id":"yokogawa-adv151-e60-32-channel-digital-input-module","title":"YOKOGAWA ADV151-E60 modul digitálních vstupů skladem","description":"\u003cp\u003eThe \u003cstrong\u003eYokogawa ADV151-E60\u003c\/strong\u003e is a 32-channel digital input module designed for the FIO (Fieldbus Independent I\/O) system. It accepts 24 V DC discrete signals in sink or source configurations and provides separate input characteristics for status and pushbutton signals. The module supports pressure clamp terminals and dedicated cable connections for field signal wiring.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eInput Configuration and Signal Characteristics\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe ADV151-E60 provides 32 digital input channels with a rated input voltage of 24 V DC. Its ON and OFF voltage thresholds define the signal recognition range, while the 30.0 V DC maximum allowable input voltage specifies the upper limit for the applied input signal.\u003c\/p\u003e\n\u003cp\u003eThe module supports both sink and source input configurations. Each channel draws 4.1 mA +\/-20% at the rated input voltage, which is relevant when checking field contact ratings and the electrical loading of connected devices.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eSignal Response and Input Functions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module supports status input and pushbutton input functions, with different timing characteristics for each:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eStatus input:\u003c\/strong\u003e Input response time of 8 ms or less.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePushbutton input:\u003c\/strong\u003e Minimum ON detection time of 20 ms.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePushbutton input:\u003c\/strong\u003e Maximum ON\/OFF cycle frequency of 25 Hz.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThese timing specifications should be considered when selecting the module for discrete signal acquisition. In particular, the 20 ms minimum ON detection time applies to pushbutton input and should not be confused with the status input response time.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eElectrical Isolation and Power Consumption\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe input signal circuits have a withstand voltage of 2 kV AC for 1 minute between the input signal and the system. The withstand voltage between commons is 500 V AC for 1 minute, with a separate common for every 16 input channels.\u003c\/p\u003e\n\u003cp\u003eMaximum current consumption is 500 mA from the 5 V DC supply. This value should be included when checking the power capacity available for the installed I\/O configuration.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eADV151-E60\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eYokogawa\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDigital Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem\u003c\/td\u003e\n\u003ctd\u003eFIO (Fieldbus Independent I\/O)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Input Channels\u003c\/td\u003e\n\u003ctd\u003e32\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Input Voltage\u003c\/td\u003e\n\u003ctd\u003e24 V DC (sink\/source)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput ON Voltage\u003c\/td\u003e\n\u003ctd\u003e18 to 26.4 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput OFF Voltage\u003c\/td\u003e\n\u003ctd\u003e5.0 V DC or less\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e4.1 mA +\/-20% \/ channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Allowable Input Voltage\u003c\/td\u003e\n\u003ctd\u003e30.0 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWithstanding Voltage (Signal to System)\u003c\/td\u003e\n\u003ctd\u003e2 kV AC, 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWithstanding Voltage (Between Commons)\u003c\/td\u003e\n\u003ctd\u003e500 V AC, 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Configuration\u003c\/td\u003e\n\u003ctd\u003eCommon every 16 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Response Time\u003c\/td\u003e\n\u003ctd\u003e8 ms or less (status input)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Current Consumption\u003c\/td\u003e\n\u003ctd\u003e500 mA (5 V DC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExternal Connection\u003c\/td\u003e\n\u003ctd\u003ePressure clamp terminal, dedicated cable (AKB331), MIL connector cable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.3 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eExternal Connections and Installation Considerations\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe ADV151-E60 supports three external connection options: pressure clamp terminals, the dedicated AKB331 cable, and MIL connector cables. The selected connection method affects the applicable wiring arrangement and electrical isolation conditions.\u003c\/p\u003e\n\u003cp\u003eWhen using a dedicated cable, the withstand voltage between the input signal and system is limited to 500 V AC. For MIL connector cables, the applicable withstand voltage depends on the electrical specifications of the cable.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the ADV151-E60 support Sequence of Events (SOE) input?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. The ADV151-E variant supports SOE data capture. This function allows the system to record discrete input events for sequence analysis and event monitoring.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can the ADV151-E60 be used for pushbutton input?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The ADV151-E and ADV151-P variants have different function allocations. The manufacturer's specification identifies SOE input for ADV151-E and pushbutton edge counting for ADV151-P. These functions should not be treated as interchangeable.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What should be checked when connecting the 32 input channels?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The module uses a common connection for every 16 channels. All 24 V DC input signals connected to the module must have the same polarity. The selected cable type should also be checked against the applicable withstand-voltage requirements.\u003c\/p\u003e","brand":"6G Controls","offers":[{"title":"Default Title","offer_id":52752235790621,"sku":"ADV151-E60","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/ADV151-E602.jpg?v=1795768509","url":"https:\/\/www.6gcontrols.com\/cs\/products\/yokogawa-adv151-e60-32-channel-digital-input-module","provider":"6G Controls","version":"1.0","type":"link"}