{"product_id":"honeywell-fc-tdol-0724p-line-monitored-relay-contact-digital-output-assembly","title":"Honeywell FC-TDOL-0724P Line-Monitored Relay Contact Digital Output Assembly","description":"\u003cp\u003eThe Honeywell FC-TDOL-0724P is a field termination assembly for 24 VDC line-monitored digital outputs in the Safety Manager system. It provides seven fused relay contact outputs, each rated at 2 A, for non-safety-related resistive or inductive loads up to 50 W. Dedicated monitoring circuits detect short circuits and lead breakages when outputs are energized or de-energized, in conjunction with compatible Safety Manager digital input and output modules and the required application software.\u003c\/p\u003e\n\u003ch3\u003eOutput Configuration and Line Monitoring\u003c\/h3\u003e\n\u003cp\u003eThe FC-TDOL-0724P provides seven individually fused relay contact outputs. Each channel supports a maximum output current of 2 A, subject to the load rating, fuse protection, and temperature-dependent derating limits. The specified field supply is 24 VDC +\/- 20%.\u003c\/p\u003e\n\u003cp\u003eEach channel includes a dedicated line-monitoring circuit for detecting wiring faults in both the energized and de-energized states. The short-circuit detection load threshold is specified as 200 ohm to 400 ohm. The diagnostic function requires coordinated operation with standard Safety Manager DI and DO modules configured for redundant or non-redundant I\/O, together with the applicable software from the Safety Manager Function Library.\u003c\/p\u003e\n\u003ch3\u003eElectrical Ratings\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFC-TDOL-0724P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eLine-Monitored Relay Contact Digital Output Field Termination Assembly\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Output Channels\u003c\/td\u003e\n\u003ctd\u003e7\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Supply Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC +\/- 20%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Output Current\u003c\/td\u003e\n\u003ctd\u003e2 A per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported Load\u003c\/td\u003e\n\u003ctd\u003eNon-safety-related resistive or inductive loads\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Field Load\u003c\/td\u003e\n\u003ctd\u003e50 W per output, as specified in the product description\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Load Resistance\u003c\/td\u003e\n\u003ctd\u003e2200 ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLoad Leakage Current\u003c\/td\u003e\n\u003ctd\u003eApprox. 1.1 mA at 24 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage, OFF State\u003c\/td\u003e\n\u003ctd\u003e90% of output supply voltage, as specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage, ON State\u003c\/td\u003e\n\u003ctd\u003e100% of output supply voltage, as specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShort-Circuit Detection Threshold\u003c\/td\u003e\n\u003ctd\u003e200 ohm \u0026lt; RTh \u0026lt; 400 ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInductive Load Suppression\u003c\/td\u003e\n\u003ctd\u003eSpark suppression diode specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelay Maximum Switched Power\u003c\/td\u003e\n\u003ctd\u003e150 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Relay Life\u003c\/td\u003e\n\u003ctd\u003e100,000 switching operations\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMechanical Relay Life\u003c\/td\u003e\n\u003ctd\u003e30,000,000 switching operations\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFuse Protection and Derating\u003c\/h3\u003e\n\u003cp\u003eEach output uses a 2 A fuse with the following specifications.\u003c\/p\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eFuse Manufacturer\u003c\/td\u003e\n\u003ctd\u003eLittelfuse\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFuse Part Number\u003c\/td\u003e\n\u003ctd\u003e0213002\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFuse Dimensions\u003c\/td\u003e\n\u003ctd\u003e5 x 20 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAC Voltage Rating\u003c\/td\u003e\n\u003ctd\u003e250 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDC Voltage Rating\u003c\/td\u003e\n\u003ctd\u003e300 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Derating\u003c\/td\u003e\n\u003ctd\u003eLinear from 2 A at 25 deg C to 1.9 A at 70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eThe fuse rating defines the specified protection component, not an unrestricted continuous load rating under all conditions. The stated current derating should be considered when evaluating operation at elevated temperatures. The product description limits field loads to 50 W, even though the relay contact specification lists a maximum switched power of 150 W; these figures describe different stated limits and should not be treated as interchangeable.\u003c\/p\u003e\n\u003ch3\u003ePower Consumption\u003c\/h3\u003e\n\u003cp\u003eThe assembly uses the 24 VDC field supply and associated Safety Manager I\/O modules for its output and read-back functions. The listed consumption values distinguish the field supply from current drawn through the associated I\/O modules.\u003c\/p\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Supply Consumption\u003c\/td\u003e\n\u003ctd\u003eLess than 9 mA with all channels OFF\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelay and Channel 8 Consumption\u003c\/td\u003e\n\u003ctd\u003eApprox. 200 mA from TSDO-0824; maximum 250 mA at Vmax\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRead-Back Circuit Consumption\u003c\/td\u003e\n\u003ctd\u003eLess than 110 mA with a single SDI-1624\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRead-Back Circuit Consumption, Redundant Configuration\u003c\/td\u003e\n\u003ctd\u003eLess than 210 mA with redundant SDI-1624\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Read-Back Consumption\u003c\/td\u003e\n\u003ctd\u003e275 mA at Vmax\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eThe listed values apply to different supply paths and circuit configurations. They should not be added together as a single power-consumption figure without confirming the applicable wiring and system configuration.\u003c\/p\u003e\n\u003ch3\u003eMechanical Design and Field Termination\u003c\/h3\u003e\n\u003cp\u003eThe assembly mounts on standard TS32 or TS35 x 7.5 DIN EN rails. Seven pairs of screw terminals provide the field wiring connections, while a keyed two-pole connector provides the common supply connection.\u003c\/p\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (L x W x H)\u003c\/td\u003e\n\u003ctd\u003e240 x 109 x 80 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (L x W x H)\u003c\/td\u003e\n\u003ctd\u003e9.45 x 4.29 x 3.15 in\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRequired DIN Rail Length\u003c\/td\u003e\n\u003ctd\u003e241 mm (9.49 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported DIN Rails\u003c\/td\u003e\n\u003ctd\u003eTS32 \/ TS35 x 7.5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Wiring Terminals\u003c\/td\u003e\n\u003ctd\u003e7 pairs of screw terminals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Field Wire Diameter\u003c\/td\u003e\n\u003ctd\u003e2.5 mm (AWG 14)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Wire Strip Length\u003c\/td\u003e\n\u003ctd\u003e7 mm (0.28 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Terminal Tightening Torque\u003c\/td\u003e\n\u003ctd\u003e0.5 Nm (0.37 ft-lb)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Connector\u003c\/td\u003e\n\u003ctd\u003eKeyed two-pole header\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Connector Manufacturer and Type\u003c\/td\u003e\n\u003ctd\u003eWeidmuller BVZ 7.62HP\/02\/180F SN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Connector Key\u003c\/td\u003e\n\u003ctd\u003eWeidmuller BV\/SV7.62HP KO\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Connector Wire Strip Length\u003c\/td\u003e\n\u003ctd\u003e8 mm, as specified in the source data\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnectable Power Conductor Range\u003c\/td\u003e\n\u003ctd\u003e0.5-6 mm, as specified in the source data\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eThe field terminals and common supply connector have separate wiring requirements. Confirm conductor size, stripping length, terminal torque, and connector keying before installation. The supplied dimensions and rail length should also be checked against the available cabinet space.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Can the FC-TDOL-0724P be used for safety-related field loads?\u003c\/p\u003e\n\u003cp\u003eA: The specified application is for non-safety-related resistive or inductive loads up to 50 W per output. Its line-monitoring capability does not, by itself, establish a safety integrity rating for the field termination assembly.\u003c\/p\u003e\n\u003cp\u003eQ: Which Safety Manager I\/O modules are required for line monitoring?\u003c\/p\u003e\n\u003cp\u003eA: The documented configuration uses the SDI-1624 digital input module and SDO-0824 digital output module. Both are required for the stated line-monitoring arrangement, with the overall configuration and application software selected for redundant or non-redundant I\/O.\u003c\/p\u003e\n\u003cp\u003eQ: What load conditions must be checked before connecting a field device?\u003c\/p\u003e\n\u003cp\u003eA: Verify the 24 VDC +\/- 20% supply, 2 A channel fuse, 50 W field-load limit, relay contact rating, and temperature-dependent current derating. Inductive loads must also meet the specified spark-suppression diode requirement.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":67834371604765,"sku":"FC-TDOL-0724P","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/FC-TDOL-07241.jpg?v=1792489883","url":"https:\/\/www.6gcontrols.com\/de\/products\/honeywell-fc-tdol-0724p-line-monitored-relay-contact-digital-output-assembly","provider":"6G Controls","version":"1.0","type":"link"}