{"product_id":"honeywell-fs-tpsu-2430-dc-dc-converter","title":"Honeywell FS-TPSU-2430 modul sustava Safety Manager, izvrsna kvaliteta","description":"\u003cp\u003eThe Honeywell FS-TPSU-2430 is a DC\/DC power converter designed for the Honeywell Safety Manager system. It converts a nominal 24 VDC input into an isolated 30 VDC output rated at 1 A. The converter supplies external power to Field Termination Assemblies (FTAs), including analog input assemblies, and provides local voltage indication and relay-based output status monitoring.\u003c\/p\u003e\n\u003ch3\u003ePower Conversion and Output Monitoring\u003c\/h3\u003e\n\u003cp\u003eThe FS-TPSU-2430 provides regulated 30 VDC power from a 24 VDC supply. Its galvanically isolated output separates the incoming supply from the field-side power circuit, supporting the external power requirements of compatible FTA configurations.\u003c\/p\u003e\n\u003cp\u003eThe module includes output voltage monitoring, a local LED indicator, and a readback relay contact. When the DC\/DC output voltage is within the acceptable range, the LED illuminates and the readback relay contact closes. This allows the system to monitor the availability of the field-side power supply.\u003c\/p\u003e\n\u003ch3\u003eFTA Power Distribution\u003c\/h3\u003e\n\u003cp\u003eThe converter provides six pairs of output terminals for distributing 30 VDC and 0 VDC to external circuits. It is intended for use with Safety Manager FTAs, including the TSAI-1620m and TSHART-1620m analog input assemblies.\u003c\/p\u003e\n\u003cp\u003eThe six output connections provide multiple field power termination points. The total output current remains limited to 1 A; the rating is not 1 A per terminal pair.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFS-TPSU-2430\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDC\/DC Converter\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem\u003c\/td\u003e\n\u003ctd\u003eSafety Manager\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Input Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage Range\u003c\/td\u003e\n\u003ctd\u003e18-36 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInrush Current\u003c\/td\u003e\n\u003ctd\u003e75%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSwitching Frequency\u003c\/td\u003e\n\u003ctd\u003e\u0026gt; 25 kHz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGalvanic Isolation\u003c\/td\u003e\n\u003ctd\u003eInput to output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Voltage\u003c\/td\u003e\n\u003ctd\u003e2000 VAC (1 min)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eReadback Relay Contact Rating\u003c\/td\u003e\n\u003ctd\u003e36 VDC \/ 40 mA; 30 VAC \/ 40 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eApprovals\u003c\/td\u003e\n\u003ctd\u003eCE, TUV, UL, CSA, FM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafety Class\u003c\/td\u003e\n\u003ctd\u003eUp to and including SIL 3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMTBF\u003c\/td\u003e\n\u003ctd\u003eApproximately 400,000 hours\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003eDIN EN rail TS32 \/ TS35 x 7.5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e150 x 70 x 62.3 mm (L x W x H)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUsed Rail Length\u003c\/td\u003e\n\u003ctd\u003e151 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFuse Rating\u003c\/td\u003e\n\u003ctd\u003e3.15 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFuse Dimensions\u003c\/td\u003e\n\u003ctd\u003e5 x 20 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Wire Size\u003c\/td\u003e\n\u003ctd\u003e2.5 mm2 (AWG 14)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWire Strip Length\u003c\/td\u003e\n\u003ctd\u003e7 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Tightening Torque\u003c\/td\u003e\n\u003ctd\u003e0.5 Nm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-5 to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCooling\u003c\/td\u003e\n\u003ctd\u003eNatural convection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.18 lbs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eElectrical Connections\u003c\/h3\u003e\n\u003cp\u003eThe FS-TPSU-2430 uses screw terminals for incoming power, output distribution, and voltage-status feedback.\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eInput terminals 3 and 4: 24 VDC IN+ and 24 VDC IN-.\u003c\/li\u003e\n\u003cli\u003eReadback terminals 1 and 2: Relay status contact.\u003c\/li\u003e\n\u003cli\u003eOutput terminals 1A-6A: 30 VDC OUT.\u003c\/li\u003e\n\u003cli\u003eOutput terminals 1B-6B: 0 VDC OUT, with terminal 6B also designated for the grounding arrangement.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe output-side grounding arrangement must follow the Safety Manager installation requirements. For predictable system behavior under a field-side short-to-earth condition, the 0 VDC output must be connected to ground or a dedicated Earth Leakage Detector (ELD) must be provided for the converter.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What is the output voltage and current capacity of the FS-TPSU-2430?\u003c\/p\u003e\n\u003cp\u003eA: It provides a regulated 30 VDC output with a rated current of 1 A. The total current capacity is shared across its six output terminal pairs.\u003c\/p\u003e\n\u003cp\u003eQ: Which Honeywell modules can receive power from the FS-TPSU-2430?\u003c\/p\u003e\n\u003cp\u003eA: The converter is designed to supply other Safety Manager FTAs, including the TSAI-1620m and TSHART-1620m analog input assemblies. The actual power configuration must account for the connected field-device load.\u003c\/p\u003e\n\u003cp\u003eQ: How can the output power status be monitored?\u003c\/p\u003e\n\u003cp\u003eA: The module provides a local LED and a readback relay contact. The LED illuminates and the relay contact closes when the output voltage is OK. The relay contact can be used for external power-status monitoring.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52750320664861,"sku":"FS-TPSU-2430","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/80363975-1501_1000_416af248-fa1c-4b1d-a4d4-1089aa8c922e.jpg?v=1787045505","url":"https:\/\/www.6gcontrols.com\/hr\/products\/honeywell-fs-tpsu-2430-dc-dc-converter","provider":"6G Controls","version":"1.0","type":"link"}