{"product_id":"honeywell-tk-ccr013-redundant-controlnet-interface-module","title":"Honeywell TK-CCR013 Redundant ControlNet Interface Module","description":"\u003cp\u003eThe Honeywell TK-CCR013 is a dual-media redundant ControlNet interface module designed for communication within Honeywell Experion PKS control systems. It provides a redundant network interface for controller and system communication. The TK prefix identifies the conformal-coated version of the ControlNet module, distinguishing it from the corresponding TC-series version.\u003c\/p\u003e\n\u003ch3\u003eCommunication Function\u003c\/h3\u003e\n\u003cp\u003eThe TK-CCR013 belongs to the Series D ControlNet interface family and uses dual-media network redundancy. In a redundant network arrangement, the dual-media interface provides two communication paths, allowing the system architecture to maintain network connectivity through its redundant media configuration.\u003c\/p\u003e\n\u003cp\u003eIt is intended for ControlNet-based Experion PKS architectures. It should not be confused with a single-media ControlNet interface or an Ethernet communication module.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eTK-CCR013\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eRedundant ControlNet Interface Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNetwork Type\u003c\/td\u003e\n\u003ctd\u003eControlNet\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNetwork Configuration\u003c\/td\u003e\n\u003ctd\u003eDual-Media \/ Redundant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Series\u003c\/td\u003e\n\u003ctd\u003eSeries D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoating\u003c\/td\u003e\n\u003ctd\u003eConformal-coated version\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupply Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC (as listed in supplied product information)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.35 lbs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eNetwork Configuration and Compatibility\u003c\/h3\u003e\n\u003cp\u003eThe module provides separate A and B connections for dual-media ControlNet networks. Honeywell documentation specifies that the A and B trunk cable drop connections must be connected to their corresponding module connectors when operating in a redundant-media configuration.\u003c\/p\u003e\n\u003cp\u003eA dual-media module can also operate in a single-media network configuration. In that arrangement, the network drop cable must connect to port A.\u003c\/p\u003e\n\u003ch3\u003eReplacement and Lifecycle Information\u003c\/h3\u003e\n\u003cp\u003eThe TK-CCR013 is identified as an obsolete Series D module in Honeywell's Experion PKS Control Hardware Installation Guide (Release 516).\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eSuccessor model: TK-CCR014, Series E dual-media redundant ControlNet interface.\u003c\/li\u003e\n\u003cli\u003eReplacement consideration: If a CCR013 module fails in a redundant chassis pair, Honeywell specifies replacing both partner modules with Series E CCR014 modules.\u003c\/li\u003e\n\u003cli\u003eBoth modules in a redundant chassis pair must be the same type.\u003c\/li\u003e\n\u003cli\u003eReplacement firmware and startup diagnostics must be checked before returning the system to operation.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What is the difference between TK-CCR013 and a single-media ControlNet module?\u003c\/p\u003e\n\u003cp\u003eA: The TK-CCR013 supports dual-media ControlNet communication through separate A and B network connections. A single-media module uses only one network connection and does not provide the same dual-media configuration.\u003c\/p\u003e\n\u003cp\u003eQ: Can the TK-CCR013 be replaced directly with a TK-CCR014?\u003c\/p\u003e\n\u003cp\u003eA: The TK-CCR014 is the documented Series E successor. However, in a redundant chassis pair, both partner CCR013 modules must be replaced with CCR014 modules of the same type. Firmware compatibility and system configuration must also be verified.\u003c\/p\u003e\n\u003cp\u003eQ: Is the TK-CCR013 hot-swappable?\u003c\/p\u003e\n\u003cp\u003eA: Honeywell's installation procedure specifies switching off chassis power before removing the ControlNet module. Do not assume that this model supports removal under power.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":67965530505501,"sku":"TK-CCR013","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/TK-CCR0132.jpg?v=1793794570","url":"https:\/\/www.6gcontrols.com\/hr\/products\/honeywell-tk-ccr013-redundant-controlnet-interface-module","provider":"6G Controls","version":"1.0","type":"link"}