
Beri tahu melalui email saat produk ini tersedia
- Deskripsi
- Reviews
- Pengiriman & Pembayaran
Configured for multi-range temperature and low-level analog measurement in the Modicon X80 platform, the Schneider Electric BMXART0814H (BMXART0814H Analog Input Module) provides eight isolated analog input channels with 15 bits + sign resolution. The module supports RTD, thermocouple, resistance, and low-level voltage inputs through a 40-way electrical connection.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMXART0814H |
| Brand | Schneider Electric |
| Product Type | Analog Input Module |
| Platform | Modicon X80 |
| Application | Severe environments |
| Number of Inputs | 8 |
| Input Isolation | Isolated between channels |
| Input Level | Low level |
| Analog Input Resolution | 15 bits + sign |
| A/D Conversion | Sigma delta, 16 bits |
| Input Types | Voltage, resistance, RTD, thermocouple |
| Voltage Ranges | +/- 40 mV, +/- 80 mV, +/- 160 mV, +/- 320 mV, +/- 640 mV, +/- 1.28 V |
| Resistance Inputs | 400 Ohm and 4000 Ohm, 2/3/4 wire |
| RTD Inputs | Cu 10, Ni 100, Ni 1000, Pt 100, Pt 1000 |
| Thermocouple Types | B, E, J, K, L, N, R, S, T, U |
| Cold Junction Compensation | External Pt100 probe |
| Common Mode Rejection | 120 dB at 50/60 Hz |
| Differential Mode Rejection | 60 dB at 50/60 Hz |
| Digital Filtering | First order |
| Temperature Probe Read Cycle | 400 ms |
| Thermocouple Read Cycle | 200 ms |
| Measurement Resolution | 0.1 deg C for temperature inputs |
| Maximum Wiring Resistance | Up to 500 Ohm depending on sensor and wiring configuration |
| Recalibration | Internal |
| Diagnostic LEDs | RUN, channel diagnostic, ERR, I/O |
| Electrical Connection | 40-way, 2 connectors |
| Current Consumption | 150 mA at 3.3 VDC; 50 mA at 24 VDC |
| Weight | 0.165 kg |
| Operating Temp | -25 to 70 deg C |
| Storage Temp | -40 to 85 deg C |
| Relative Humidity | 5-95% at 55 deg C, non-condensing |
| Protection Rating | IP20 |
| Vibration Resistance | 3 gn |
| Shock Resistance | 30 gn |
| Operating Altitude | 0 to 2000 m; 2000 to 5000 m with derating |
| Protective Treatment | Conformal coating |
| Certifications | CSA, UL, IEC-Ex, CE, Merchant Navy, RCM, ATEX, EAC |
| Standards | IEC 61131-2, IEC 61000-6-4, IEC 61000-6-2, EN 61010-2-201 |
PLC Backplane and Analog Signal Characteristics
The BMXART0814H is an X80 analog input module with eight isolated channels. Its input circuitry accepts low-level voltage signals, resistance measurements, RTD sensors, and thermocouples. The sigma-delta converter provides 16-bit internal conversion, while the specified analog input resolution is 15 bits + sign.
For temperature measurement, the module supports multiple IEC and UL/JIS sensor configurations. External Pt100 cold junction compensation is specified for thermocouple measurement. Open-circuit detection is provided for supported RTD and thermocouple inputs.
The module provides 120 dB common-mode rejection and 60 dB differential-mode rejection at 50/60 Hz. These characteristics apply to the analog signal acquisition path and should be considered when routing sensor wiring near power conductors or switching equipment.
Frequently Asked Questions
Q: What sensor types can the BMXART0814H accept?
A: It supports Cu 10, Ni 100, Ni 1000, Pt 100, Pt 1000, thermocouples B/E/J/K/L/N/R/S/T/U, 400 Ohm and 4000 Ohm resistance inputs, and low-level voltage ranges from +/- 40 mV to +/- 1.28 V.
Q: How is thermocouple cold junction compensation implemented?
A: Cold junction compensation is specified as external compensation using a Pt100 probe.
Q: Does the module provide channel isolation and diagnostics?
A: Yes. The inputs are isolated between channels, and the front diagnostics include a RUN LED, one diagnostic LED per channel, ERR, and I/O indicators.
Field Installation Guidelines
Install the BMXART0814H on the applicable Modicon X80 rack and establish the electrical connection through the specified 40-way connector arrangement.
Route thermocouple and RTD wiring separately from high-current and switching circuits where practical. Maintain appropriate shielding and grounding practices for low-level analog signals. Avoid creating unintended ground loops between sensor circuits, shields, and cabinet grounding points.
Verify the selected input type and measurement range in the PAC configuration before connecting field sensors. For RTD measurements, select the correct 2-wire, 3-wire, or 4-wire configuration and remain within the specified wiring resistance limit.
For thermocouple channels, verify the configured thermocouple type and the external Pt100 cold junction compensation arrangement. Confirm sensor polarity before commissioning.
The conformal-coated BMXART0814H is specified for operation from -25 to 70 deg C and IP20 protection. The enclosure and cabinet installation should provide the required environmental protection because IP20 does not provide protection against water or dust ingress.
Pembayaran: T/T, Western Union.
Pelabuhan pengiriman: Xiamen.
Waktu produksi: Biasanya 1–3 hari kerja setelah pembayaran dikonfirmasi (tergantung ketersediaan stok).
Pengiriman ke seluruh dunia: Kami mengirimkan komponen otomasi industri kepada pelanggan di seluruh dunia. Biaya pengiriman akan dicantumkan dalam RFQ Anda.
F.A.Q.
Pertanyaan umum tentang penawaran harga, pengiriman, garansi, dan pengembalian barangKlik Minta Penawaran di halaman produk dan kirimkan nomor komponen, jumlah yang diperlukan, serta negara tujuan kepada kami. Tim penjualan kami akan membalas dengan informasi ketersediaan terkini, harga, dan perkiraan waktu pengiriman.
Barang yang tersedia biasanya disiapkan setelah pembayaran dan konfirmasi pesanan. Sebagian besar pesanan dikirim dari gudang kami di Tiongkok, meskipun lokasi pengiriman dapat berbeda tergantung ketersediaan stok saat ini.
Ya. Kami mengirimkan suku cadang otomasi industri kepada pelanggan di seluruh dunia. Biaya pengiriman dan waktu transit bergantung pada tujuan, berat paket, ukuran produk, serta persyaratan impor setempat.
Kami biasanya menggunakan DHL, FedEx, UPS, dan layanan kurir internasional lainnya. Jasa pengiriman dapat dipilih sesuai dengan tujuan, kecepatan pengiriman, ukuran kiriman, dan kebutuhan pelanggan.
Produk kami umumnya dilindungi oleh garansi 12 bulan. Produk yang memenuhi syarat juga dapat dikembalikan berdasarkan kebijakan pengembalian dana 30 hari kami. Harap hubungi tim kami sebelum mengembalikan barang apa pun untuk mengonfirmasi ketentuan yang berlaku dan petunjuk pengembalian.
Anda mungkin juga menyukai
Pos Blog
Berita otomasi industri, panduan teknis, dan pembaruan produk.
