{"product_id":"schneider-electric-bmxddm3202k-modicon-x80-discrete-i-o-module","title":"Schneider Electric BMXDDM3202K Modicon X80 Discrete I\/O Module","description":"\u003cp\u003eThe \u003cstrong\u003eBMXDDM3202K\u003c\/strong\u003e is a 24 VDC discrete mixed input\/output module in the Schneider Electric Modicon X80 platform. It combines 16 positive-logic (sink) discrete inputs and 16 positive-logic (source) solid-state outputs within a single rack slot, using a 40-pin front connector for high-density field wiring in Modicon M340 and M580 automation architectures.\u003c\/p\u003e\n\u003ch3\u003eChannel Configuration and Electrical Characteristics\u003c\/h3\u003e\n\u003cp\u003eThe input section meets IEC\/EN 61131-2 Type 3 requirements with a 9600 Ohm input impedance, a typical response time of 4 ms (7 ms maximum), and sensor voltage supervision that flags faults below 14 VDC and confirms normal status above 18 VDC.\u003c\/p\u003e\n\u003cp\u003eThe output section provides 16 solid-state channels rated at 0.1 A nominal per channel (0.125 A maximum per channel, 3.2 A maximum per module) with a 1.2 ms output response time and a maximum voltage drop below 1.5 V in State 1. Up to 3 outputs can be connected in parallel to drive higher-current loads, and each output channel integrates reverse polarity and overvoltage protection.\u003c\/p\u003e\n\u003ch3\u003eSystem Compatibility and Mounting\u003c\/h3\u003e\n\u003cp\u003eThe module operates across Modicon M340 and Modicon M580 PLC systems in both local racks and remote I\/O drops. It draws up to 166 mA from the 3.3 VDC backplane bus and up to 104 mA at 24 VDC.\u003c\/p\u003e\n\u003cp\u003eThis standard-version unit features IP20 ingress protection and TC (all-climate) treatment for operation from 0 deg C to 60 deg C. Field signals connect via a 40-pin removable terminal block or pre-wired cordsets such as the BMXFCW503 paired with Modicon ABE7 Telefast sub-bases. The module installs directly into a Modicon X80 rack and secures with two captive mounting screws.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXDDM3202K\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDiscrete Mixed I\/O Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiscrete Inputs\u003c\/td\u003e\n\u003ctd\u003e16 channels, 24 VDC, positive logic (IEC\/EN 61131-2 Type 3)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e9600 Ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Response Time\u003c\/td\u003e\n\u003ctd\u003e4 ms typical, 7 ms maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSensor Voltage Detection Threshold\u003c\/td\u003e\n\u003ctd\u003eLess than 14 VDC fault; greater than 18 VDC OK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiscrete Outputs\u003c\/td\u003e\n\u003ctd\u003e16 channels, 24 VDC, positive logic solid-state\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Output Current\u003c\/td\u003e\n\u003ctd\u003e0.1 A per channel (0.125 A max per channel, 3.2 A max per module)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Response Time\u003c\/td\u003e\n\u003ctd\u003e1.2 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage Drop\u003c\/td\u003e\n\u003ctd\u003eLess than 1.5 V in State 1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Paralleling\u003c\/td\u003e\n\u003ctd\u003eYes, maximum 3 outputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResistive Load Impedance\u003c\/td\u003e\n\u003ctd\u003eLess than or equal to 220 Ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Overload Time\u003c\/td\u003e\n\u003ctd\u003e15 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSwitching Frequency\u003c\/td\u003e\n\u003ctd\u003e0.5 \/ LI^2 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Features\u003c\/td\u003e\n\u003ctd\u003eReverse polarity protection (input and output), output overvoltage protection, external 0.5 A fast-blow fuse per input group\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003eLess than or equal to 104 mA at 24 VDC; less than or equal to 166 mA at 3.3 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDielectric Strength\u003c\/td\u003e\n\u003ctd\u003e1500 VAC at 50\/60 Hz for 1 min (output\/ground, output\/internal logic, primary\/secondary); 500 VDC for 1 min (between input and output groups)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInsulation Resistance\u003c\/td\u003e\n\u003ctd\u003eGreater than 10 MOhm at 500 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFront Connector\u003c\/td\u003e\n\u003ctd\u003e40-pin connector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAmbient Operating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 deg C to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5% to 95% at 55 deg C, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDegree of Protection\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoating\u003c\/td\u003e\n\u003ctd\u003eStandard version (TC all-climate treatment)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMTBF\u003c\/td\u003e\n\u003ctd\u003e429,248 hours (430,000 hours nominal)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.11 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCertifications and Standards\u003c\/td\u003e\n\u003ctd\u003eCE, UL, CSA, RCM, EAC, UKCA, Merchant Navy; EN 61131-2 Type 3, EN 61000-6-5, EN 61850-3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How does the BMXDDM3202K differ from the BMXDDM3202KH?A: The BMXDDM3202K is the standard-coated version rated for 0 deg C to 60 deg C, whereas the \"H\" suffix variants in the Modicon X80 family add conformal coating and extended temperature ratings for harsh environments.\u003c\/p\u003e\n\u003cp\u003eQ: Can outputs on the BMXDDM3202K be wired in parallel for higher load current?A: Yes, up to 3 output channels can be connected in parallel on this module to increase current capacity, provided the total module current does not exceed 3.2 A.\u003c\/p\u003e\n\u003cp\u003eQ: What wiring accessories are required to connect field devices to this 40-pin module?A: The module uses a 40-pin front interface and requires a compatible 40-pin removable terminal block or pre-wired cordsets (such as BMXFCW503) connected to Modicon ABE7 Telefast wiring bases.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":68110188871965,"sku":"BMXDDM3202K","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/BMXDDM3202K2.jpg?v=1794910389","url":"https:\/\/www.6gcontrols.com\/ms\/products\/schneider-electric-bmxddm3202k-modicon-x80-discrete-i-o-module","provider":"6G Controls","version":"1.0","type":"link"}