The Schneider Electric BMXDRA0805H is an 8-channel normally open (NO) relay discrete output module designed for the Modicon X80 common I/O platform, supporting Modicon M580 and Modicon M340 Programmable Automation Controllers (PAC). Engineered with conformal coating and an extended operating temperature range of -25 deg C to +70 deg C, this ruggedized module switches 24 to 240 V AC and 24 V DC loads in severe industrial environments.
Output Switching and Electrical Performance
The BMXDRA0805H provides 8 normally open relay output channels configured with positive discrete output logic. It accommodates a nominal load voltage range of 24 to 240 V AC (19 to 264 V AC operating limits) and 12 to 24 V DC (10 to 34 V DC operating limits), requiring a minimum switching load of 10 mA at 5 V DC to ensure reliable contact closure.
Backplane power draw is 79 mA typical at 3.3 V DC. Output switching response times are less than 10 ms for activation and less than 8 ms for deactivation, making the module suitable for general relay control of solenoids, contactors, and pilot indicators. Channel-to-bus isolation is rated at 2000 V AC (50/60 Hz for 1 minute) with an insulation resistance exceeding 10 MOhm at 500 V DC.
Ruggedized Construction and Environmental Ratings
The "H" suffix designates the hardened version featuring conformal coating on the internal printed circuit boards. This protective treatment enables continuous operation from -25 deg C to +70 deg C and up to 95% non-condensing relative humidity at 55 deg C.
The IP20-rated housing is qualified against corrosive and particulate contaminants under standard industrial classifications:
- Gas resistance: Class Gx and Class 3C4
- Dust and sand resistance: Class 3S4
- Salt mist resistance: Level 2
- Mold growth and fungal spore resistance: Class 3B2
Lifecycle Status and Replacement
Schneider Electric discontinued the BMXDRA0805H on July 1, 2022, with end-of-service scheduled for June 30, 2030. The official direct replacement is the Schneider Electric BMXDRA0815H, which retains the 8 NO relay output form factor and conformal coating while expanding the nominal DC switching capability to 24 to 125 V DC.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXDRA0805H |
| Brand | Schneider Electric |
| Product Series | Modicon X80 |
| Product Type | Discrete Output Module |
| Compatible Controllers | Modicon M580, Modicon M340 |
| Number of Outputs | 8 NO Relay Outputs |
| Output Logic | Positive |
| Nominal Output Voltage | 24 to 240 V AC / 12 to 24 V DC |
| Operating Voltage Range | 19 to 264 V AC / 10 to 34 V DC |
| Minimum Switching Current | 10 mA at 5 V DC |
| Backplane Current Consumption | 79 mA typical at 3.3 V DC |
| Output Response Time | < 10 ms (activation), < 8 ms (deactivation) |
| Dielectric Strength | 2000 V AC at 50/60 Hz for 1 min |
| Insulation Resistance | > 10 MOhm at 500 V DC |
| MTBF | 2,119,902 hours |
| Protective Treatment | Conformal coating |
| Operating Temperature | -25 deg C to +70 deg C |
| Relative Humidity | 5% to 95% at 55 deg C (without condensation) |
| Enclosure Protection | IP20 |
| Certifications | ATEX, CE, CSA, EAC, IECEx, Merchant Navy, RCM, UL |
| Standards Compliance | EN 61131-2, EN 61000-6-4, EN 61000-6-2, EN 61010-2-201 |
| Net Weight | 0.145 kg |
Frequently Asked Questions
Q: What is the difference between the BMXDRA0805H and the standard BMXDRA0805?A: The "H" suffix indicates a hardened version with conformal coating, extending the operating temperature range to -25 deg C to +70 deg C and adding resistance to corrosive gases (Gx, 3C4), dust/sand (3S4), salt (Level 2), and mold/fungi (3B2).
Q: Can the BMXDRA0805H be replaced directly by the BMXDRA0815H?A: Yes. Schneider Electric designates the BMXDRA0815H as the official replacement for the discontinued BMXDRA0805H, offering the same 8 NO relay outputs and severe-environment coating while supporting an expanded 24 to 125 V DC load range.
Q: What is the minimum load required for reliable relay switching on the BMXDRA0805H?A: Each relay output requires a minimum switching current of 10 mA at 5 V DC to maintain proper contact reliability.
Pembayaran: T/T, Western Union.
Pelabuhan penghantaran: Xiamen.
Tempoh penghantaran: Biasanya 1–3 hari bekerja selepas pengesahan pembayaran (tertakluk pada stok).
Penghantaran ke seluruh dunia: Kami menghantar alat ganti automasi industri kepada pelanggan di seluruh dunia. Kos penghantaran akan disebut harga bersama RFQ anda.
Soalan Lazim
Soalan lazim tentang sebut harga, penghantaran, waranti dan pemulanganKlik Minta Sebut Harga pada halaman produk dan hantar nombor bahagian, kuantiti yang diperlukan serta negara destinasi kepada kami. Pasukan jualan kami akan membalas dengan ketersediaan semasa, harga dan anggaran masa penghantaran.
Item dalam stok biasanya disediakan selepas pembayaran dan pengesahan pesanan. Kebanyakan pesanan dihantar dari gudang kami di China, walaupun lokasi penghantaran mungkin berbeza bergantung pada stok semasa.
Ya. Kami menghantar komponen automasi industri kepada pelanggan di seluruh dunia. Kos penghantaran dan masa transit bergantung pada destinasi, berat bungkusan, saiz produk dan keperluan import tempatan.
Kami biasanya menggunakan DHL, FedEx, UPS dan perkhidmatan kurier antarabangsa yang lain. Syarikat pengangkutan boleh dipilih berdasarkan destinasi, kelajuan penghantaran, saiz kiriman dan keperluan pelanggan.
Produk kami secara amnya dilindungi oleh waranti 12 bulan. Produk yang layak juga boleh dipulangkan di bawah polisi bayaran balik 30 hari kami. Sila hubungi pasukan kami sebelum memulangkan mana-mana item untuk mengesahkan terma yang berkenaan dan arahan pemulangan.
Anda mungkin juga suka
Siaran Blog
Berita automasi industri, panduan teknikal dan kemas kini produk.