Dimaklumkan melalui e-mel apabila produk ini tersedia semula
- Penerangan
- Reviews
- Penghantaran & Pembayaran
The BMXSAI0410 is a safety analog input module for the Schneider Electric Modicon X80 I/O platform, engineered specifically for Modicon M580 safety systems. It provides 4 isolated 4-20 mA current inputs with 16-bit A/D conversion, internal recalibration, and out-of-range current detection. Featuring a red housing coating designated for safety components, it supports functional safety architectures up to SIL 3, Category 4, and PLd, and operates exclusively with a Modicon M580 Safety CPU.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXSAI0410 |
| Brand | Schneider Electric |
| Product Range | Modicon X80 |
| Product Type | Safety Analog Input Module |
| Number of Inputs | 4 isolated channels |
| Input Type | Current, 4-20 mA (high level) |
| Analog/Digital Conversion | 16-bit |
| Input Resolution | 13-bit (0 to 12,500 counts; 2 uA measurement resolution) |
| Digital Value Format | +/- 10,000 (default); +/- 32,000 (user scale) |
| Nominal Read Cycle Time | 6 ms for 4 channels |
| Measurement Error | Less than or equal to 0.3% of full scale at -25 to 60 deg C |
| Temperature Drift | 30 ppm/deg C |
| Input Impedance | 286 Ohm (0.1% internal resistor precision, 15 ppm/deg C) |
| Permitted Input Overload | 25 mA (maximum conversion range: 0-25 mA) |
| Digital Filtering | Second-order digital filter |
| Crosstalk Attenuation | Minimum 120 dB |
| Electrical Connection | 20-way removable terminal block (1 connector) |
| Isolation Voltage | 500 VDC (channel-to-channel); 1500 VDC (channel-to-ground and channel-to-bus) |
| Current Consumption | 200 mA at 3.3 VDC; 115 mA at 24 VDC |
| Status Indicators | 1 green RUN LED, 1 red ERR LED, 1 red I/O LED, 4 green channel diagnostic LEDs |
| Safety Ratings | Up to SIL 3, Category 4, PLd; CIP Safety compliant |
| Certifications | TUV Rheinland, CE, UL, CSA, ATEX, IECEx, EAC, RCM, Merchant Navy |
| Compliance Standards | IEC 61131-2, IEC 61010-2-201, UL 61010-2-201, CSA C22.2 No 61010-2-201 |
| Operating Temperature | -25 to 60 deg C |
| Storage Temperature | -40 to 85 deg C |
| Relative Humidity | 5 to 95% at 55 deg C (without condensation) |
| Operating Altitude | 0 to 2,000 m (2,000 to 5,000 m with derating factor) |
| Environmental Resistance | Gas class Gx / 3C4; Dust and sand class 3S4; Salt level 2; Mold and fungal spore class 3B2 (IEC 60721-3-3) |
| Mechanical Resistance | Vibration: 3 gn; Shock: 15 gn |
| Protection Rating | IP20 |
| MTBF | 463,000 hours |
| Net Weight | 0.143 kg |
| Dimensions (H x W x L) | 5.5 cm x 18.0 cm x 26.0 cm |
Signal Processing and Isolation Architecture
Each of the four channels measures 4-20 mA process signals across an internal 286 Ohm precision resistor (0.1% tolerance) and converts the signal via a 16-bit A/D converter with second-order digital filtering. The module scans all 4 channels within a nominal read cycle time of 6 ms, maintaining a measurement resolution of 2 uA and an accuracy within 0.3% of full scale across the -25 to 60 deg C operating range.
Galvanic isolation is rated at 500 VDC between individual channels and 1500 VDC from channels to ground and backplane bus, preventing ground loops and cross-channel interference (minimum 120 dB crosstalk attenuation). Built-in diagnostics monitor for out-of-range current conditions up to the 25 mA overload limit and report status via dedicated green channel LEDs alongside module-level RUN, ERR, and I/O indicators.
Compatibility and Installation Considerations
- Controller Requirement: Although part of the common Modicon X80 I/O family, the BMXSAI0410 is dedicated to Modicon M580 safety architectures and can only operate with a Modicon M580 Safety CPU. It cannot be used in standard non-safety M340 or standard M580 configurations.
- Rack Placement and Clearance: The module can be installed in either a local main rack or a remote drop rack (Ethernet or X-bus). Note that the physical height of this safety I/O module exceeds the standard Modicon X80 rack height; cabinet layouts must account for the extra vertical clearance before mounting the rack.
- Field Wiring: Field signals connect via a single 20-way removable terminal block, allowing module replacement without disturbing field wiring.
Frequently Asked Questions
Q: Can the BMXSAI0410 be used with a standard Modicon M340 or non-safety M580 CPU?A: No. While it uses the Modicon X80 form factor, the BMXSAI0410 is strictly dedicated to Modicon M580 safety systems and requires a Safety CPU to function.
Q: What physical clearance is needed when mounting the BMXSAI0410 in a rack?A: The height of the BMXSAI0410 module is greater than the height of a standard Modicon X80 Ethernet or X-bus rack. Ensure sufficient vertical space above or below the rack in the enclosure prior to installation.
Q: How are channel faults and out-of-range signals indicated on the module?A: The module features continuous current out-of-range detection up to 25 mA, displaying channel-specific diagnostics on 4 individual green LEDs along with module-level red ERR and I/O fault LEDs.
Pembayaran: T/T, Western Union.
Pelabuhan penghantaran: Xiamen.
Tempoh penghantaran: Biasanya 1–3 hari bekerja selepas pengesahan pembayaran (tertakluk pada stok).
Penghantaran ke seluruh dunia: Kami menghantar alat ganti automasi industri kepada pelanggan di seluruh dunia. Kos penghantaran akan disebut harga bersama RFQ anda.
Soalan Lazim
Soalan lazim tentang sebut harga, penghantaran, waranti dan pemulanganKlik Minta Sebut Harga pada halaman produk dan hantar nombor bahagian, kuantiti yang diperlukan serta negara destinasi kepada kami. Pasukan jualan kami akan membalas dengan ketersediaan semasa, harga dan anggaran masa penghantaran.
Item dalam stok biasanya disediakan selepas pembayaran dan pengesahan pesanan. Kebanyakan pesanan dihantar dari gudang kami di China, walaupun lokasi penghantaran mungkin berbeza bergantung pada stok semasa.
Ya. Kami menghantar komponen automasi industri kepada pelanggan di seluruh dunia. Kos penghantaran dan masa transit bergantung pada destinasi, berat bungkusan, saiz produk dan keperluan import tempatan.
Kami biasanya menggunakan DHL, FedEx, UPS dan perkhidmatan kurier antarabangsa yang lain. Syarikat pengangkutan boleh dipilih berdasarkan destinasi, kelajuan penghantaran, saiz kiriman dan keperluan pelanggan.
Produk kami secara amnya dilindungi oleh waranti 12 bulan. Produk yang layak juga boleh dipulangkan di bawah polisi bayaran balik 30 hari kami. Sila hubungi pasukan kami sebelum memulangkan mana-mana item untuk mengesahkan terma yang berkenaan dan arahan pemulangan.
Anda mungkin juga suka
Siaran Blog