Configured for temperature, voltage, resistance, and thermocouple measurement in the Modicon X80 platform, the Schneider Electric BMXART0814 (BMXART0814 analog input module) provides eight isolated low-level analog input channels with 15 bits + sign resolution. It supports RTD, thermocouple, resistance, and voltage input ranges with external cold junction compensation by Pt100 probe.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMXART0814 |
| Brand | Schneider Electric |
| Series | Modicon X80 |
| Product Type | Analog input module |
| Analog Inputs | 8 |
| Input Level | Low level |
| Channel Isolation | Isolated between channels |
| Input Types | Voltage, resistance, RTD, thermocouple |
| Analog Input Resolution | 15 bits + sign |
| A/D Conversion | Sigma delta, 16 bits |
| Voltage Ranges | +/- 40 mV, +/- 80 mV, +/- 160 mV, +/- 320 mV, +/- 640 mV, +/- 1.28 V |
| Resistance Inputs | 400 Ohm and 4000 Ohm, 2-wire, 3-wire, or 4-wire |
| RTD Inputs | Cu 10, Ni 100, Ni 1000, Pt 100, Pt 1000 |
| Thermocouple Types | B, E, J, K, L, N, R, S, T, U |
| Cold Junction Compensation | External by Pt100 probe |
| Nominal Read Cycle | 400 ms with temperature probe; 200 ms with thermocouple |
| Common Mode Rejection | 120 dB at 50/60 Hz |
| Differential Mode Rejection | 60 dB at 50/60 Hz |
| Digital Filtering | First order |
| Measurement Resolution | 0.1 deg C for supported temperature inputs |
| Maximum Wiring Resistance | Up to 500 Ohm depending on sensor and wiring configuration |
| Electrical Connection | 40-way, 2 connectors |
| Current Consumption | 150 mA at 3.3 VDC; 50 mA at 24 VDC |
| Weight | 0.165 kg |
| Operating Temp | 0 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| IP Rating | IP20 |
| Vibration Resistance | 3 gn |
| Shock Resistance | 30 gn |
| Operating Altitude | 0 to 2000 m; 2000 to 5000 m with derating |
| Recalibration | Internal |
| Open Circuit Detection | Supported for specified RTD and thermocouple inputs |
| Status Indication | RUN, channel diagnostic, ERR, and I/O LEDs |
| Certifications | CE, EAC, UL, CSA, Merchant Navy, RCM |
| Standards | IEC 61131-2, IEC 61000-6-4, IEC 61000-6-2, EN 61010-2-201 |
| Protective Treatment | Standard version |
The module specifications identify eight isolated inputs, low-level input operation, 15 bits + sign resolution, and a 150 mA current consumption at 3.3 VDC. The environmental ratings and physical weight are specified as IP20, 0 to 60 deg C operating temperature, and 0.165 kg net weight.
I/O Density and Signal Conditioning
The BMXART0814 provides eight analog channels within a Modicon X80 module. The input circuitry accepts multiple low-level voltage ranges, resistance configurations, RTD types, and thermocouple types. Channel-to-channel isolation separates the individual input circuits. The module applies first-order digital filtering and provides common-mode rejection of 120 dB and differential-mode rejection of 60 dB at 50/60 Hz.
For temperature measurement, cold junction compensation is performed externally using a Pt100 probe. The specified measurement and temperature-drift values vary according to the selected sensor or input range. Internal recalibration and open-circuit detection are provided for the supported sensor types.
Frequently Asked Questions
Q: How many analog channels does the BMXART0814 provide?
A: It provides 8 analog input channels with channel-to-channel isolation.
Q: What power consumption is specified for the module?
A: The module consumes 150 mA at 3.3 VDC and 50 mA at 24 VDC.
Q: How is cold junction compensation implemented?
A: Cold junction compensation is external and uses a Pt100 probe.
Field Installation Guidelines
- Install the module in the compatible Modicon X80 rack and secure the module mechanically before connecting field wiring.
- Use the specified 40-way connector arrangement for electrical connections.
- Separate low-level analog and thermocouple wiring from high-current power and switching conductors where practical.
- Maintain correct sensor wiring configuration for 2-wire, 3-wire, or 4-wire resistance and RTD measurements.
- Apply shield termination according to the installation grounding scheme and avoid creating unintended ground loops.
- For thermocouple channels, use the appropriate thermocouple wiring and verify the external Pt100 connection required for cold junction compensation.
- Confirm the selected input range and sensor type before commissioning each channel.
- Observe the IP20 enclosure limitation and install the module inside an enclosure providing the required environmental protection.
- Keep ambient operating temperature within 0 to 60 deg C and account for altitude derating above 2000 m.
Płatność: T/T, Western Union.
Port wysyłki: Xiamen.
Czas realizacji: Zazwyczaj 1–3 dni robocze po potwierdzeniu płatności (w zależności od dostępności).
Dostawa na cały świat: Wysyłamy części do automatyki przemysłowej klientom na całym świecie. Koszt transportu jest podawany wraz z wyceną na podstawie zapytania ofertowego.
Najczęściej zadawane pytania
Często zadawane pytania dotyczące wycen, wysyłki, gwarancji i zwrotówNa stronie produktu kliknij Poproś o wycenę i prześlij nam numer części, wymaganą ilość oraz kraj docelowy. Nasz zespół sprzedaży odpowie, podając aktualną dostępność, cenę i szacowany czas dostawy.
Produkty dostępne w magazynie są zazwyczaj przygotowywane po dokonaniu płatności i potwierdzeniu zamówienia. Większość zamówień jest wysyłana z naszego magazynu w Chinach, choć miejsce wysyłki może się różnić w zależności od aktualnego stanu magazynowego.
Tak. Wysyłamy części do automatyki przemysłowej klientom na całym świecie. Koszt wysyłki i czas transportu zależą od miejsca docelowego, wagi przesyłki, rozmiaru produktu oraz lokalnych wymogów importowych.
Najczęściej korzystamy z usług DHL, FedEx, UPS i innych międzynarodowych firm kurierskich. Przewoźnika można wybrać w zależności od miejsca docelowego, szybkości dostawy, rozmiaru przesyłki i wymagań klienta.
Nasze produkty są zazwyczaj objęte 12-miesięczną gwarancją. Produkty spełniające odpowiednie warunki można również zwrócić zgodnie z naszą 30-dniową polityką zwrotu pieniędzy. Przed zwrotem dowolnego produktu skontaktuj się z naszym zespołem, aby potwierdzić obowiązujące warunki i instrukcje dotyczące zwrotu.
Możesz też polubić
Wpisy na blogu
Wiadomości o automatyce przemysłowej, poradniki techniczne i aktualizacje produktów.