{"product_id":"schneider-electric-bmxddo3202kc-modicon-x80-discrete-output-module","title":"Schneider Electric BMXDDO3202KC Modicon X80 Discrete Output Module","description":"\u003cp\u003eThe \u003cstrong\u003eSchneider Electric BMXDDO3202KC\u003c\/strong\u003e is a 32-channel discrete output module for the Modicon X80 automation platform. It uses solid-state transistor outputs with 24 VDC positive logic to control external actuators and other DC loads. This version features conformal coating for operation in more severe environmental conditions, with individual channel diagnostics and electronic output protection.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eOutput Configuration and Operation\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe BMXDDO3202KC provides 32 independent 24 VDC positive-logic outputs. Its source-type output design supplies current from the external DC supply to connected pre-actuators when the corresponding output is activated.\u003c\/p\u003e\n\u003cp\u003eEach channel has a nominal output current of 0.1 A and a maximum channel current of 0.125 A. The total current across the module must not exceed 3.2 A. These limits should be considered together when distributing loads across the 32 channels.\u003c\/p\u003e\n\u003cp\u003eThe output response time is 1.2 ms, making the module suitable for switching discrete control signals. The maximum voltage drop in the ON state is less than 1.5 V, while the maximum leakage current in the OFF state is 0.1 mA.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eProtection and Channel Diagnostics\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module incorporates several protection functions for its solid-state output circuits:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eReverse-polarity protection using a reverse-mounted diode.\u003c\/li\u003e\n\u003cli\u003eExternal short-circuit protection.\u003c\/li\u003e\n\u003cli\u003eOverload protection with current limiting.\u003c\/li\u003e\n\u003cli\u003eElectronic circuit-breaker protection, with a specified trip-current range of 0.125 A to 0.185 A.\u003c\/li\u003e\n\u003cli\u003eOutput overvoltage protection using a Transil diode.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eGreen LEDs provide module operating and individual channel status indications. Red LEDs indicate module errors and I\/O faults, helping maintenance personnel identify output-related problems.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eEnvironmental Design\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe BMXDDO3202KC is the conformal-coated version of the BMXDDO3202K. Its protective coating distinguishes it from the standard version and makes it suitable for specified severe environmental conditions, including chemically aggressive atmospheres.\u003c\/p\u003e\n\u003cp\u003eThe product documentation identifies gas resistance class Gx and 3C4, dust and sand resistance class 3S4, and salt resistance level 2. These classifications are relevant when selecting the module for installations where environmental exposure is an important equipment selection criterion.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXDDO3202KC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Series\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDiscrete Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Type\u003c\/td\u003e\n\u003ctd\u003eSolid-state transistor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Outputs\u003c\/td\u003e\n\u003ctd\u003e32\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Logic\u003c\/td\u003e\n\u003ctd\u003ePositive logic (source)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Output Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage Range\u003c\/td\u003e\n\u003ctd\u003e19-30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Output Current\u003c\/td\u003e\n\u003ctd\u003e0.1 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Current per Channel\u003c\/td\u003e\n\u003ctd\u003e0.125 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Current per Module\u003c\/td\u003e\n\u003ctd\u003e3.2 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Leakage Current\u003c\/td\u003e\n\u003ctd\u003e0.1 mA at state 0\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Voltage Drop\u003c\/td\u003e\n\u003ctd\u003eLess than 1.5 V at state 1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Response Time\u003c\/td\u003e\n\u003ctd\u003e1.2 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Insulation Resistance\u003c\/td\u003e\n\u003ctd\u003eGreater than 10 MOhm at 500 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Paralleling\u003c\/td\u003e\n\u003ctd\u003eMaximum 3 outputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMinimum Load Impedance\u003c\/td\u003e\n\u003ctd\u003e220 Ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Overload Time\u003c\/td\u003e\n\u003ctd\u003e15 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOverload Protection\u003c\/td\u003e\n\u003ctd\u003eCurrent limiter and electronic circuit breaker\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOvervoltage Protection\u003c\/td\u003e\n\u003ctd\u003eTransil diode\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTypical Internal Current Consumption\u003c\/td\u003e\n\u003ctd\u003e125 mA at 3.3 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003e3.6 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtective Treatment\u003c\/td\u003e\n\u003ctd\u003eConformal coating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet Weight\u003c\/td\u003e\n\u003ctd\u003e0.11 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMTBF\u003c\/td\u003e\n\u003ctd\u003e312254 hours\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the difference between BMXDDO3202KC and BMXDDO3202K?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Both models provide 32-channel, 24 VDC positive-logic static outputs with the same principal electrical output characteristics. The BMXDDO3202KC is the conformal-coated version, designed for more severe environmental conditions, while the BMXDDO3202K is the standard version.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What type of loads can the BMXDDO3202KC control?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: It is designed for DC discrete loads such as pre-actuators. The connected load must comply with the 24 VDC output range, current limits and minimum load impedance. The nominal current is 0.1 A per output, with a maximum of 0.125 A per channel.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What external protection is required for the output circuits?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The module documentation specifies a fast-blow 2 A external fuse for each 16-channel group. Therefore, the 32 outputs are protected through two external fuse groups. The built-in electronic protection does not eliminate this external fuse requirement.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":68110326300957,"sku":"BMXDDO3202KC","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/BMXDDO3202KC2.jpg?v=1794910561","url":"https:\/\/www.6gcontrols.com\/pl\/products\/schneider-electric-bmxddo3202kc-modicon-x80-discrete-output-module","provider":"6G Controls","version":"1.0","type":"link"}