{"product_id":"abb-di820-3bse008512r1-s800-digital-input-module","title":"ABB DI820 3BSE008512R1 S800 Digital Input Module","description":"\u003cp\u003eThe \u003cstrong\u003eABB DI820 3BSE008512R1\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eDI820\u003c\/strong\u003e Digital Input Module, provides eight individually isolated digital input channels for 120 V AC and 110 V DC field signals in the ABB S800 I\/O system. Each channel includes current limiting, EMC protection, optical isolation, status indication, and selectable digital filtering. Channels 1 and 8 can provide field voltage supervision for channel groups 2-4 and 5-7 respectively, with supervision status reported through the ModuleBus.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eDI820\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eArticle Number\u003c\/td\u003e\n\u003ctd\u003e3BSE008512R1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDigital Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eS800 I\/O\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Specification\u003c\/td\u003e\n\u003ctd\u003e120 V AC \/ 110 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Type\u003c\/td\u003e\n\u003ctd\u003eCurrent sinking\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAC Input Voltage\u003c\/td\u003e\n\u003ctd\u003e77-130 V AC for logic \"1\"; 0-30 V AC for logic \"0\"\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDC Input Voltage\u003c\/td\u003e\n\u003ctd\u003e75-145 V DC for logic \"1\"; 0-20 V DC for logic \"0\"\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e10 mA at 120 V AC; 2.8 mA at 110 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e12 kOhm AC \/ 39 kOhm DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003eIndividually isolated channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFilter Times\u003c\/td\u003e\n\u003ctd\u003e2, 4, 8, 16 ms selectable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Frequency\u003c\/td\u003e\n\u003ctd\u003e47-63 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Filter Delay\u003c\/td\u003e\n\u003ctd\u003e5 ms ON \/ 18 ms OFF\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Field Cable Length\u003c\/td\u003e\n\u003ctd\u003e200 m AC with 100 pF\/m; 600 m DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Insulation Voltage\u003c\/td\u003e\n\u003ctd\u003e250 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDielectric Test Voltage\u003c\/td\u003e\n\u003ctd\u003e2000 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003eTypically 2.8 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModuleBus Current at +5 V\u003c\/td\u003e\n\u003ctd\u003e50 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModuleBus Current at +24 V\u003c\/td\u003e\n\u003ctd\u003e0 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExternal +24 V Current\u003c\/td\u003e\n\u003ctd\u003e0 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHART\u003c\/td\u003e\n\u003ctd\u003eNo\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSOE\u003c\/td\u003e\n\u003ctd\u003eNo\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRedundancy\u003c\/td\u003e\n\u003ctd\u003eNo\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHigh Integrity\u003c\/td\u003e\n\u003ctd\u003eNo\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIntrinsic Safety\u003c\/td\u003e\n\u003ctd\u003eNo\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMechanics\u003c\/td\u003e\n\u003ctd\u003eS800\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompatible MTU\u003c\/td\u003e\n\u003ctd\u003eTU811, TU813, TU831, TU839, TU851\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eKeying Code\u003c\/td\u003e\n\u003ctd\u003eAB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to +55 deg C; approvals issued for +5 to +55 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5 to 95%, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Class\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCorrosion Protection\u003c\/td\u003e\n\u003ctd\u003eISA-S71.04: G3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.18 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e45 mm W x 102 mm D x 119 mm H\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eABB S800 ModuleBus and Input Diagnostics\u003c\/h3\u003e\n\u003cp\u003eThe DI820 processes field input states through an analog filter, optical isolation barrier, EMC protection components, current limiting components, and front-panel status indication. The module reports diagnostic information through the ModuleBus, including module error, module warning, and channel error conditions.\u003c\/p\u003e\n\u003cp\u003eChannels 1 and 8 have an additional supervision function. Channel 1 can supervise field input voltage for channels 2-4, while channel 8 can supervise channels 5-7. Loss of the supervised voltage activates the corresponding error inputs and Warning LED.\u003c\/p\u003e\n\u003cp\u003eThe module provides front LEDs for Fault, Run, Warning, and channel status. The input filtering can be selected at 2, 4, 8, or 16 ms, while the analog filter has specified ON\/OFF delays of 5 ms and 18 ms.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What field signal ranges does the DI820 accept?\u003cbr\u003eA: The module accepts 77-130 V AC and 75-145 V DC for a logic \"1\". Logic \"0\" ranges are 0-30 V AC and 0-20 V DC.\u003c\/p\u003e\n\u003cp\u003eQ: Are the eight input channels electrically isolated from each other?\u003cbr\u003eA: Yes. Each input channel is individually isolated and includes an optical isolation barrier.\u003c\/p\u003e\n\u003cp\u003eQ: How does the DI820 detect loss of field input power?\u003cbr\u003eA: Channel 1 can supervise channels 2-4, and channel 8 can supervise channels 5-7. Loss of the supervised voltage activates the error inputs and Warning LED, with the error condition available through the ModuleBus.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eInstall the DI820 in a compatible S800 MTU using the specified keying code AB. Verify the selected MTU type against the approved compatibility list before wiring.\u003c\/p\u003e\n\u003cp\u003eSeparate AC or DC field wiring from low-level analog, communication, and other noise-sensitive circuits. Route conductors according to the site's EMC installation practices and maintain appropriate separation from high-current switching circuits.\u003c\/p\u003e\n\u003cp\u003eTerminate cable shields according to the system grounding design and the applicable ABB installation documentation. Avoid creating unintended shield current paths through multiple grounding points.\u003c\/p\u003e\n\u003cp\u003eVerify field polarity and voltage before energizing each input group. Confirm that the applied voltage remains within the specified input range and that field cable length is compatible with the stated limits.\u003c\/p\u003e\n\u003cp\u003eCheck the front-panel input status LEDs and ModuleBus diagnostics after commissioning. Where voltage supervision is configured, verify the supervised field supply and the corresponding Warning and diagnostic indications.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":52750366146845,"sku":"DI820 3BSE008512R1","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/DI820-1_1000.jpg?v=1787037612","url":"https:\/\/www.6gcontrols.com\/products\/abb-di820-3bse008512r1-s800-digital-input-module","provider":"6G Controls","version":"1.0","type":"link"}