{"product_id":"abb-ntai06-analog-input-termination-unit","title":"ABB NTAI06 Analog Input Termination Unit","description":"\u003cp\u003eThe \u003cstrong\u003eABB NTAI06\u003c\/strong\u003e is a 16-channel analog input termination unit designed to connect field signals to an analog input module in a Bailey control system. It provides field wiring termination and configurable input connections for different analog signal types. The unit mounts in the NFTP01 Field Termination Panel and requires an external +24 VDC supply when system-powered 4-20 mA inputs are used.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFunctional Description\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe NTAI06 provides termination points for up to 16 analog field input signals. Its terminal connections route field signals through the termination assembly to the associated analog input module for acquisition by the control system.\u003c\/p\u003e\n\u003cp\u003eEach input channel can be configured using jumpers to match the connected field signal. Documented input configurations include voltage, current, and three-wire RTD signals. This channel-level configuration allows different input types to be handled by the same termination unit, subject to the associated input module's specifications.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eMounting and Electrical Requirements\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe NTAI06 is installed in the \u003cstrong\u003eNFTP01 Field Termination Panel\u003c\/strong\u003e. Its field terminals provide the connection point between external instruments and the control system's analog input circuitry.\u003c\/p\u003e\n\u003cp\u003eAn additional +24 VDC supply is required when system-powered 4-20 mA transmitters are connected. This requirement should be considered when checking the field wiring and power distribution arrangement.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eNTAI06\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eABB (Bailey)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Input Termination Unit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e16\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Requirements\u003c\/td\u003e\n\u003ctd\u003e+24 VDC required when system-powered 4-20 mA inputs are used\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003eNFTP01 Field Termination Panel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAmbient Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 70 deg C (32 to 158 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5% to 90% +\/- 5% up to 55 deg C, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity at 70 deg C\u003c\/td\u003e\n\u003ctd\u003e5% to 40% +\/- 5%, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAtmospheric Pressure\u003c\/td\u003e\n\u003ctd\u003eSea level to 3 km (1.86 miles)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAir Quality\u003c\/td\u003e\n\u003ctd\u003eNoncorrosive\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCooling Requirements\u003c\/td\u003e\n\u003ctd\u003eNo additional cooling required when installed in Bailey Controls cabinets and operated within specified limits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectromagnetic \/ Radio Frequency Interference\u003c\/td\u003e\n\u003ctd\u003eNo numerical values specified; keep cabinet doors closed and communication equipment at least 2 m from the cabinet\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCertification\u003c\/td\u003e\n\u003ctd\u003eCSA certified for process control equipment in ordinary (nonhazardous) locations\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.653 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eInput Configuration\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe NTAI06 uses configurable jumpers to select the appropriate electrical connection for each analog input channel. Documented signal configurations include:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eVoltage inputs, including differential and single-ended connections.\u003c\/li\u003e\n\u003cli\u003eSystem-powered 4-20 mA current inputs.\u003c\/li\u003e\n\u003cli\u003eExternally powered 4-20 mA current inputs.\u003c\/li\u003e\n\u003cli\u003eThree-wire RTD inputs.\u003c\/li\u003e\n\u003cli\u003eThermocouple and millivolt input configurations, as documented in the applicable termination unit instructions.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe jumper positions must correspond to the connected field instrument and the associated analog input module configuration. Incorrect jumper settings can result in improper signal acquisition.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How many analog input channels does the ABB NTAI06 support?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The NTAI06 provides termination for 16 analog input channels. Each channel can be configured independently according to the supported input signal type.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the NTAI06 require an external power supply?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: A +24 VDC supply is required when system-powered 4-20 mA inputs are used. This requirement does not mean that every input configuration requires the same external supply arrangement.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Which mounting panel is required for the NTAI06?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The NTAI06 mounts in the NFTP01 Field Termination Panel. The associated analog input module and termination cable arrangement must also match the installed control system configuration.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":52752488464669,"sku":"NTAI06","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/NTAI062.jpg?v=1795516265","url":"https:\/\/www.6gcontrols.com\/products\/abb-ntai06-analog-input-termination-unit","provider":"6G Controls","version":"1.0","type":"link"}