{"product_id":"abb-sa-811f-3bdh000013r1-ac-800f-power-supply","title":"ABB SA 811F 3BDH000013R1 AC 800F Power Supply","description":"\u003cp\u003eThe \u003cstrong\u003eABB SA 811F (3BDH000013R1)\u003c\/strong\u003e is an AC power supply module for the ABB AC 800F controller platform. It accepts 115\/230 VAC input and provides two regulated DC output rails, 5 VDC and 3.3 VDC, for supplying AC 800F modules. It includes power-failure detection, overload protection and short-circuit protection. The module is specified for use with PM 802F or PM 803F controllers.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003ePower Supply Function\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe SA 811F converts incoming AC power into regulated DC power for the AC 800F controller hardware. It provides separate 5 VDC and 3.3 VDC outputs, with respective current capacities of up to 5.5 A and 6.5 A.\u003c\/p\u003e\n\u003cp\u003eIts electronically controlled outputs maintain voltage stability and low residual ripple. Open-circuit, overload and sustained short-circuit protection help protect the power supply and connected electronics against abnormal load conditions.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003ePower-Failure Detection and Protection\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe SA 811F includes a power-failure detection function that supports controlled controller shutdown. When the input power is lost for at least 5 ms, the module generates a power-fail signal for the CPU.\u003c\/p\u003e\n\u003cp\u003eThe CPU uses this signal to shut down operations and place connected Remote I\/O outputs into their defined safe state. The power supply maintains its output voltage within tolerance for at least another 15 ms, allowing the system to manage a mains voltage drop of approximately 20 ms and support a controlled restart after power restoration.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eSA 811F\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrder Number\u003c\/td\u003e\n\u003ctd\u003e3BDH000013R1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAC Power Supply Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Family\u003c\/td\u003e\n\u003ctd\u003ePower Supply\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eController Platform\u003c\/td\u003e\n\u003ctd\u003eAC 800F\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompatible Controllers\u003c\/td\u003e\n\u003ctd\u003ePM 802F, PM 803F\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e115-230 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePermissible Input Range\u003c\/td\u003e\n\u003ctd\u003e90-260 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Frequency\u003c\/td\u003e\n\u003ctd\u003e50-60 Hz (permissible 47-63 Hz)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current at Nominal Load\u003c\/td\u003e\n\u003ctd\u003e275 mA at 230 VAC; 541 mA at 115 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Input Power\u003c\/td\u003e\n\u003ctd\u003e63 VA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage\u003c\/td\u003e\n\u003ctd\u003e5 VDC, 3.3 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage Tolerance\u003c\/td\u003e\n\u003ctd\u003e+\/- 3% typical\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Current\u003c\/td\u003e\n\u003ctd\u003e5.5 A at 5 VDC; 6.5 A at 3.3 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTotal Output Power\u003c\/td\u003e\n\u003ctd\u003eMax. 35 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Limit\u003c\/td\u003e\n\u003ctd\u003eApprox. 7.5 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower-Failure Backup\u003c\/td\u003e\n\u003ctd\u003eMore than 20 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection\u003c\/td\u003e\n\u003ctd\u003eOpen-circuit, overload and sustained short-circuit protection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFuse\u003c\/td\u003e\n\u003ctd\u003e2.5 AT subminiature fuse, soldered\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (H x W x D)\u003c\/td\u003e\n\u003ctd\u003e155 x 67 x 155 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet Weight\u003c\/td\u003e\n\u003ctd\u003e0.46 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCountry of Origin\u003c\/td\u003e\n\u003ctd\u003eGermany\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRequired Software Version\u003c\/td\u003e\n\u003ctd\u003eABB Freelance V7.1 SP2a or higher\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eController Compatibility and Software Requirements\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe SA 811F is specified for use with ABB PM 802F and PM 803F controllers. The required ABB Freelance software version is \u003cstrong\u003eV7.1 SP2a or higher\u003c\/strong\u003e.\u003c\/p\u003e\n\u003cp\u003eWhen selecting this module for controller maintenance or replacement, verify the installed CPU type and engineering software version. The power supply must match the controller hardware configuration and its DC power requirements.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Which controllers are compatible with the ABB SA 811F?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The SA 811F is specified for use with ABB PM 802F and PM 803F controllers in the AC 800F platform.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What DC output voltages does the SA 811F provide?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: It provides 5 VDC at up to 5.5 A and 3.3 VDC at up to 6.5 A. The maximum total output power is 35 W.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What software version is required for the SA 811F?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: ABB Freelance V7.1 SP2a or higher is mandatory for the specified configuration.\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":52750366671133,"sku":"SA811F 3BDH000013R1","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/SA811F_1000.jpg?v=1787037725","url":"https:\/\/www.6gcontrols.com\/products\/abb-sa-811f-3bdh000013r1-ac-800f-power-supply","provider":"6G Controls","version":"1.0","type":"link"}