{"product_id":"honeywell-10101-2-1-fsc-fail-safe-digital-input-module","title":"Honeywell 10101\/2\/1 FSC Fail-safe Digital Input Module","description":"\u003cp\u003eThe \u003cstrong\u003eHoneywell 10101\/2\/1\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003e10101\/2\/1\u003c\/strong\u003e FSC Fail-safe Digital Input Module, provides sixteen 24 VDC digital input channels with fail-to-safe input-stage behavior. It monitors logic 0, logic 1, and input-to-input crosstalk within the configured process safety time.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e10101\/2\/1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGeneral Type Number\u003c\/td\u003e\n\u003ctd\u003e10101\/2\/1 11000\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eFSC fail-safe digital input module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem\u003c\/td\u003e\n\u003ctd\u003eHoneywell FSC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e16 digital inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Input Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Input Voltage\u003c\/td\u003e\n\u003ctd\u003e36 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e7 mA at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput HIGH\u003c\/td\u003e\n\u003ctd\u003e\u0026gt; 15 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput LOW\u003c\/td\u003e\n\u003ctd\u003e\u0026lt; 9 VDC, I \u0026lt; 2 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTypical Input Delay\u003c\/td\u003e\n\u003ctd\u003e10 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5 VDC Power Requirement\u003c\/td\u003e\n\u003ctd\u003e8 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e24 VDC Internal Power\u003c\/td\u003e\n\u003ctd\u003e110 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e24 VDC External Power\u003c\/td\u003e\n\u003ctd\u003e110 mA, input currents\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5 VDC Ripple Content\u003c\/td\u003e\n\u003ctd\u003e\u0026lt; 0.5 Vp-p, 0-360 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSpace Requirement\u003c\/td\u003e\n\u003ctd\u003e4 TE, 3 HE = 4 HP, 3U\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSoftware Version\u003c\/td\u003e\n\u003ctd\u003e\u0026gt;= 3.00\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eApprovals\u003c\/td\u003e\n\u003ctd\u003eCE, TUV, UL\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Connector Coding\u003c\/td\u003e\n\u003ctd\u003eHoles A5, C5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRack Connector Coding\u003c\/td\u003e\n\u003ctd\u003eLarge pins A5, C5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.22 lb\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e2.5 cm x 12.7 cm x 20.3 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFail-safe Digital Input Monitoring\u003c\/h3\u003e\n\u003cp\u003eThe input stage operates in a fail-to-safe configuration. A component failure is designed to result in a de-energized input signal at the processor, corresponding to the specified safe condition for a typically energized system.\u003c\/p\u003e\n\u003cp\u003eThe system self-test functions cover the remaining module logic circuitry. Within the configured process safety time, diagnostic testing includes:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eReception of logic level 0 signals\u003c\/li\u003e\n\u003cli\u003eReception of logic level 1 signals\u003c\/li\u003e\n\u003cli\u003eDetection of crosstalk between input channels\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe 16 input channels accept 24 VDC field signals. The specified HIGH threshold is above 15 VDC, while the LOW condition is below 9 VDC with input current below 2 mA.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How many digital input channels does the 10101\/2\/1 provide?\u003c\/strong\u003e\u003cbr\u003e\u003cstrong\u003eA:\u003c\/strong\u003e It provides 16 digital input channels rated for 24 VDC operation.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What happens to the processor input signal under an input-stage component failure?\u003c\/strong\u003e\u003cbr\u003e\u003cstrong\u003eA:\u003c\/strong\u003e The fail-to-safe input stage causes the processor-side input signal to become de-energized, which is the defined safe condition for a typically energized system.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What electrical supply does the module require?\u003c\/strong\u003e\u003cbr\u003e\u003cstrong\u003eA:\u003c\/strong\u003e The specified requirements are 5 VDC at 8 mA, 24 VDC internal supply at 110 mA, and 24 VDC external supply at 110 mA for input currents.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eInstall the module in the designated FSC rack position according to the applicable rack configuration.\u003c\/li\u003e\n\u003cli\u003eVerify the module and rack connector coding before insertion. The specified coding is A5 and C5.\u003c\/li\u003e\n\u003cli\u003eConfirm that field digital signals remain within the stated 36 VDC maximum input voltage.\u003c\/li\u003e\n\u003cli\u003eMaintain correct polarity and wiring identification for all 16 input channels.\u003c\/li\u003e\n\u003cli\u003eSeparate digital input wiring from high-current and high-noise conductors where practical.\u003c\/li\u003e\n\u003cli\u003eUse appropriate cable shielding and grounding practices according to the FSC installation documentation and site grounding design.\u003c\/li\u003e\n\u003cli\u003eVerify the 5 VDC and 24 VDC supply wiring before energizing the rack.\u003c\/li\u003e\n\u003cli\u003eCheck the specified input HIGH and LOW thresholds during commissioning where signal verification is required.\u003c\/li\u003e\n\u003cli\u003eConfirm that the installed software version meets the stated requirement of \u0026gt;= 3.00.\u003c\/li\u003e\n\u003cli\u003eDo not substitute connector or rack coding arrangements without confirming system compatibility.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52750314078493,"sku":"10101\/2\/1","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/10101212.jpg?v=1792142401","url":"https:\/\/www.6gcontrols.com\/products\/honeywell-10101-2-1-fsc-fail-safe-digital-input-module","provider":"6G Controls","version":"1.0","type":"link"}