{"product_id":"honeywell-tc-odd321-experion-dc-output-module","title":"Honeywell TC-ODD321 Experion DC Output Module","description":"\u003cp\u003eThe Honeywell TC-ODD321 is an Experion DC Output Module designed to provide 32 discrete DC output points for control signal distribution to external field devices. It supports 16 points per common and operates across specified DC voltage ranges with temperature-dependent limits. The module also provides repeatable surge current capability and connects through the TC-TBCH 36-position terminal block.\u003c\/p\u003e\n\u003ch3\u003eOutput Configuration and Electrical Characteristics\u003c\/h3\u003e\n\u003cp\u003eThe TC-ODD321 provides 32 output channels arranged in two groups of 16 points per common. This configuration is relevant when allocating field loads and planning common connections. Each output has a minimum on-state load current requirement of 3.0 mA.\u003c\/p\u003e\n\u003cp\u003eThe output voltage range depends on the operating temperature. At 50 deg C, the specified range is 10 to 31.2 VDC with linear derating. At 60 deg C, the specified range is 10 to 28 VDC. These limits should be considered when checking the supply voltage and connected load requirements.\u003c\/p\u003e\n\u003ch3\u003eSurge Current and Output Voltage Drop\u003c\/h3\u003e\n\u003cp\u003eEach output supports a surge current of 1 A for 10 ms at 60 deg C. This surge capability is repeatable every 2 seconds. It should be distinguished from the continuous on-state load current when evaluating field-device electrical requirements.\u003c\/p\u003e\n\u003cp\u003eThe maximum on-state voltage drop is 1 VDC at rated current per point, or 3 VDC under IEC 1131-2 conditions. The applicable value should be considered when calculating the voltage available to the connected load.\u003c\/p\u003e\n\u003ch3\u003eTerminal Block and Power Requirements\u003c\/h3\u003e\n\u003cp\u003eThe module uses the TC-TBCH 36-position terminal block for field-side connections. The terminal block provides the connection interface for the module's output wiring.\u003c\/p\u003e\n\u003cp\u003ePower dissipation is specified at 6.1 W. The backplane current must be determined from the module Power Consumption Data rather than estimated from the power dissipation value.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eTC-ODD321\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eExperion DC Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Outputs\u003c\/td\u003e\n\u003ctd\u003e32\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Configuration\u003c\/td\u003e\n\u003ctd\u003e16 points\/common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage Range at 50 deg C\u003c\/td\u003e\n\u003ctd\u003e10-31.2 VDC (linear derating)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage Range at 60 deg C\u003c\/td\u003e\n\u003ctd\u003e10-28 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSurge Current\u003c\/td\u003e\n\u003ctd\u003e1 A for 10 ms per output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSurge Current Repeat Interval\u003c\/td\u003e\n\u003ctd\u003eEvery 2 s at 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMinimum On-State Current Load\u003c\/td\u003e\n\u003ctd\u003e3.0 mA per output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum On-State Voltage Drop\u003c\/td\u003e\n\u003ctd\u003e1 VDC at rated current per point\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOn-State Voltage Drop (IEC 1131-2)\u003c\/td\u003e\n\u003ctd\u003e3 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003e6.1 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBackplane Current\u003c\/td\u003e\n\u003ctd\u003eRefer to module Power Consumption Data\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnection Terminal Block\u003c\/td\u003e\n\u003ctd\u003eTC-TBCH\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Block Positions\u003c\/td\u003e\n\u003ctd\u003e36\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How many output channels does the Honeywell TC-ODD321 provide?\u003c\/p\u003e\n\u003cp\u003eA: The TC-ODD321 provides 32 DC output points, arranged as 16 points per common. This grouping should be considered when planning output wiring and field-load connections.\u003c\/p\u003e\n\u003cp\u003eQ: Does the TC-ODD321 support the same output voltage range at 50 deg C and 60 deg C?\u003c\/p\u003e\n\u003cp\u003eA: No. The specified range is 10-31.2 VDC at 50 deg C, with linear derating, and 10-28 VDC at 60 deg C. The applicable temperature limit must be considered when selecting the field supply voltage.\u003c\/p\u003e\n\u003cp\u003eQ: Which terminal block is specified for the TC-ODD321?\u003c\/p\u003e\n\u003cp\u003eA: The specified connection terminal block is the Honeywell TC-TBCH, featuring 36 positions. Confirm the terminal block configuration when checking replacement parts or preparing the module for installation.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52750314275101,"sku":"TC-ODD321 97067175-A01","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/TC-ODD3212.jpg?v=1793864165","url":"https:\/\/www.6gcontrols.com\/products\/honeywell-tc-odd321-experion-dc-output-module","provider":"6G Controls","version":"1.0","type":"link"}