{"product_id":"schneider-electric-bmxert1604t-modicon-x80-multifunction-input-module","title":"Schneider Electric BMXERT1604T Modicon X80 Multifunction Input Module","description":"\u003cp\u003eThe \u003cstrong\u003eSchneider Electric BMXERT1604T\u003c\/strong\u003e is a 16-channel multifunction input module in the Modicon X80 range, designed for Modicon M340 and M580 Programmable Automation Controllers (PACs). It accepts 24 V DC, 48-60 V DC, and 110-125 V DC process inputs and supports event recording with 1 ms time stamps. The module also provides configurable input filtering and time-code synchronization interfaces for applications requiring time-correlated event acquisition.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFunctional Overview\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe BMXERT1604T provides 16 discrete process inputs arranged in four groups of four channels. It acquires input state changes and supports time-stamped data recording, allowing the controller to correlate field events with their occurrence times.\u003c\/p\u003e\n\u003cp\u003eIts multifunction capability includes two time synchronization protocols:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eDCF77:\u003c\/strong\u003e Supports synchronization using the DCF77 time signal.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIRIG-B:\u003c\/strong\u003e Supports time synchronization using the IRIG-B time-code format.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003e1 ms time stamps:\u003c\/strong\u003e Provides millisecond-resolution event timestamps.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput filtering:\u003c\/strong\u003e Configurable anti-bounce filtering helps suppress unwanted transitions caused by contact bounce or short-duration input disturbances.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe sampling duration is 0.5 ms, with an acquisition time of 1 ms. These specifications describe different stages of input processing and should not be interpreted as a guaranteed end-to-end controller response time.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eInput Configuration and Signal Processing\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module supports three rated DC input voltage classes. The applicable voltage range depends on the selected input circuit configuration and the actual field signal:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e24 V DC: 19-30 V DC\u003c\/li\u003e\n\u003cli\u003e48-60 V DC: 38-75 V DC\u003c\/li\u003e\n\u003cli\u003e110-125 V DC: 88-156 V DC\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe switching voltage and corresponding input current vary by voltage class. This distinction is important when checking compatibility with field contacts and external signal sources.\u003c\/p\u003e\n\u003cp\u003eThe configurable anti-bounce filter ranges from 0 to 255 ms. A shorter setting allows faster recognition of input transitions, while a longer setting provides more filtering against contact bounce. The selected filter value should reflect the characteristics of the connected field device and the required event detection behavior.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTime Stamping and Event Synchronization\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe BMXERT1604T supports event recording with 1 ms time stamps. This allows changes in discrete process signals to be recorded with timing information, helping engineers analyze the sequence of events during process disturbances, equipment trips, and control-system diagnostics.\u003c\/p\u003e\n\u003cp\u003eThe module accepts external time synchronization signals through DCF77 and IRIG-B interfaces. These protocols provide a time reference for event records, which is particularly relevant when comparing events collected by multiple modules or distributed control-system components.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eElectrical Characteristics and Isolation\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module has a maximum power consumption of 4 W for process inputs. Its current consumption is specified separately for the two supply rails: 30 mA at 24 V DC and 130 mA at 3.3 V DC.\u003c\/p\u003e\n\u003cp\u003eThe specified isolation ratings are:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e2500 V DC for 60 seconds between the bus and discrete inputs.\u003c\/li\u003e\n\u003cli\u003e1400 V DC for 60 seconds between the bus and IRIG\/DCF interfaces.\u003c\/li\u003e\n\u003cli\u003e2500 V DC for 60 seconds between discrete inputs and IRIG\/DCF interfaces.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThese ratings describe the specified insulation withstand conditions, rather than continuous operating voltages.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eInstallation and Diagnostics\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe BMXERT1604T supports hot swapping. Its local LED indicators provide information about module operation, time-code input status, module faults, power supply interruption, and the individual states of all 16 inputs.\u003c\/p\u003e\n\u003cp\u003eThe module occupies 32 mm of rack width and measures 86 mm in depth and 100 mm in height. Its 28-pin removable terminal block is provided separately, so the required connection accessory should be checked when planning a replacement or new installation.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXERT1604T\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Range\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eMultifunction Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n\u003ctd\u003e16 discrete inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Configuration\u003c\/td\u003e\n\u003ctd\u003e4 groups of 4 process inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Supply Voltage\u003c\/td\u003e\n\u003ctd\u003e24 V DC (19-30 V DC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Supply Voltage\u003c\/td\u003e\n\u003ctd\u003e48-60 V DC (38-75 V DC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Supply Voltage\u003c\/td\u003e\n\u003ctd\u003e110-125 V DC (88-156 V DC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSwitching Voltage\u003c\/td\u003e\n\u003ctd\u003e24 V at 6.7 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSwitching Voltage\u003c\/td\u003e\n\u003ctd\u003e48 V at 2.5 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSwitching Voltage\u003c\/td\u003e\n\u003ctd\u003e60 V at 2.5 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSwitching Voltage\u003c\/td\u003e\n\u003ctd\u003e110 V at 1.3 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSwitching Voltage\u003c\/td\u003e\n\u003ctd\u003e125 V at 1.3 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eData Recording\u003c\/td\u003e\n\u003ctd\u003e1 ms time stamps\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTime Synchronization Protocols\u003c\/td\u003e\n\u003ctd\u003eDCF77, IRIG-B\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnti-Bounce Filtering\u003c\/td\u003e\n\u003ctd\u003eConfigurable from 0 to 255 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSampling Duration\u003c\/td\u003e\n\u003ctd\u003e0.5 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAcquisition Time\u003c\/td\u003e\n\u003ctd\u003e1 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Power Consumption\u003c\/td\u003e\n\u003ctd\u003e4 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003e30 mA at 24 V DC; 130 mA at 3.3 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Voltage\u003c\/td\u003e\n\u003ctd\u003e2500 V DC, 60 s, bus to discrete input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Voltage\u003c\/td\u003e\n\u003ctd\u003e1400 V DC, 60 s, bus to IRIG\/DCF\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Voltage\u003c\/td\u003e\n\u003ctd\u003e2500 V DC, 60 s, discrete input to IRIG\/DCF\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHot Swap\u003c\/td\u003e\n\u003ctd\u003eSupported\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWidth\u003c\/td\u003e\n\u003ctd\u003e32 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHeight\u003c\/td\u003e\n\u003ctd\u003e100 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDepth\u003c\/td\u003e\n\u003ctd\u003e86 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-25 to 70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e95%, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Operating Altitude\u003c\/td\u003e\n\u003ctd\u003e4000 m\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLocal Diagnostics\u003c\/td\u003e\n\u003ctd\u003eRUN, T, ERR, I\/O and 16 input status LEDs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Certifications\u003c\/td\u003e\n\u003ctd\u003eCE, RCM, CSA, EAC, Merchant Navy, UL\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStandards\u003c\/td\u003e\n\u003ctd\u003eIEC 61010-2-201, IEC 61131-2, UL 61010-2-201, CSA C22.2 No. 61010-2-201\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEnvironmental Resistance\u003c\/td\u003e\n\u003ctd\u003eGx, 3C4, 3S4, 3B2; salt resistance level 2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCountry of Origin\u003c\/td\u003e\n\u003ctd\u003eUS\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eGTIN\u003c\/td\u003e\n\u003ctd\u003e3595864146232\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Weight\u003c\/td\u003e\n\u003ctd\u003e0.119 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can the BMXERT1604T record the sequence of discrete input events?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. It supports 1 ms time-stamped data recording. DCF77 and IRIG-B provide external time synchronization references for event records.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What input voltage levels can the BMXERT1604T accept?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: It supports 24 V DC, 48-60 V DC, and 110-125 V DC input classes. The corresponding permitted voltage ranges are 19-30 V DC, 38-75 V DC, and 88-156 V DC. The field signal must match the selected input configuration.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Is the BMXERT1604T supplied with its terminal block?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The 28-pin removable terminal block is specified as a separate accessory. The connection accessory must therefore be checked separately when ordering the module or preparing a replacement.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":68121713705245,"sku":"BMXERT1604T","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/BMXERT1604T.jpg?v=1794997577","url":"https:\/\/www.6gcontrols.com\/products\/schneider-electric-bmxert1604t-modicon-x80-multifunction-input-module","provider":"6G Controls","version":"1.0","type":"link"}