{"product_id":"schneider-bmxcps2010-modicon-x80-power-supply-module","title":"Schneider BMXCPS2010 Modicon X80 Power Supply Module","description":"\u003cp\u003eThe \u003cstrong\u003eSchneider BMXCPS2010\u003c\/strong\u003e is an isolated 24 VDC power supply module for the Modicon X80 platform, providing power to the I\/O modules and processor through the rack backplane. It delivers 16.8 W at 24 VDC and 8.3 W at 3.3 VDC for the I\/O logic supply. The module includes secondary-circuit overload, overvoltage and short-circuit protection, along with a rack voltage status LED and a RESET button for cold restart.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003ePower Supply Function\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe BMXCPS2010 converts an external isolated 24 VDC input into the secondary supply rails required by the Modicon X80 rack. Its outputs serve different functions: the 24 VDC rail supplies the I\/O modules and processor, while the 3.3 VDC rail supplies I\/O module logic.\u003c\/p\u003e\n\u003cp\u003eThe module provides 0.7 A at 24 VDC and 2.5 A at 3.3 VDC. These separate output ratings should be considered when checking the total power requirements of the installed rack configuration.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eProtection and Status Indication\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe secondary circuits include overload, overvoltage and short-circuit protection for the 24 VDC sensor supply. The primary-circuit internal fuse is not accessible. A green LED indicates that rack voltage is OK, allowing maintenance personnel to check the power supply status locally.\u003c\/p\u003e\n\u003cp\u003eA RESET button provides a cold-start reset function. The module also has a two-pin alarm relay connector for the alarm circuit.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eElectrical Connections and Installation\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module uses a five-pin connector for the supply input, protective earth and 24 VDC input sensor connection. It must be installed in a compatible module rack and secured with two screws.\u003c\/p\u003e\n\u003cp\u003eThe specified maximum cable distances depend on the copper conductor cross-section:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e20 m with 1.5 mm2 copper power supply cable.\u003c\/li\u003e\n\u003cli\u003e30 m with 2.5 mm2 copper power supply cable.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe specified power interruption immunity is 1 ms. Primary-to-earth and primary-to-secondary insulation resistance are both at least 10 MOhm.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eParameter Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXCPS2010\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eModicon X80 Power Supply Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePrimary Voltage\u003c\/td\u003e\n\u003ctd\u003e24 VDC, isolated\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePrimary Voltage Range\u003c\/td\u003e\n\u003ctd\u003e18-31.2 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e1 A at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInrush Current\u003c\/td\u003e\n\u003ctd\u003e30 A at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSecondary Power\u003c\/td\u003e\n\u003ctd\u003e16.8 W at 24 VDC; 8.3 W at 3.3 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSecondary Current\u003c\/td\u003e\n\u003ctd\u003e0.7 A at 24 VDC; 2.5 A at 3.3 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Power Dissipation\u003c\/td\u003e\n\u003ctd\u003e8.5 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Interruption Immunity\u003c\/td\u003e\n\u003ctd\u003e1 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection\u003c\/td\u003e\n\u003ctd\u003eSecondary overload, overvoltage and short-circuit protection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Indicator\u003c\/td\u003e\n\u003ctd\u003e1 green LED, rack voltage OK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eReset Function\u003c\/td\u003e\n\u003ctd\u003eCold-start RESET button\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Connections\u003c\/td\u003e\n\u003ctd\u003e2-pin alarm relay connector; 5-pin power supply connector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Cable Distance\u003c\/td\u003e\n\u003ctd\u003e20 m with 1.5 mm2 copper cable; 30 m with 2.5 mm2 copper cable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInsulation Resistance\u003c\/td\u003e\n\u003ctd\u003eAt least 10 MOhm, primary\/earth and primary\/secondary\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDielectric Strength\u003c\/td\u003e\n\u003ctd\u003e1500 V, primary\/earth and primary\/secondary\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5-95% at 55 deg C, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoating\u003c\/td\u003e\n\u003ctd\u003eTC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Altitude\u003c\/td\u003e\n\u003ctd\u003e0-2000 m; derating required from 2000 to 5000 m\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVibration Resistance\u003c\/td\u003e\n\u003ctd\u003e3 Gn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShock Resistance\u003c\/td\u003e\n\u003ctd\u003e30 gn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMTBF\u003c\/td\u003e\n\u003ctd\u003e4,886,000 h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.29 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEAN\u003c\/td\u003e\n\u003ctd\u003e3595863909005\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTotal Lifecycle Carbon Footprint\u003c\/td\u003e\n\u003ctd\u003e456 kg CO2 eq.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eBackplane Compatibility\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe BMXCPS2010 is designed for Modicon X80 module racks used in Modicon M340 and Modicon M580 automation architectures. However, it is explicitly listed as \u003cstrong\u003enot compatible with BMEXBP..02 backplanes\u003c\/strong\u003e. Rack selection should therefore be checked against the exact backplane reference before installation.\u003c\/p\u003e\n\u003cp\u003eThe module is specified for IP20 protection and compliance with EN 61131-2, EN 61000-6-4, EN 61000-6-2 and EN 61010-2-201. Listed approvals include CE, RCM, Merchant Navy, CSA, EAC and UL.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can the BMXCPS2010 operate with a 24 VDC input below 24 V?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. Its specified primary voltage range is 18-31.2 VDC. The input supply should remain within this range under normal operating and load conditions.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Is the BMXCPS2010 compatible with all Modicon X80 backplanes?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: No. Although it is specified for Modicon X80 racks, it is explicitly excluded from BMEXBP..02 backplanes. Check the exact rack reference before selecting this power supply.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the difference between the 24 VDC and 3.3 VDC outputs?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The 24 VDC output supplies the I\/O modules and processor, while the 3.3 VDC output supplies I\/O module logic. Both output power ratings must be considered when checking the rack power budget.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":68095697682717,"sku":"BMXCPS2010","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/BMXCPS20102.jpg?v=1794821068","url":"https:\/\/www.6gcontrols.com\/ro\/products\/schneider-bmxcps2010-modicon-x80-power-supply-module","provider":"6G Controls","version":"1.0","type":"link"}