{"product_id":"schneider-electric-bmxart0814h-modicon-x80-analog-input-module","title":"Schneider Electric BMXART0814H Modicon X80 Analog Input Module","description":"\u003cp\u003eConfigured for multi-range temperature and low-level analog measurement in the Modicon X80 platform, the \u003cstrong\u003eSchneider Electric BMXART0814H\u003c\/strong\u003e (\u003cstrong\u003eBMXART0814H\u003c\/strong\u003e Analog Input Module) provides eight isolated analog input channels with 15 bits + sign resolution. The module supports RTD, thermocouple, resistance, and low-level voltage inputs through a 40-way electrical connection.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXART0814H\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePlatform\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eApplication\u003c\/td\u003e\n\u003ctd\u003eSevere environments\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Isolation\u003c\/td\u003e\n\u003ctd\u003eIsolated between channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Level\u003c\/td\u003e\n\u003ctd\u003eLow level\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Input Resolution\u003c\/td\u003e\n\u003ctd\u003e15 bits + sign\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA\/D Conversion\u003c\/td\u003e\n\u003ctd\u003eSigma delta, 16 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Types\u003c\/td\u003e\n\u003ctd\u003eVoltage, resistance, RTD, thermocouple\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Ranges\u003c\/td\u003e\n\u003ctd\u003e+\/- 40 mV, +\/- 80 mV, +\/- 160 mV, +\/- 320 mV, +\/- 640 mV, +\/- 1.28 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResistance Inputs\u003c\/td\u003e\n\u003ctd\u003e400 Ohm and 4000 Ohm, 2\/3\/4 wire\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRTD Inputs\u003c\/td\u003e\n\u003ctd\u003eCu 10, Ni 100, Ni 1000, Pt 100, Pt 1000\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eThermocouple Types\u003c\/td\u003e\n\u003ctd\u003eB, E, J, K, L, N, R, S, T, U\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCold Junction Compensation\u003c\/td\u003e\n\u003ctd\u003eExternal Pt100 probe\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Mode Rejection\u003c\/td\u003e\n\u003ctd\u003e120 dB at 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDifferential Mode Rejection\u003c\/td\u003e\n\u003ctd\u003e60 dB at 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDigital Filtering\u003c\/td\u003e\n\u003ctd\u003eFirst order\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTemperature Probe Read Cycle\u003c\/td\u003e\n\u003ctd\u003e400 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eThermocouple Read Cycle\u003c\/td\u003e\n\u003ctd\u003e200 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMeasurement Resolution\u003c\/td\u003e\n\u003ctd\u003e0.1 deg C for temperature inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Wiring Resistance\u003c\/td\u003e\n\u003ctd\u003eUp to 500 Ohm depending on sensor and wiring configuration\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRecalibration\u003c\/td\u003e\n\u003ctd\u003eInternal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiagnostic LEDs\u003c\/td\u003e\n\u003ctd\u003eRUN, channel diagnostic, ERR, I\/O\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Connection\u003c\/td\u003e\n\u003ctd\u003e40-way, 2 connectors\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003e150 mA at 3.3 VDC; 50 mA at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.165 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-25 to 70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5-95% at 55 deg C, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVibration Resistance\u003c\/td\u003e\n\u003ctd\u003e3 gn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShock Resistance\u003c\/td\u003e\n\u003ctd\u003e30 gn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Altitude\u003c\/td\u003e\n\u003ctd\u003e0 to 2000 m; 2000 to 5000 m with derating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtective Treatment\u003c\/td\u003e\n\u003ctd\u003eConformal coating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCertifications\u003c\/td\u003e\n\u003ctd\u003eCSA, UL, IEC-Ex, CE, Merchant Navy, RCM, ATEX, EAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStandards\u003c\/td\u003e\n\u003ctd\u003eIEC 61131-2, IEC 61000-6-4, IEC 61000-6-2, EN 61010-2-201\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003ePLC Backplane and Analog Signal Characteristics\u003c\/h3\u003e\n\u003cp\u003eThe BMXART0814H is an X80 analog input module with eight isolated channels. Its input circuitry accepts low-level voltage signals, resistance measurements, RTD sensors, and thermocouples. The sigma-delta converter provides 16-bit internal conversion, while the specified analog input resolution is 15 bits + sign.\u003c\/p\u003e\n\u003cp\u003eFor temperature measurement, the module supports multiple IEC and UL\/JIS sensor configurations. External Pt100 cold junction compensation is specified for thermocouple measurement. Open-circuit detection is provided for supported RTD and thermocouple inputs.\u003c\/p\u003e\n\u003cp\u003eThe module provides 120 dB common-mode rejection and 60 dB differential-mode rejection at 50\/60 Hz. These characteristics apply to the analog signal acquisition path and should be considered when routing sensor wiring near power conductors or switching equipment.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What sensor types can the BMXART0814H accept?\u003c\/strong\u003e\u003cbr\u003e\u003cstrong\u003eA:\u003c\/strong\u003e It supports Cu 10, Ni 100, Ni 1000, Pt 100, Pt 1000, thermocouples B\/E\/J\/K\/L\/N\/R\/S\/T\/U, 400 Ohm and 4000 Ohm resistance inputs, and low-level voltage ranges from +\/- 40 mV to +\/- 1.28 V.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How is thermocouple cold junction compensation implemented?\u003c\/strong\u003e\u003cbr\u003e\u003cstrong\u003eA:\u003c\/strong\u003e Cold junction compensation is specified as external compensation using a Pt100 probe.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the module provide channel isolation and diagnostics?\u003c\/strong\u003e\u003cbr\u003e\u003cstrong\u003eA:\u003c\/strong\u003e Yes. The inputs are isolated between channels, and the front diagnostics include a RUN LED, one diagnostic LED per channel, ERR, and I\/O indicators.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eInstall the BMXART0814H on the applicable Modicon X80 rack and establish the electrical connection through the specified 40-way connector arrangement.\u003c\/p\u003e\n\u003cp\u003eRoute thermocouple and RTD wiring separately from high-current and switching circuits where practical. Maintain appropriate shielding and grounding practices for low-level analog signals. Avoid creating unintended ground loops between sensor circuits, shields, and cabinet grounding points.\u003c\/p\u003e\n\u003cp\u003eVerify the selected input type and measurement range in the PAC configuration before connecting field sensors. For RTD measurements, select the correct 2-wire, 3-wire, or 4-wire configuration and remain within the specified wiring resistance limit.\u003c\/p\u003e\n\u003cp\u003eFor thermocouple channels, verify the configured thermocouple type and the external Pt100 cold junction compensation arrangement. Confirm sensor polarity before commissioning.\u003c\/p\u003e\n\u003cp\u003eThe conformal-coated BMXART0814H is specified for operation from -25 to 70 deg C and IP20 protection. The enclosure and cabinet installation should provide the required environmental protection because IP20 does not provide protection against water or dust ingress.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":52999032373533,"sku":"BMXART0814H","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/BMXART0814H2.jpg?v=1789970162","url":"https:\/\/www.6gcontrols.com\/ro\/products\/schneider-electric-bmxart0814h-modicon-x80-analog-input-module","provider":"6G Controls","version":"1.0","type":"link"}