{"product_id":"schneider-electric-bmxamo0410-modicon-x80-analog-output-module","title":"Schneider Electric BMXAMO0410 Modicon X80 Analog Output Module","description":"\u003cp\u003eConfigured for isolated analog signal output in the Modicon X80 platform, the \u003cstrong\u003eSchneider Electric BMXAMO0410\u003c\/strong\u003e (\u003cstrong\u003eBMXAMO0410\u003c\/strong\u003e Analog Output Module) provides four electrically isolated channels for 0-20 mA, 4-20 mA, or +\/-10 V output. The module communicates with the PLC through the rack backplane and uses a 20-way connector for field wiring.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXAMO0410\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog output module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Outputs\u003c\/td\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Signals\u003c\/td\u003e\n\u003ctd\u003e0-20 mA, 4-20 mA, +\/-10 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Resolution\u003c\/td\u003e\n\u003ctd\u003e15 bits + sign\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Isolation\u003c\/td\u003e\n\u003ctd\u003eIsolated\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation Voltage\u003c\/td\u003e\n\u003ctd\u003e1400 V DC between channels and ground; 1400 V DC between channels and bus; 750 V DC between channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConversion Time\u003c\/td\u003e\n\u003ctd\u003e\u0026lt;= 1 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMinimum Crosstalk Attenuation\u003c\/td\u003e\n\u003ctd\u003e80 dB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Mode Rejection\u003c\/td\u003e\n\u003ctd\u003e100 dB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMeasurement Error\u003c\/td\u003e\n\u003ctd\u003e\u0026lt;= 0.2% of full scale from 0 to 60 deg C; 0.1% of full scale at 25 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLoad Impedance\u003c\/td\u003e\n\u003ctd\u003e\u0026gt;= 1000 Ohm for +\/-10 V; \u0026lt;= 500 Ohm for 0-20 mA and 4-20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Connection\u003c\/td\u003e\n\u003ctd\u003e20-way connector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupply\u003c\/td\u003e\n\u003ctd\u003eInternal power supply via rack\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e3 W at 24 VDC typical; 3.6 W maximum; 0.45 W at 3.3 VDC typical; 0.51 W maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003e150 mA at 3.3 VDC; 140 mA at 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.15 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e32 x 100 x 86 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5-95% at 55 deg C, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Altitude\u003c\/td\u003e\n\u003ctd\u003e0 to 2000 m; 2000 to 5000 m with derating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVibration Resistance\u003c\/td\u003e\n\u003ctd\u003e3 gn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShock Resistance\u003c\/td\u003e\n\u003ctd\u003e30 gn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompatible PLC Platforms\u003c\/td\u003e\n\u003ctd\u003eModicon M340 and Modicon M580 local or remote I\/O\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtective Treatment\u003c\/td\u003e\n\u003ctd\u003eStandard version\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Indication\u003c\/td\u003e\n\u003ctd\u003eRUN, channel diagnostics, ERR, I\/O LEDs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eAnalog Output Isolation and Signal Characteristics\u003c\/h3\u003e\n\u003cp\u003eThe BMXAMO0410 provides four isolated high-level analog outputs. Each channel can be configured for current or voltage output according to the supported signal ranges. The specified isolation voltage is 1400 V DC between channels and ground and between channels and the bus.\u003c\/p\u003e\n\u003cp\u003eThe module provides 80 dB minimum crosstalk attenuation and 100 dB common mode rejection. Open-circuit detection is provided for 0-20 mA and 4-20 mA outputs, while short-circuit detection is specified for +\/-10 V outputs. Fallback operation can be configured or predefined.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: What output signals does the BMXAMO0410 support?\u003cbr\u003eA: It supports 0-20 mA, 4-20 mA, and +\/-10 V analog outputs across four channels.\u003c\/p\u003e\n\u003cp\u003eQ: How is the module powered?\u003cbr\u003eA: The module receives its internal power through the Modicon X80 rack backplane.\u003c\/p\u003e\n\u003cp\u003eQ: Can the BMXAMO0410 be installed on both M340 and M580 systems?\u003cbr\u003eA: Yes. The supplied data specifies compatibility with Modicon M340 and Modicon M580 PLCs for local or remote I\/O configurations.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eInstall the BMXAMO0410 on the specified Modicon X80 rack and secure the module with the two required mounting screws. Use the appropriate 20-way removable terminal block for field wiring.\u003c\/p\u003e\n\u003cp\u003eRoute analog signal conductors separately from high-current power wiring and switching conductors where practical. Maintain appropriate shielding and grounding practices for the connected analog circuits. Verify the selected current or voltage mode and the corresponding load impedance before energizing the field circuit.\u003c\/p\u003e\n\u003cp\u003eConfirm rack power availability and module seating before commissioning. Check the RUN, ERR, I\/O, and channel diagnostic LEDs after startup. For remote I\/O installations, verify the communication path and rack configuration before applying output commands.\u003c\/p\u003e","brand":"Schneider","offers":[{"title":"Default Title","offer_id":52998567854365,"sku":"BMXAMO0410","price":9.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0983\/5387\/3181\/files\/BMXAMO04102.jpg?v=1789962703","url":"https:\/\/www.6gcontrols.com\/sr\/products\/schneider-electric-bmxamo0410-modicon-x80-analog-output-module","provider":"6G Controls","version":"1.0","type":"link"}