The GE IC200MDL940F is a 16-point relay output module in the VersaMax I/O product family. It provides individually isolated Form A (normally open) relay contacts for switching external AC and DC field loads. Its voltage-dependent contact ratings allow the module to handle different field circuit requirements, while individual channel indicators provide local output status information.

Output Configuration and Switching

The module uses 16 normally open mechanical relay contacts. Each output operates as a dry contact: the PLC output command controls relay operation, while the external field power supply provides the energy required by the connected load.

Individual channel isolation allows separate field circuits to be switched without sharing a common output reference. This is useful when different output points operate loads supplied from independent AC or DC circuits.

The relay contacts are rated for different current levels depending on the applied voltage:

  • 5-265 VAC: maximum 2.0 A per point.
  • 5-30 VDC: maximum 2.0 A per point.
  • 31-125 VDC: maximum 0.2 A per point.

These ratings are specified for resistive loads. The 2.0 A rating must not be applied to the entire DC voltage range. Inductive loads also require consideration of contact switching stress and suppression requirements.

Switching Characteristics and Output Protection

The maximum ON and OFF response times are both 10 ms. This is a mechanical relay output rather than a high-speed semiconductor output, so it is intended for discrete switching rather than pulse-width modulation or rapid repetitive switching.

For inductive loads, the specified maximum switching frequency is 20 cycles per minute. The module does not include internal output fuses or snubber circuits. External overcurrent protection and suitable suppression components should be selected according to the connected load.

Individual point-status LEDs indicate the output states, while the OK indicator provides information about backplane power availability.

Backplane Power and Installation

The module draws its operating power from the VersaMax backplane, with a maximum specified 5 VDC current consumption of 490 mA. The external field supply provides the power switched through the relay contacts; the backplane supply should not be confused with the field-load supply.

An appropriate VersaMax I/O carrier is required for field wiring termination. Before installation or replacement, verify the carrier arrangement, terminal assignments, field supply voltage and contact-current requirements against the installed hardware configuration.

Technical Specifications

Parameter Specification
Model IC200MDL940F
Brand GE
Product Series VersaMax
Product Type Relay Output Module
Number of Output Points 16
Relay Contact Type Form A, Normally Open (NO)
Relay Mechanism Fixed coil, moving armature
Contact Material Silver alloy
Output Voltage 0-265 VAC; 0-125 VDC
Nominal Output Voltage 120/240 VAC; 5/24/125 VDC
Maximum Load Current 2.0 A per point (5-265 VAC); 2.0 A per point (5-30 VDC); 0.2 A per point (31-125 VDC)
Minimum Load Current 10 mA per point
Channel-to-Channel Isolation Individually isolated points
ON Response Time 10 ms maximum
OFF Response Time 10 ms maximum
Switching Frequency 20 cycles per minute (inductive loads)
Output Voltage Drop 0.3 V maximum
Output Leakage Current Not applicable (open relay contact)
Backplane Power Supply 5 VDC
Backplane Current Consumption 490 mA maximum
External AC Field Supply Frequency 47-63 Hz

Frequently Asked Questions

Q: Can the IC200MDL940F switch different AC and DC voltage circuits simultaneously?

A: Yes. Its individually isolated relay contacts allow separate field circuits to use different AC or DC voltage sources, provided each circuit remains within the specified voltage and current ratings.

Q: What is the maximum DC switching current?

A: The maximum is 2.0 A per point at 5-30 VDC. For 31-125 VDC, the maximum decreases to 0.2 A per point. These ratings should be checked against the actual load characteristics.

Q: Does the IC200MDL940F provide built-in protection for inductive loads?

A: No. It does not include internal fuses or snubber circuits. External circuit protection and suitable transient suppression should be evaluated when switching relay coils, contactors or solenoid valves.

การชำระเงิน: T/T, Western Union

ท่าเรือขนส่ง: เซี่ยเหมิน

ระยะเวลาดำเนินการ: โดยทั่วไป 1–3 วันทำการหลังยืนยันการชำระเงิน (ขึ้นอยู่กับสินค้าในสต็อก)

จัดส่งทั่วโลก: เราจัดส่งชิ้นส่วนระบบอัตโนมัติทางอุตสาหกรรมให้แก่ลูกค้าทั่วโลก โดยจะแจ้งค่าขนส่งพร้อมใบขอใบเสนอราคาของคุณ

คำถามที่พบบ่อย

คำถามที่พบบ่อยเกี่ยวกับใบเสนอราคา การจัดส่ง การรับประกัน และการคืนสินค้า

คลิก ขอใบเสนอราคา ในหน้าสินค้า แล้วส่งหมายเลขชิ้นส่วน จำนวนที่ต้องการ และประเทศปลายทางให้เรา ทีมฝ่ายขายของเราจะตอบกลับพร้อมข้อมูลสินค้าที่มีจำหน่าย ราคา และระยะเวลาจัดส่งโดยประมาณ

สินค้าที่มีอยู่ในสต็อกโดยปกติจะจัดเตรียมหลังจากได้รับการชำระเงินและยืนยันคำสั่งซื้อแล้ว คำสั่งซื้อส่วนใหญ่จัดส่งจากคลังสินค้าของเราในประเทศจีน แต่สถานที่จัดส่งอาจแตกต่างกันไปตามสต็อกปัจจุบัน

ใช่ เราจัดส่งชิ้นส่วนระบบอัตโนมัติทางอุตสาหกรรมให้ลูกค้าทั่วโลก ค่าจัดส่งและระยะเวลาในการขนส่งขึ้นอยู่กับปลายทาง น้ำหนักพัสดุ ขนาดสินค้า และข้อกำหนดการนำเข้าของท้องถิ่น

เราใช้บริการ DHL, FedEx, UPS และบริษัทขนส่งระหว่างประเทศอื่น ๆ เป็นประจำ โดยสามารถเลือกผู้ให้บริการขนส่งได้ตามปลายทาง ความเร็วในการจัดส่ง ขนาดของพัสดุ และความต้องการของลูกค้า

โดยทั่วไป สินค้าของเราครอบคลุมการรับประกัน 12 เดือน สินค้าที่มีสิทธิ์ยังสามารถส่งคืนได้ภายใต้นโยบายคืนเงินภายใน 30 วัน โปรดติดต่อทีมงานของเราก่อนส่งคืนสินค้าใด ๆ เพื่อยืนยันข้อกำหนดที่ใช้บังคับและคำแนะนำในการส่งคืน

Products FAQs

คุณอาจชอบสิ่งเหล่านี้ด้วย