แจ้งเตือนทางอีเมลเมื่อสินค้านี้พร้อมจำหน่าย
- คำอธิบาย
- Reviews
- การจัดส่งและการชำระเงิน
The Schneider Electric BMXEHC0200H is a hardened high-speed counter module for the Modicon M340 automation platform. It provides two independent high-speed counting channels for processing signals from proximity sensors and incremental encoders. The module supports counting frequencies up to 60 kHz and includes configurable counting functions, auxiliary inputs, and two discrete outputs for counter-related control operations.
High-Speed Counting and Signal Processing
The BMXEHC0200H provides two high-speed counter channels, each designed to process external pulse signals. It accepts signals from 2-wire or 3-wire proximity sensors operating at 19.2-30 V DC, incremental encoders with push-pull outputs, and 10-30 V DC totem-pole devices.
Its counting functions support different measurement and control requirements:
- Ratio counting and event counting.
- Frequency measurement.
- Up/down counting.
- 32-bit counter operation.
- Loop (modulo) counting.
- Time-period measurement.
- Width modulation.
The 1 ms cycle time supports periodic counter processing. The maximum counting frequency of 60 kHz defines the upper input pulse frequency supported by the module.
Input and Output Configuration
The module provides six inputs in total: three high-speed inputs and three auxiliary inputs. The input interface supports 24 V DC Type 3 signals, with defined voltage and current thresholds for reliable state recognition.
Two discrete outputs are available, with positive or negative logic configurable. Integrated overload and short-circuit protection provides electrical protection for the output circuits.
The output functions can be used in counter-related control operations. Actual load selection must account for the per-output current limit, module-level current limit, output voltage range, and load-current specifications.
Hardened Design for Severe Environments
The BMXEHC0200H belongs to the Modicon X80 common I/O platform and features conformal coating for operation in more demanding environmental conditions. Its specified operating temperature range is -25 to +70 deg C, with IP20 protection for the electronic assembly.
The environmental specifications include resistance classifications for gases, dust, sand, mold growth, and fungal spores. These characteristics are relevant when evaluating the module for installations exposed to industrial contaminants.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXEHC0200H |
| Brand | Schneider Electric |
| Product Type | Hardened High-Speed Counter Module |
| Product Range | Modicon X80 |
| Automation Platform | Modicon M340 |
| Application | Severe environments |
| Number of Channels | 2 |
| Maximum Counting Frequency | 60 kHz |
| Number of Inputs | 6 |
| High-Speed Inputs | 3 |
| Auxiliary Inputs | 3 |
| Input Voltage | 24 V DC, Type 3 |
| Input Compatibility | 19.2-30 V DC 2-wire/3-wire proximity sensors; incremental encoders with push-pull outputs; 10-30 V DC totem-pole signals |
| Input Current | 2 mA at 11 V |
| Voltage State 1 Guaranteed | 11-30 V DC |
| Current State 1 Guaranteed | Greater than 2 mA at U >= 11 V |
| Voltage State 0 Guaranteed | Less than 5 V DC |
| Current State 0 Guaranteed | Less than 1.5 mA |
| Number of Outputs | 2 |
| Output Voltage | 24 V DC |
| Output Voltage Limits | 19.2-30 V |
| Discrete Output Logic | Positive or negative configurable |
| Maximum Output Current | 2 A per module; 0.5 A per output |
| Maximum Load Current | 1 A per module; 0.5 A per output |
| Maximum Leakage Current | 0.1 mA at state 0 |
| Maximum Voltage Drop | Less than 3 V at state 1 |
| Output Overload Protection | Integrated |
| Output Short-Circuit Protection | Integrated, 1.5 A |
| Overlap Time | 0.2 ms |
| Counter Cycle Time | 1 ms |
| Counter Functions | Ratio count, frequency meter, down counting, 32-bit counting, modulo counting, time-period measurement, event counting, width modulation |
| Isolation Voltage | 1500 V for 60 s |
| Current Consumption | 200 mA at 3.3 V DC bus |
| Rack Current Consumption | 40 mA at 24 V DC rack |
| Sensor Power Consumption | 80 mA at 24 V DC sensor supply |
| Electrical Connections | 1 x 10-pin connector for auxiliary inputs and sensor power; 2 x 16-pin connectors for counter channel sensors |
| Module Format | Standard |
| Protective Treatment | Conformal coating |
| Operating Temperature | -25 to +70 deg C |
| Relative Humidity | 10-95%, non-condensing |
| Protection Rating | IP20 |
| Environmental Classification | Gx ISA S71.04; 3C4, 3S4 and 3B2 IEC 60721-3-3 |
| Hazardous Location Classification | Class I, Division 2 |
| Product Certifications | CE, UL, CSA, RCM, EAC |
| Standards | IEC 61131-2, IEC 61010-2-201, UL 61010-2-201, CSA C22.2 No. 61010-2-201, IACS E10 |
| Net Weight | 0.112 kg |
| Country of Origin | USA |
| GTIN | 3595864010410 |
Installation and Electrical Connections
The BMXEHC0200H is installed on the Modicon X80 rack and secured using two screws. Its three dedicated connectors separate the auxiliary input and sensor power wiring from the sensor connections for counter channels 0 and 1.
When preparing the wiring, verify the sensor output type, voltage levels, and input state thresholds. For output circuits, check both the 0.5 A per-output limit and the 1 A maximum module load current.
Frequently Asked Questions
Q: What is the difference between the two counter channels and the six inputs?
A: The module has two high-speed counter channels and six physical inputs in total. These comprise three high-speed inputs and three auxiliary inputs. The six-input configuration should not be interpreted as six independent high-speed counting channels.
Q: Which sensor types can be connected to the BMXEHC0200H?
A: The module supports 19.2-30 V DC 2-wire and 3-wire proximity sensors, incremental encoders with push-pull outputs, and 10-30 V DC totem-pole signals. The selected sensor must also meet the specified input voltage and current thresholds.
Q: Can the module operate in high-temperature industrial environments?
A: Yes. The specified operating temperature range is -25 to +70 deg C. Its conformal coating and environmental resistance classifications support applications in severe environments, subject to the specified installation and operating conditions.
การชำระเงิน: T/T, Western Union
ท่าเรือขนส่ง: เซี่ยเหมิน
ระยะเวลาดำเนินการ: โดยทั่วไป 1–3 วันทำการหลังยืนยันการชำระเงิน (ขึ้นอยู่กับสินค้าในสต็อก)
จัดส่งทั่วโลก: เราจัดส่งชิ้นส่วนระบบอัตโนมัติทางอุตสาหกรรมให้แก่ลูกค้าทั่วโลก โดยจะแจ้งค่าขนส่งพร้อมใบขอใบเสนอราคาของคุณ
คำถามที่พบบ่อย
คำถามที่พบบ่อยเกี่ยวกับใบเสนอราคา การจัดส่ง การรับประกัน และการคืนสินค้าคลิก ขอใบเสนอราคา ในหน้าสินค้า แล้วส่งหมายเลขชิ้นส่วน จำนวนที่ต้องการ และประเทศปลายทางให้เรา ทีมฝ่ายขายของเราจะตอบกลับพร้อมข้อมูลสินค้าที่มีจำหน่าย ราคา และระยะเวลาจัดส่งโดยประมาณ
สินค้าที่มีอยู่ในสต็อกโดยปกติจะจัดเตรียมหลังจากได้รับการชำระเงินและยืนยันคำสั่งซื้อแล้ว คำสั่งซื้อส่วนใหญ่จัดส่งจากคลังสินค้าของเราในประเทศจีน แต่สถานที่จัดส่งอาจแตกต่างกันไปตามสต็อกปัจจุบัน
ใช่ เราจัดส่งชิ้นส่วนระบบอัตโนมัติทางอุตสาหกรรมให้ลูกค้าทั่วโลก ค่าจัดส่งและระยะเวลาในการขนส่งขึ้นอยู่กับปลายทาง น้ำหนักพัสดุ ขนาดสินค้า และข้อกำหนดการนำเข้าของท้องถิ่น
เราใช้บริการ DHL, FedEx, UPS และบริษัทขนส่งระหว่างประเทศอื่น ๆ เป็นประจำ โดยสามารถเลือกผู้ให้บริการขนส่งได้ตามปลายทาง ความเร็วในการจัดส่ง ขนาดของพัสดุ และความต้องการของลูกค้า
โดยทั่วไป สินค้าของเราครอบคลุมการรับประกัน 12 เดือน สินค้าที่มีสิทธิ์ยังสามารถส่งคืนได้ภายใต้นโยบายคืนเงินภายใน 30 วัน โปรดติดต่อทีมงานของเราก่อนส่งคืนสินค้าใด ๆ เพื่อยืนยันข้อกำหนดที่ใช้บังคับและคำแนะนำในการส่งคืน
คุณอาจชอบสิ่งเหล่านี้ด้วย
บทความในบล็อก
ข่าวสารระบบอัตโนมัติในภาคอุตสาหกรรม คู่มือด้านเทคนิค และอัปเดตผลิตภัณฑ์