Ir a la información del producto
1 de 3

GE IS200ECTBG2ADE EX2100 Exciter Contact Terminal Board

11 disponibles en stock
  • Manufacturer: General Electric
  • Product No.: IS200ECTBG2ADE
  • Product Type: EX2100 Exciter Contact Terminal Board
  • Condition: Completamente nuevo
  • Payment: T/T, Western Union
  • Weight: 0.34 kg
  • Shipping port: Xiamen
  • Warranty: 12 meses
  • Descripción
  • Reviews
  • Envío y pago

The GE IS200ECTBG2ADE is an Exciter Contact Terminal Board for the EX2100 excitation control system. It provides field contact input monitoring and relay output interfaces between external equipment and the excitation controller. Designed for simplex operation, the board handles trip contacts, general-purpose relay outputs, and auxiliary contact signals using separate relay control and contact wetting voltages.

Functional Description

The ECTB provides electrical interfaces for contact signals associated with generator excitation control. Its relay outputs allow the controller to operate external circuits, while its contact input circuits monitor the status of customer-supplied auxiliary contacts.

The board includes two trip relay outputs and four general-purpose Form-C relay outputs. The latter provide normally open, normally closed, and common terminals for external circuit switching. Relay operation is controlled by the excitation controller through the EMIO interface.

Contact Input and Relay Configuration

The contact input circuits use a nominal 70 V DC wetting supply to detect external contact states. This arrangement allows the controller to monitor auxiliary contacts and dedicated generator status and lockout signals.

The distinction between the board's voltage ratings is important: 24 V DC supplies the relay control circuits, 125 V DC is the nominal customer supply for relay contacts, and 70 V DC provides contact wetting for input monitoring. These voltages serve different circuit functions.

Relay Contact Ratings

The general-purpose relay contacts use a customer-supplied DC power circuit. Their breaking capacity depends on the load type and operating voltage, rather than being represented by a single universal current rating.

According to the EX2100 control guide, the general-purpose relay contact characteristics include:

  • Resistive load: 2 A at 28 V DC or 0.5 A at 125 V DC.
  • Inductive load: 1 A at 28 V DC or 0.1 A at 125 V DC.
  • Inductive load rating is specified at an L/R time constant of 0.007 s.
  • External suppression must be provided by the customer for inductive loads.

These ratings should be checked against the actual external load before connecting field circuits.

Technical Specifications

Parameter Specification
Model IS200ECTBG2ADE
Brand General Electric (GE)
Series EX2100
Product Type Exciter Contact Terminal Board
Operational Mode Simplex only
Trip Relay Outputs 2
General-Purpose Relay Outputs 4 Form-C
Auxiliary Contact Inputs 6
Dedicated Contact Inputs 52G, 86G
Relay Control Voltage 24 V DC
Customer Power 125 V DC nominal
Contact Wetting Voltage 70 V DC
Relay Break Characteristic 28 V DC
Weight 0.34 kg
Dimensions 150 x 76 x 90 mm

Simplex Configuration and System Interface

The ECTBG2 configuration is intended for simplex EX2100 control. Its contact signals are connected to the M1 controller, rather than being distributed across multiple controllers for redundant voting.

The distinction between ECTBG1 and ECTBG2 is important when identifying replacement hardware. ECTBG1 supports redundant control with a two-out-of-three relay voting arrangement, whereas ECTBG2 is designed for simplex operation. These configurations should not be treated as interchangeable.

Frequently Asked Questions

Q: Can the IS200ECTBG2ADE be used in a redundant EX2100 control system?

A: No. The ECTBG2 configuration is intended for simplex operation. The ECTBG1 version is used for redundant control and has a different controller interface and relay voting arrangement.

Q: What is the difference between the 24 V DC and 125 V DC supplies?

A: The 24 V DC supply operates the relay control circuits, while the nominal 125 V DC customer supply is switched through the relay contacts to external circuits. They perform different electrical functions and should not be interchanged.

Q: What is the purpose of the 70 V DC wetting voltage?

A: It provides the electrical excitation required to monitor external contact states. The board uses this voltage for auxiliary contact monitoring and dedicated 52G and 86G status inputs.

Pago: T/T, Western Union.

Puerto de envío: Xiamen.

Plazo de entrega: Normalmente, de 1 a 3 días laborables después de confirmar el pago (sujeto a disponibilidad).

Envíos a todo el mundo: Enviamos piezas de automatización industrial a clientes de todo el mundo. El flete se cotiza con su solicitud de cotización.

Preguntas frecuentes

Preguntas frecuentes sobre cotizaciones, envíos, garantía y devoluciones

Haz clic en Solicitar un presupuesto en la página del producto y envíanos el número de pieza, la cantidad necesaria y el país de destino. Nuestro equipo de ventas responderá con la disponibilidad actual, el precio y el plazo de entrega estimado.

Los artículos disponibles normalmente se preparan después del pago y la confirmación del pedido. La mayoría de los pedidos se envían desde nuestro almacén en China, aunque la ubicación del envío puede variar según el inventario disponible.

Sí. Enviamos piezas de automatización industrial a clientes de todo el mundo. El costo de envío y el tiempo de tránsito dependen del destino, el peso del paquete, el tamaño del producto y los requisitos locales de importación.

Usamos habitualmente DHL, FedEx, UPS y otros servicios de mensajería internacionales. El transportista puede seleccionarse según el destino, la velocidad de entrega, el tamaño del envío y los requisitos del cliente.

Nuestros productos generalmente están cubiertos por una garantía de 12 meses. Los productos elegibles también pueden devolverse conforme a nuestra política de reembolso de 30 días. Ponte en contacto con nuestro equipo antes de devolver cualquier artículo para confirmar los términos aplicables y las instrucciones de devolución.

Products FAQs

También te puede gustar