Configured for isolated analog signal acquisition in the Modicon X80 platform, the Schneider Electric BMXAMI0410H (BMXAMI0410H analog input module) provides four high-level input channels for current and voltage measurement. It supports 16-bit analog resolution, channel isolation, conformal coating, and direct connection through a 20-way connector.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMXAMI0410H |
| Brand | Schneider Electric |
| Series | Modicon X80 |
| Product Type | Analog input module |
| Input Channels | 4 |
| Input Type | Isolated high-level analog input |
| Current Input | +/- 20 mA, 0...20 mA, 4...20 mA |
| Voltage Input | +/- 10 V, +/- 5 V, 0...10 V, 0...5 V, 1...5 V |
| Analog Input Resolution | 16 bits |
| A/D Conversion | 24 bits |
| Measurement Resolution | 0.92 uA for current ranges; 0.35 mV for voltage ranges |
| Input Impedance | 10 MOhm voltage mode; 250 Ohm + 3.6...50 Ohm internal protective resistor current mode |
| Channel Isolation | 300 VDC between channels |
| Isolation to Ground | 1400 VDC |
| Isolation to Bus | 1400 VDC |
| Crosstalk Attenuation | Minimum 80 dB |
| Common Mode Rejection | 90 dB |
| Conversion Cycle | 1 ms + 1 ms x number of channels used, fast read |
| Nominal Read Cycle | 5 ms for 4 channels |
| Measurement Error | 0.15% of full scale for current inputs at 25 deg C; 0.075% of full scale for voltage inputs at 25 deg C |
| Maximum Operating Error | Up to 0.55% of full scale for current inputs and 0.2% of full scale for voltage inputs over -25...70 deg C |
| Power Consumption | 0.82 W typical / 1.30 W maximum at 24 VDC |
| Current Consumption | 45 mA at 24 VDC; 150 mA at 3.3 VDC |
| Electrical Connection | 20-way connector |
| Protective Treatment | Conformal coating |
| Protection Rating | IP20 |
| Operating Temp | -25...70 deg C |
| Storage Temp | -40...85 deg C |
| Relative Humidity | 5...95% at 55 deg C, non-condensing |
| Vibration Resistance | 3 gn |
| Shock Resistance | 30 gn |
| Weight | 0.143 kg |
| Origin | US |
| Certifications | CE, RCM, CSA, EAC, Merchant Navy, UL, ATEX, IEC-Ex |
| Standards | IEC 61010-2-201, IEC 61131-2, UL 61010-2-201, CSA C22.2 No 61010-2-201 |
Industrial Control and Analog Signal Integrity
The BMXAMI0410H uses isolated input channels to separate analog measurement circuits from each other and from the Modicon X80 bus. The module accepts both current and voltage signal ranges, allowing channel configuration for 4-20 mA, 0-20 mA, +/- 20 mA, 0-10 V, +/- 10 V, 0-5 V, +/- 5 V, and 1-5 V signals.
A minimum 80 dB crosstalk attenuation and 90 dB common mode rejection are specified for signal acquisition. The module uses first-order digital filtering and provides a digital value range of -32768 to +32767 in maximum user scale, with +/-10000 as the default scale.
The conformal-coated construction is specified for severe environments. Environmental characteristics include gas resistance class Gx and 3C4, dust and sand resistance class 3S4, salt resistance level 2, and mold and fungal-spore resistance class 3B2.
Frequently Asked Questions
Q: What signal types can the BMXAMI0410H measure?
A: The four channels support +/- 20 mA, 0...20 mA, 4...20 mA, +/- 10 V, +/- 5 V, 0...10 V, 0...5 V, and 1...5 V input ranges.
Q: Are the four analog channels electrically isolated?
A: Yes. The module specifies 300 VDC isolation between channels and 1400 VDC isolation between channels and ground and between channels and the bus.
Q: What is the maximum power consumption of the module?
A: The specified maximum consumption is 1.30 W at 24 VDC. The typical value is 0.82 W.
Field Installation Guidelines
- Install the module in a compatible Modicon X80 rack and connect it through the specified 20-way connector.
- Verify the configured input range against the actual field transmitter or voltage source before energizing the channel.
- Keep analog signal wiring separated from high-current power and switching conductors to reduce electromagnetic coupling.
- Use appropriate shield termination practices for the installed signal and cabinet grounding design.
- Confirm channel isolation requirements when connecting field devices with different reference potentials.
- Maintain the specified operating temperature and humidity limits inside the enclosure.
- Check the RUN, channel diagnostic, ERR, and I/O LEDs during commissioning.
- Do not apply input voltages or currents outside the documented overload and conversion limits.
پرداخت: حواله بانکی، وسترن یونیون.
بندر حمل: شیامن.
زمان آمادهسازی: معمولاً ۱ تا ۳ روز کاری پس از تأیید پرداخت (مشروط به موجودی).
تحویل در سراسر جهان: قطعات اتوماسیون صنعتی را برای مشتریان سراسر جهان ارسال میکنیم. هزینه حمل با درخواست استعلام قیمت شما اعلام میشود.
پرسشهای متداول
پرسشهای متداول درباره قیمتها، ارسال، گارانتی و مرجوعیدر صفحهٔ محصول روی درخواست قیمت کلیک کنید و شمارهٔ قطعه، مقدار موردنیاز و کشور مقصد را برای ما ارسال کنید. تیم فروش ما دربارهٔ موجودی فعلی، قیمت و زمان تقریبی تحویل پاسخ خواهد داد.
اقلام موجود معمولاً پس از پرداخت و تأیید سفارش آماده میشوند. بیشتر سفارشها از انبار ما در چین ارسال میشوند، هرچند محل ارسال ممکن است بسته به موجودی فعلی متفاوت باشد.
بله. قطعات اتوماسیون صنعتی را برای مشتریان سراسر جهان ارسال میکنیم. هزینه ارسال و زمان حملونقل به مقصد، وزن بسته، اندازه محصول و الزامات واردات محلی بستگی دارد.
ما معمولاً از خدمات پیک بینالمللی DHL، FedEx، UPS و سایر شرکتها استفاده میکنیم. شرکت حملونقل را میتوان بر اساس مقصد، سرعت تحویل، اندازه محموله و نیازهای مشتری انتخاب کرد.
محصولات ما معمولاً شامل ضمانت ۱۲ماهه هستند. محصولات واجد شرایط همچنین ممکن است طبق سیاست بازپرداخت ۳۰روزه قابل بازگشت باشند. لطفاً پیش از بازگرداندن هر کالا با تیم ما تماس بگیرید تا شرایط قابلاعمال و دستورالعملهای بازگشت را تأیید کنید.
ممکن است اینها را هم بپسندید
پستهای وبلاگ
اخبار اتوماسیون صنعتی، راهنماهای فنی و بهروزرسانیهای محصولات.