The Schneider BMXCPS4002 is a Modicon X80 power supply module designed for redundant power architectures in PLC and PAC systems. It accepts a 100-240 V AC primary supply and provides separate 3.3 V DC and 24 V DC secondary outputs for module logic and I/O power distribution. Network-based diagnostics and redundancy monitoring support power supply status supervision in the control system.
Power Supply Function and Redundant Architecture
The BMXCPS4002 supplies the internal power requirements of an X80 module rack. Its 3.3 V DC output powers I/O module logic, while the 24 V DC output supplies I/O module power and the processor, subject to the specified load conditions.
The module supports redundant power architecture and provides redundancy status information. Its diagnostic functions include temperature monitoring, redundancy testing, operating time and remaining service-life information. These diagnostics can be accessed over the network.
Electrical Protection and Status Monitoring
The secondary circuits incorporate overload, overvoltage and short-circuit protection. These functions protect the downstream power distribution circuits against specified electrical fault conditions. The primary circuit also has internal protection.
Three green LEDs indicate voltage availability, redundancy status and overall power supply status. A RESET button provides a cold-start reset function.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXCPS4002 |
| Brand | Schneider Electric |
| Product Series | Modicon X80 |
| Product Type | Redundant Power Supply Module |
| Primary Voltage | 100-240 V AC |
| Primary Voltage Limits | 85-264 V |
| Supply Frequency | 50/60 Hz |
| Frequency Limits | 47-63 Hz |
| Apparent Power | 0.13 kVA |
| Input Current | 0.55 A at 240 V; 1.01 A at 115 V |
| Inrush Current | 30 A at 120 V; 60 A at 240 V |
| Secondary Output | 3.3 V DC and 24 V DC |
| Secondary Power | 18 W at 3.3 V DC; 40 W at 24 V DC |
| Secondary Current | 5.5 A at 3.3 V DC; 1.67 A at 24 V DC |
| Maximum Power Dissipation | 8.5 W |
| Power Interruption Immunity | 1 ms |
| Protection | Secondary overload, overvoltage and short-circuit protection |
| Diagnostics | Temperature monitoring, redundancy test, operating time and remaining operating life |
| Status Indicators | 3 green LEDs |
| Reset Function | Cold-start RESET button |
| Electrical Connections | 2-pin alarm relay connector; 5-pin power supply and protective earth connector |
| Insulation Resistance | >= 100 MOhm, primary/earth and primary/secondary |
| Dielectric Strength | 1500 V primary/secondary; 1500 V primary/earth; 2300 V sensor supply/secondary; 500 V sensor output/ground |
| Protection Rating | IP20 |
| Operating Temperature | 0 to 60 deg C |
| Storage Temperature | -40 to 85 deg C |
| Relative Humidity | 5-95% at 55 deg C, non-condensing |
| Operating Altitude | 0-2,000 m; derating required from 2,000 to 5,000 m |
| Coating | TC, Humiseal 1A33 |
| Environmental Classification | 3C3 and 3C4 according to IEC 60721-3-3 |
| Vibration Resistance | 3 Gn |
| Shock Resistance | 30 gn |
| MTBF | 792,000 h |
| Weight | 0.51 kg |
| EAN | 3606480927560 |
| Lifecycle Carbon Footprint | 496 kg CO2 eq. |
Electrical Connections and Installation
The BMXCPS4002 has separate connectors for the alarm relay and incoming power supply. The 5-pin connector provides the power supply and protective earth connections, while the 2-pin connector is used for the alarm relay.
Installation requirements include:
- Mount the module in a Modicon X80 module rack.
- Secure the power supply using two screws.
- Use the supplied removable 5-way and 2-way terminal blocks.
- Observe the specified operating temperature and altitude derating conditions.
The module has an IP20 protection rating and is intended for installation within an appropriate equipment enclosure.
Certifications and Standards
The product documentation identifies the following certifications and standards:
- Certifications: CE, RCM, Merchant Navy, CSA, EAC and UL.
- EN 61131-2
- EN 61000-6-4
- EN 61000-6-2
- EN 61010-2-201
- EU Low Voltage Directive 2014/35/EU
- EU EMC Directive 2014/30/EU
Frequently Asked Questions
Q: Can the BMXCPS4002 be used in a redundant power supply architecture?
A: Yes. The BMXCPS4002 is specified for redundant power architectures. Its redundancy monitoring functions provide status information for system-level supervision. The actual redundant configuration must follow the applicable Modicon X80 system design requirements.
Q: What are the two secondary output voltages used for?
A: The 3.3 V DC output supplies I/O module logic, while the 24 V DC output supplies I/O module power and the processor under the specified load conditions. The rated output powers are 18 W and 40 W respectively.
Q: Does the BMXCPS4002 provide network diagnostics?
A: Yes. Available diagnostic information includes temperature sensor data, redundancy test results, operating time and remaining operating life. These functions support remote monitoring of the power supply condition.
Paiement : virement bancaire, Western Union.
Port d’expédition : Xiamen.
Délai : généralement 1 à 3 jours ouvrés après confirmation du paiement (sous réserve des stocks).
Livraison dans le monde entier : nous expédions des pièces d’automatisation industrielle à des clients du monde entier. Les frais de transport sont indiqués avec votre demande de devis.
Foire aux questions (FAQ)
Questions fréquentes sur les devis, l’expédition, la garantie et les retoursCliquez sur Demander un devis sur la page du produit et envoyez-nous la référence, la quantité souhaitée et le pays de destination. Notre équipe commerciale vous répondra avec les disponibilités actuelles, le prix et le délai de livraison estimé.
Les articles en stock sont généralement préparés après le paiement et la confirmation de la commande. La plupart des commandes sont expédiées depuis notre entrepôt en Chine, bien que le lieu d’expédition puisse varier en fonction des stocks disponibles.
Oui. Nous expédions des pièces d’automatisation industrielle à des clients partout dans le monde. Les frais d’expédition et le délai de transport dépendent de la destination, du poids du colis, de la taille du produit et des exigences locales en matière d’importation.
Nous utilisons généralement DHL, FedEx, UPS et d’autres services de messagerie internationaux. Le transporteur peut être choisi en fonction de la destination, de la rapidité de livraison, de la taille de l’envoi et des exigences du client.
Nos produits sont généralement couverts par une garantie de 12 mois. Les produits admissibles peuvent également être retournés conformément à notre politique de remboursement sous 30 jours. Veuillez contacter notre équipe avant de retourner tout article afin de confirmer les conditions applicables et les instructions de retour.
Vous aimerez peut-être aussi
Articles de blog
Actualités sur l’automatisation industrielle, guides techniques et mises à jour des produits.