Notification par e-mail lorsque ce produit sera disponible
- Description
- Reviews
- Livraison et paiement
Configured for isolated analog signal acquisition in the Modicon X80 platform, the Schneider Electric BMXAMI0410H (BMXAMI0410H analog input module) provides four high-level input channels for current and voltage measurement. It supports 16-bit analog resolution, channel isolation, conformal coating, and direct connection through a 20-way connector.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMXAMI0410H |
| Brand | Schneider Electric |
| Series | Modicon X80 |
| Product Type | Analog input module |
| Input Channels | 4 |
| Input Type | Isolated high-level analog input |
| Current Input | +/- 20 mA, 0...20 mA, 4...20 mA |
| Voltage Input | +/- 10 V, +/- 5 V, 0...10 V, 0...5 V, 1...5 V |
| Analog Input Resolution | 16 bits |
| A/D Conversion | 24 bits |
| Measurement Resolution | 0.92 uA for current ranges; 0.35 mV for voltage ranges |
| Input Impedance | 10 MOhm voltage mode; 250 Ohm + 3.6...50 Ohm internal protective resistor current mode |
| Channel Isolation | 300 VDC between channels |
| Isolation to Ground | 1400 VDC |
| Isolation to Bus | 1400 VDC |
| Crosstalk Attenuation | Minimum 80 dB |
| Common Mode Rejection | 90 dB |
| Conversion Cycle | 1 ms + 1 ms x number of channels used, fast read |
| Nominal Read Cycle | 5 ms for 4 channels |
| Measurement Error | 0.15% of full scale for current inputs at 25 deg C; 0.075% of full scale for voltage inputs at 25 deg C |
| Maximum Operating Error | Up to 0.55% of full scale for current inputs and 0.2% of full scale for voltage inputs over -25...70 deg C |
| Power Consumption | 0.82 W typical / 1.30 W maximum at 24 VDC |
| Current Consumption | 45 mA at 24 VDC; 150 mA at 3.3 VDC |
| Electrical Connection | 20-way connector |
| Protective Treatment | Conformal coating |
| Protection Rating | IP20 |
| Operating Temp | -25...70 deg C |
| Storage Temp | -40...85 deg C |
| Relative Humidity | 5...95% at 55 deg C, non-condensing |
| Vibration Resistance | 3 gn |
| Shock Resistance | 30 gn |
| Weight | 0.143 kg |
| Origin | US |
| Certifications | CE, RCM, CSA, EAC, Merchant Navy, UL, ATEX, IEC-Ex |
| Standards | IEC 61010-2-201, IEC 61131-2, UL 61010-2-201, CSA C22.2 No 61010-2-201 |
Industrial Control and Analog Signal Integrity
The BMXAMI0410H uses isolated input channels to separate analog measurement circuits from each other and from the Modicon X80 bus. The module accepts both current and voltage signal ranges, allowing channel configuration for 4-20 mA, 0-20 mA, +/- 20 mA, 0-10 V, +/- 10 V, 0-5 V, +/- 5 V, and 1-5 V signals.
A minimum 80 dB crosstalk attenuation and 90 dB common mode rejection are specified for signal acquisition. The module uses first-order digital filtering and provides a digital value range of -32768 to +32767 in maximum user scale, with +/-10000 as the default scale.
The conformal-coated construction is specified for severe environments. Environmental characteristics include gas resistance class Gx and 3C4, dust and sand resistance class 3S4, salt resistance level 2, and mold and fungal-spore resistance class 3B2.
Frequently Asked Questions
Q: What signal types can the BMXAMI0410H measure?
A: The four channels support +/- 20 mA, 0...20 mA, 4...20 mA, +/- 10 V, +/- 5 V, 0...10 V, 0...5 V, and 1...5 V input ranges.
Q: Are the four analog channels electrically isolated?
A: Yes. The module specifies 300 VDC isolation between channels and 1400 VDC isolation between channels and ground and between channels and the bus.
Q: What is the maximum power consumption of the module?
A: The specified maximum consumption is 1.30 W at 24 VDC. The typical value is 0.82 W.
Field Installation Guidelines
- Install the module in a compatible Modicon X80 rack and connect it through the specified 20-way connector.
- Verify the configured input range against the actual field transmitter or voltage source before energizing the channel.
- Keep analog signal wiring separated from high-current power and switching conductors to reduce electromagnetic coupling.
- Use appropriate shield termination practices for the installed signal and cabinet grounding design.
- Confirm channel isolation requirements when connecting field devices with different reference potentials.
- Maintain the specified operating temperature and humidity limits inside the enclosure.
- Check the RUN, channel diagnostic, ERR, and I/O LEDs during commissioning.
- Do not apply input voltages or currents outside the documented overload and conversion limits.
Paiement : virement bancaire, Western Union.
Port d’expédition : Xiamen.
Délai : généralement 1 à 3 jours ouvrés après confirmation du paiement (sous réserve des stocks).
Livraison dans le monde entier : nous expédions des pièces d’automatisation industrielle à des clients du monde entier. Les frais de transport sont indiqués avec votre demande de devis.
Foire aux questions (FAQ)
Questions fréquentes sur les devis, l’expédition, la garantie et les retoursCliquez sur Demander un devis sur la page du produit et envoyez-nous la référence, la quantité souhaitée et le pays de destination. Notre équipe commerciale vous répondra avec les disponibilités actuelles, le prix et le délai de livraison estimé.
Les articles en stock sont généralement préparés après le paiement et la confirmation de la commande. La plupart des commandes sont expédiées depuis notre entrepôt en Chine, bien que le lieu d’expédition puisse varier en fonction des stocks disponibles.
Oui. Nous expédions des pièces d’automatisation industrielle à des clients partout dans le monde. Les frais d’expédition et le délai de transport dépendent de la destination, du poids du colis, de la taille du produit et des exigences locales en matière d’importation.
Nous utilisons généralement DHL, FedEx, UPS et d’autres services de messagerie internationaux. Le transporteur peut être choisi en fonction de la destination, de la rapidité de livraison, de la taille de l’envoi et des exigences du client.
Nos produits sont généralement couverts par une garantie de 12 mois. Les produits admissibles peuvent également être retournés conformément à notre politique de remboursement sous 30 jours. Veuillez contacter notre équipe avant de retourner tout article afin de confirmer les conditions applicables et les instructions de retour.
Vous aimerez peut-être aussi
Articles de blog
Actualités sur l’automatisation industrielle, guides techniques et mises à jour des produits.