Notification par e-mail lorsque ce produit sera disponible
- Description
- Reviews
- Livraison et paiement
The BMXDAO1605 is a 16-channel AC triac discrete output module in the Schneider Electric Modicon X80 range. It switches AC loads through solid-state outputs, with a rated operating voltage range of 100 to 240 V AC. The module provides individual channel switching, resistive-load response specifications, and external fast-blow fuse protection.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXDAO1605 |
| Brand | Schneider Electric |
| Product Range | Modicon X80 |
| Product Type | Discrete Output Module |
| Number of Outputs | 16 |
| Output Technology | Triac |
| Rated Output Voltage | 100 to 240 V AC |
| Output Voltage Range | 85 to 288 V AC |
| Current per Channel | 0.6 A |
| Output Current Limits | 0.025 to 4.8 A |
| Inrush Current | 20 A |
| Typical Current Consumption | 100 mA at 3.3 V DC |
| Output Response Time | 10 MOhm at 500 V DC |
| Dielectric Strength | 2830 V AC, 50/60 Hz, 1 min |
| Protection | 1 external fast-blow fuse |
| Protection Rating | IP20 |
| Protective Treatment | Standard version |
| MTBF | 1,800,000 h |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| Package Weight | 203 g |
| GTIN | 3595863966954 |
Output Operation and Protection
The BMXDAO1605 uses triac switching devices to control AC loads. Unlike electromechanical relay outputs, triac outputs have no mechanical contacts. Their solid-state switching characteristics make the module suitable for AC discrete control circuits where the load current and voltage remain within the specified operating limits.
The specified output response time of 1.011 ms applies to resistive-load activation and deactivation. Actual switching behavior with inductive or other non-resistive loads may differ and should be checked against the applicable load requirements.
Electrical Protection and Isolation
The module specifies one external fast-blow fuse as its output protection arrangement. Fuse selection and installation must account for the connected load and the applicable channel current limits. The 20 A inrush current specification should also be considered when evaluating loads with high starting currents.
The insulation resistance and dielectric strength ratings describe electrical isolation performance under the stated test conditions. They should not be interpreted as permission to exceed the rated operating voltage.
Modicon X80 Platform
The BMXDAO1605 belongs to the Modicon X80 common module platform, which is used with Modicon M340 and M580 Programmable Automation Controllers. Its platform classification identifies the product family; the actual rack configuration and controller compatibility should be checked against the relevant hardware configuration documentation.
Operating Conditions and Load Distribution
The output current must be assessed at both channel and group level. The module's total permissible load depends on the number of energized channels and ambient temperature; the individual channel rating should not be treated as an allowance to operate all 16 outputs simultaneously at maximum current.
For a 220 V AC resistive-load example, Schneider Electric's X80 module documentation specifies the following load conditions:
- At 0 to 40 deg C, 16 channels at 0.3 A each correspond to a total load of 4.8 A.
- Above 40 deg C, output loading must follow the specified temperature derating curve.
- At 60 deg C, the maximum total current is reduced to approximately 2.9 A, corresponding to 10 channels at 0.3 A or 16 channels at approximately 0.18 A.
These limits are important when distributing loads across the output groups and checking cabinet operating temperature.
Frequently Asked Questions
Q: What type of loads can the BMXDAO1605 switch?
A: It uses triac outputs for AC switching within the specified 100 to 240 V AC operating range. It is not a DC transistor output module.
Q: Does each output support 0.6 A continuously?
A: The 0.6 A figure is listed in Schneider Electric's product information, but it should not be interpreted as 0.6 A simultaneously on all 16 channels. Total current and channel loading are subject to group limits and temperature derating.
Q: What external protection is required?
A: The module specifies external fast-blow fuse protection. Schneider's connection documentation identifies a 3 A fast-blow fuse for each four-channel group; confirm the applicable wiring diagram and load requirements before installation.
Paiement : virement bancaire, Western Union.
Port d’expédition : Xiamen.
Délai : généralement 1 à 3 jours ouvrés après confirmation du paiement (sous réserve des stocks).
Livraison dans le monde entier : nous expédions des pièces d’automatisation industrielle à des clients du monde entier. Les frais de transport sont indiqués avec votre demande de devis.
Foire aux questions (FAQ)
Questions fréquentes sur les devis, l’expédition, la garantie et les retoursCliquez sur Demander un devis sur la page du produit et envoyez-nous la référence, la quantité souhaitée et le pays de destination. Notre équipe commerciale vous répondra avec les disponibilités actuelles, le prix et le délai de livraison estimé.
Les articles en stock sont généralement préparés après le paiement et la confirmation de la commande. La plupart des commandes sont expédiées depuis notre entrepôt en Chine, bien que le lieu d’expédition puisse varier en fonction des stocks disponibles.
Oui. Nous expédions des pièces d’automatisation industrielle à des clients partout dans le monde. Les frais d’expédition et le délai de transport dépendent de la destination, du poids du colis, de la taille du produit et des exigences locales en matière d’importation.
Nous utilisons généralement DHL, FedEx, UPS et d’autres services de messagerie internationaux. Le transporteur peut être choisi en fonction de la destination, de la rapidité de livraison, de la taille de l’envoi et des exigences du client.
Nos produits sont généralement couverts par une garantie de 12 mois. Les produits admissibles peuvent également être retournés conformément à notre politique de remboursement sous 30 jours. Veuillez contacter notre équipe avant de retourner tout article afin de confirmer les conditions applicables et les instructions de retour.
Vous aimerez peut-être aussi
Articles de blog
Actualités sur l’automatisation industrielle, guides techniques et mises à jour des produits.