ABB AI895 3BSC690086R1 Analog Input Module S800

Low stock: 10 left
  • Manufacturer: ABB
  • Product No.: AI895 3BSC690086R1
  • Country of origin: Sweden
  • Product Type: Analog Input Module
  • Condition: Brand New
  • Payment: T/T, Western Union
  • Weight: 0.2 kg
  • Dimensions: 45 x 102 x 119 mm
  • Shipping port: Xiamen
  • Warranty: 12 months
  • Description
  • Reviews
  • Shipping & Payment

The ABB AI895 3BSC690086R1, also cataloged as the AI895 Analog Input Module, provides eight 4-20 mA input channels with HART communication for the ABB S800 I/O system. Each channel supports two-wire transmitters and includes intrinsic safety protection for interfacing with process equipment in hazardous areas. With a suitable connection, the module also supports four-wire transmitters while retaining HART capability. It is compatible with TU890, TU891, and TU891Z Module Termination Units (MTUs).

Hardware Specifications

Parameter Specification
Model AI895
Article Number 3BSC690086R1
Brand ABB
Product Type Analog Input Module
I/O Platform S800 I/O
Weight 0.2 kg
Dimensions (W x D x H) 45 x 102 x 119 mm
Depth Including Connector 111 mm
Operating Temp 0 to +55 deg C
Storage Temperature -40 to +70 deg C
Max Ambient Temperature 55 deg C; 40 deg C for vertical mounting in compact MTU
Power Consumption 4.75 W power dissipation
Modulebus Current Consumption +5 V: typically 130 mA
External Supply Current +24 V: typically 270 mA, maximum less than 370 mA
Number of Channels 8
Signal Range 4-20 mA
Signal Type Unipolar single-ended
Resolution 12 bit
HART Communication Supported
Input Error Typically 0.05%, maximum 0.1%
Temperature Drift Typically 100 ppm/deg C
Input Filter Rise Time 20 ms, 0-90%
Under-range / Over-range 1.5 mA / 22 mA
Input Voltage Drop Typically 3 V, including PTC
Transmitter Supply At least 15 V at 20 mA loop current
Transmitter Overload Limit 23 mA
Isolation Groupwise isolated from ground
CMRR Greater than 80 dB at 50 Hz and 60 Hz
NMRR Greater than 10 dB at 50 Hz and 60 Hz
Rated Insulation Voltage 50 V
Dielectric Test Voltage 500 V AC
Intrinsic Safety Yes
Compatible MTUs TU890, TU891, TU891Z
Keying Code AE
Front Diagnostics Fault, Run, Warning, HART transmit LEDs
Internal Supervision Process supply
Protection Class IP20
Relative Humidity 5-95%, non-condensing
Pollution Degree 2
Corrosion Protection ISA-S71.04 G3
EMC Standards EN 61000-6-4, EN 61000-6-2
Electrical Safety EN 61010-1, EN 61010-2-201
Mechanical Conditions IEC/EN 61131-2
Hazardous Area Certifications ATEX/IECEx and North American hazardous-location ratings as specified by the manufacturer
Marine Certifications ABS, BV, DNV, LR, CCS
RoHS Compliance EU RoHS, UAE RoHS, CN RoHS
WEEE Compliance Directive 2012/19/EU

Intrinsic Safety and HART Signal Processing

The AI895 integrates intrinsic safety protection components on each input channel. Each channel can supply and monitor a two-wire process transmitter while supporting HART communication over the current loop. The built-in current-limited transmitter supply provides at least 15 V at a 20 mA loop current, with overload current limited to 23 mA.

Four-wire transmitters can also be connected using a specified wiring arrangement that preserves HART functionality. The input stage has a typical voltage drop of 3 V, including the PTC component. Installation design must account for this voltage drop when checking transmitter voltage requirements and available loop power.

Frequently Asked Questions

Q: Can the AI895 interface with both two-wire and four-wire transmitters?

A: Yes. Two-wire transmitters are powered and monitored by the module. Four-wire transmitters can be connected using the specified connection arrangement while retaining HART communication capability.

Q: Which MTUs are compatible with the AI895?

A: The module is specified for use with TU890, TU891, and TU891Z MTUs. TU890 is intended for Ex applications, while TU891 is intended for non-Ex applications. Confirm the applicable MTU variant and installation certification before commissioning.

Q: Does the AI895 support redundant operation or hot swapping?

A: The supplied specifications identify the module as non-redundant. They do not establish a hot-swap capability. Check the applicable ABB S800 hardware and system documentation before removing or replacing the module in an energized system.

Field Installation Guidelines

  • MTU selection: Verify the installed MTU type and its suitability for the intended hazardous-area application. Confirm compatibility with the system configuration before mounting the module.
  • Mechanical installation: Install the module in the designated S800 I/O position and verify connector engagement, mounting security, and access to the front diagnostic LEDs.
  • Transmitter wiring: Follow the ABB wiring diagram for each two-wire or four-wire transmitter arrangement. Check polarity, loop current requirements, and the voltage drop across the module before energizing the circuit.
  • HART communication: Maintain the specified loop wiring arrangement and verify HART communication after commissioning. Use the Tx LED and system diagnostics as applicable.
  • Hazardous-area installation: Observe the applicable intrinsic safety control drawings, entity parameters, grounding requirements, and hazardous-area certification conditions. Do not substitute a non-Ex MTU where an Ex-approved configuration is required.
  • Grounding and shielding: Apply the manufacturer's grounding and cable-shield termination instructions. Keep analog signal wiring separated from high-voltage conductors and switching power cables to reduce electromagnetic interference.
  • Power verification: Confirm the +5 V Modulebus and +24 V external supply requirements against the installed I/O system power budget. Check the external transmitter supply under the actual connected load.
  • Environmental limits: Maintain the specified operating temperature and humidity limits. For vertical mounting with a compact MTU, observe the 40 deg C maximum ambient temperature stated in the supplied data.
  • Commissioning checks: Verify channel configuration, 4-20 mA input response, transmitter supply voltage, HART communication, and Fault, Run, and Warning indications before placing the loop into service.

Payment: T/T, Western Union.

Shipping port: Xiamen.

Lead time: Typically 1–3 working days after payment confirmation (subject to stock).

Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.

F.A.Q.

Common questions about quotes, shipping, warranty and returns

Click Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.

In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.

Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.

We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.

Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.

Products FAQs

You may also like