The ABB GIS810 3BSE078740R1, also cataloged as the GIS810 Generic I/O Module, handles I/O data communication between the Fieldbus Communication Interface (FCI) and Signal Conditioning Modules (SCMs) in the ABB Ability System 800xA Select I/O architecture. It communicates upstream through Modulebus and supports up to 16 SCMs downstream. The module supports single or redundant configuration and hot swap.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | GIS810 |
| Article Number | 3BSE078740R1 |
| Brand | ABB |
| Product Type | Generic I/O Module |
| Platform | Select I/O / ABB Ability System 800xA |
| Communication | Modulebus |
| Downstream SCM Capacity | Up to 16 SCMs |
| HART | Yes |
| SOE | Yes |
| Redundancy | Yes |
| Hot Swap | Yes |
| High Integrity | No |
| Intrinsic Safety | N/A |
| Power Dissipation | 0.4 W |
| Operating Temp | -40 deg C to +70 deg C |
| Storage Temp | -40 deg C to +85 deg C |
| Relative Humidity | 5 to 95 %, non-condensing |
| Altitude | -1000 to 5000 m, restrictions apply |
| Pollution Degree | 2 according to IEC 60664-1 |
| Protection Class | IP20 according to IEC 60529 |
| Corrosive Atmosphere | G3 |
| Width | 77.9 mm |
| Depth | 108 mm |
| Height | 15.8 mm |
| Weight | 76 g |
| Power Consumption | 0.4 W power dissipation |
| Mechanical Conditions | IEC 61131-2 |
| EMC | IEC/EN 61000-6-4, IEC/EN 61000-6-2 |
| Overvoltage Category | Category II according to IEC 60664-1 |
| Electrical Safety | IEC/EN 61010-1, UL 61010-1, CSA-C22.2 No. 61010-1-12, IEC/EN 61010-2-201, UL 61010-2-201, CSA C22.2 No. 61010-2-201 |
| Marine Certification | DNV, ABS |
| CE Marking | Yes |
| UKCA | Yes |
| Hazardous Area ATEX | II 3G Ex nA IIC T4 Gc; II 3G Ex ec IIC T4 Gc; II 3G Ex ic nA IIC T4 Gc; II 3G Ex ic ec IIC T4 Gc |
| Hazardous Area IECEx | Available on IPA |
| Hazardous Location US/CAN | cULus; CL I, ZN 2 and CL I, DIV 2 classifications as specified |
| Hazardous Area CCC | Ex ec IIC T4 Gc; Ex ec ic IIC T4 Gc |
| RoHS | EU RoHS, UAE RoHS, CN RoHS |
| WEEE | EU |
Select I/O ModuleBus Communication and Diagnostics
GIS810 performs the communication layer between the FCI and the SCMs. The upstream interface uses Modulebus, while the downstream side communicates with up to 16 SCMs. Process I/O data is distributed between the connected SCMs and the FCI.
A mechanical locking slider disconnects the power supplies before module removal. Mechanical keying prevents insertion of an incorrect module type. LED indicators provide Status (S) and Primary (P) indications.
Diagnostics include internal hardware supervision, communication supervision, and internal power supervision. The module can operate in either single or redundant configuration.
Frequently Asked Questions
Q: Does the GIS810 support hot swap?
A: Yes. The module supports hot swap. The mechanical locking slider is designed to turn off the power supplies before removal.
Q: How many Signal Conditioning Modules can one GIS810 communicate with?
A: The GIS810 communicates downstream with up to 16 Signal Conditioning Modules.
Q: Can the GIS810 be used in hazardous areas?
A: Yes. The supplied specifications include ATEX, IECEx availability, cULus, and CCC hazardous-area classifications. The applicable certification and installation conditions must be verified for the specific installation.
Field Installation Guidelines
Install the GIS810 in the designated Select I/O mechanical position and ensure that the module is correctly keyed before insertion. Verify that the mechanical locking mechanism is engaged according to the installation procedure.
Route communication and field wiring separately from high-voltage or high-current conductors where practical. Maintain appropriate shielding and grounding practices for the connected I/O system and avoid creating unintended ground loops.
For hazardous-area installations, use only the approved installation arrangement and associated equipment required by the applicable ATEX, IECEx, cULus, or other certification. Verify enclosure, wiring, segregation, and environmental requirements before energization.
The module has an IP20 protection rating; therefore, the surrounding cabinet or enclosure must provide the environmental protection required by the installation. Confirm operating temperature, humidity, altitude, pollution degree, and corrosive-atmosphere conditions against the stated limits.
For replacement or hot-swap operations, follow the system maintenance procedure and use the mechanical locking slider to remove power from the module before extraction.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like
Blog Posts
Industrial automation news, technical guides, and product updates.