Configured for feeder, transformer, and motor protection in medium-voltage switchgear, the ABB REF542plus (1VCR007346) (REF542plus feeder terminal) provides integrated measurement, monitoring, protection, control, self-diagnostics, and substation communication.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | REF542plus (1VCR007346) |
| Brand | ABB |
| Series | REF542plus Series |
| Device Type | Feeder Terminal / Multifunction Digital Protection Relay |
| Rated System Voltage | 12 kV to 36 kV |
| Rated Current Range | 630 A to 5000 A |
| Rated Frequency | 50 Hz / 60 Hz |
| Protection Functions | Overcurrent, directional overcurrent, earth/ground fault, overvoltage, undervoltage, thermal overload, phase imbalance, short circuit |
| Measurement | Current, voltage, active power, reactive power, energy, frequency, power factor |
| Communication | Modbus RTU, IEC 60870-5-103, IEC 61850 GOOSE, RS485 |
| Event Recording | Up to 30 recent events with timestamp and RMS current values |
| Disturbance Recording | Up to 7 analog channels and 32 binary signals |
| Real-Time Clock | Internal RTC with supercapacitor backup; timekeeping maintained for >= 2 hours during DC power failure |
| Operating Temp | -20 deg C to +60 deg C |
| Storage Temp | -25 deg C to +70 deg C |
| Relative Humidity | 5% to 95%, non-condensing |
| IP Protection | IP20; front panel/casing protection depends on mounting |
| Dimensions | 483 mm x 265 mm x 180 mm |
| Weight | 10.0 kg |
Protection, Measurement, and Control Functions
The REF542plus combines bay control and protection functions in one feeder terminal. Protection functions include phase overcurrent, directional overcurrent, earth/ground fault, voltage protection, thermal overload, phase imbalance, and short-circuit detection.
Measurement processing covers current, voltage, active and reactive power, energy, frequency, and power factor. The event log stores up to 30 recent events with associated timestamps and RMS current values. The disturbance recorder supports up to 7 analog channels and 32 binary signals.
Communication interfaces include Modbus RTU, IEC 60870-5-103, IEC 61850 GOOSE messaging, and RS485 for integration with substation automation and supervisory systems.
Industrial Control and Firmware Compatibility
As an ABB digital bay control and protection unit, the REF542plus combines measurement, monitoring, control, protection, communication, and self-diagnostic functions within a single hardware platform. Its integrated communication functions allow connection to ABB or third-party substation automation systems.
The supplied documentation identifies the REF542plus as a not-active product since 2020. Firmware compatibility, configuration software requirements, and replacement engineering should therefore be verified against the installed terminal revision before commissioning or retrofit work.
Frequently Asked Questions (FAQ)
Q: How long does the internal RTC retain time during a DC power failure?
A: The internal RTC uses a supercapacitor backup and maintains timekeeping for >= 2 hours during DC power failure.
Q: What disturbance recording capacity is specified for the REF542plus?
A: The disturbance recorder supports up to 7 analog channels and 32 binary signals.
Q: Which communication protocols are specified for the terminal?
A: The supplied data specifies Modbus RTU, IEC 60870-5-103, IEC 61850 GOOSE messaging, and RS485.
Field Installation Guidelines
- Verify the REF542plus part number, hardware revision, terminal configuration, and protection settings against the approved switchgear documentation before installation.
- Confirm the rated system voltage and current range of the installed application before connecting measurement circuits.
- Route current and voltage measurement wiring separately from high-current power conductors where practical to reduce electromagnetic interference.
- Use shielded communication cabling where required by the site communication design, and terminate shields according to the plant grounding specification.
- Verify RS485 polarity, termination, cable routing, and grounding before energizing the communication interface.
- Confirm CT and VT circuit wiring and polarity before enabling protection functions.
- Check the enclosure and mounting arrangement against the specified IP20 protection condition and the actual switchgear installation.
- Allow the terminal to reach the specified operating temperature range before commissioning.
- Because the REF542plus is identified as inactive since 2020, verify available engineering tools, firmware compatibility, configuration files, and system interfaces before replacing or reconfiguring an installed unit.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like
Blog Posts
Industrial automation news, technical guides, and product updates.