Configured for infrared flame signal detection in industrial combustion systems, the ABB UR600 IR (UR600 Flame Detector) provides a raw signal to the Uvisor MFD control unit representing infrared radiation amplitude and flicker frequency from the primary combustion zone. It uses a PbS sensor with sensitivity from 0.6 to 3 um and is specified for atomized oil and pulverized coal flames.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | UR600 IR |
| Brand | ABB |
| Product Type | Flame Detector |
| Sensor | PbS (Lead Sulphide) |
| Spectrum Sensitivity | 0.6 to 3 um |
| Detection Signal | Infrared radiation amplitude and flicker frequency |
| Compatible Control Unit | Uvisor MFD / Uvisor series amplifier |
| Power Consumption | 300 mW DC |
| Power Source | Uvisor series control units |
| Enclosure Protection | IP66 / NEMA 4X |
| Operating Temp | -10 to 80 deg C |
| Storage Temp | -40 to 100 deg C |
| Hazardous Area Classification | EEx-d IIC T6; ATEX category G-D |
| ATEX Certificate | CESI 03 ATEX 151 |
| Dimensions | 94 x 94 x 172 mm |
| Weight | 1 kg |
| Mounting Connection | 1 in NPT male thread |
| Cable Entry | 1/2 in NPT female thread |
| Electrical Connection | 4 x 0.55 sq.mm (20 AWG) shielded cable |
| Recommended Maximum Cable Length | 300 m |
| Lens Cleaning Air | Clean ambient air |
| Direct View Cleaning Air Flow | 115 l/min (4 SCFM) |
| Extended Probe Cleaning Air Flow | 400 l/min (14 SCFM) |
| Direct View Minimum Cleaning Air Pressure | 20 mm H2O (1 in W.C.) above maximum wind box pressure |
| Extended Probe Minimum Cleaning Air Pressure | 300 mm H2O (12 in W.C.) above maximum wind box pressure |
Infrared Flame Signal Detection
The UR600 IR uses a PbS infrared sensor to detect radiation in the 0.6 to 3 um range. Its output is a raw flame signal containing amplitude and flicker-frequency information. The Uvisor MFD control unit processes this signal for flame discrimination against background radiation and adjacent burner flames.
The detector is specified for individual burner flame monitoring with atomized oil and pulverized coal combustion. The optical sensing path is supported by lens-cleaning airflow to limit contamination of the viewing surface.
Lens Cleaning and Pneumatic Interface
Clean ambient air is used for lens cleaning. Direct-view installation requires an airflow of 115 l/min, while an extended-probe arrangement requires 400 l/min.
The specified minimum cleaning-air pressure is referenced to the maximum wind box pressure. For direct view, the pressure must be 20 mm H2O above the maximum wind box pressure. For an extended probe, the required differential is 300 mm H2O.
Frequently Asked Questions (FAQ)
Q: What signal does the UR600 IR provide to the Uvisor MFD?
A: It provides a raw infrared flame signal representing detected radiation amplitude and flicker frequency.
Q: What electrical cable is specified for the detector?
A: The specified connection is 4 x 0.55 sq.mm (20 AWG) shielded cable, with a recommended maximum cable length of 300 m.
Q: What is the detector operating temperature range?
A: The specified operating range is -10 to 80 deg C. The storage range is -40 to 100 deg C.
Field Installation Guidelines
- Mount the detector using its 1 in NPT male mounting connection and maintain a clear optical path toward the monitored primary combustion zone.
- Provide the specified clean-air supply for lens cleaning. Select the direct-view or extended-probe airflow according to the installed optical configuration.
- Verify that cleaning-air pressure exceeds the maximum wind box pressure by the specified differential before commissioning.
- Use the specified 4 x 0.55 sq.mm (20 AWG) shielded cable and keep the cable route separated from high-energy power conductors where practical.
- Terminate and ground the cable shield according to the Uvisor control system and site electrical installation requirements.
- Use the 1/2 in NPT female cable entry with a compatible cable gland or conduit arrangement suitable for the enclosure and hazardous-area classification.
- Confirm the installation maintains the required EEx-d IIC T6 and ATEX equipment conditions where the detector is installed in a hazardous area.
- Verify the detector supply is provided by the compatible Uvisor series control unit before applying power.
- Check the optical lens and cleaning-air path during commissioning to ensure that contamination or inadequate airflow does not obstruct infrared detection.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.