Description
The Rack Interface Module (RIM) serves as the primary interface to the 3500 rack, supporting a proprietary protocol for configuration and machinery information retrieval. Positioned in slot 1 of the rack, adjacent to the power supplies, the RIM facilitates seamless communication within the system. Compatible with Bently Nevada external communications processors like TDXnet, TDIX, and DDIX, the RIM enhances the versatility of the monitoring setup. While offering certain functionalities common to the entire rack, the RIM does not form a part of the critical monitoring path and does not impact the proper operation of the overall monitoring system. Each rack requires one RIM. For Triple Modular Redundant (TMR) applications, a TMR version of the RIM is necessary. In addition to standard functions, the TMR RIM performs "monitor channel comparison," comparing outputs from three redundant monitors. If deviations are detected beyond configured thresholds, the TMR RIM flags the monitor as in error and logs an event in the System Event List.Specifications
- Power Consumption: 4.75 watts (typical)
-
Data Inputs:
- Front Panel: Standard RS232 serial communications, Data Rate 38.4 k baud
- I/O Modules:
- RS232/RS422 serial communications
- Internal modem communications
- Data Rate: 38.4 k baud maximum for serial communications, 14.4 k baud for internal modem communications
-
Outputs:
- Front Panel LEDs: OK, TX/RX, TM, CONFIG OK
- I/O Module OK Relay: Rated to 5A @ 24 Vdc/120 Vac
-
Controls:
- Front Panel: Rack reset button, Address switch, Configuration Keylock
-
Communications:
- Front Panel Communications: RS232 serial communications only, Bently Nevada proprietary protocol, Data rate 38.4 k baud maximum, Cable length 30 meters (100 feet) maximum
- RS232/RS422 I/O Module Communications: RS232, RS422, or external modem, Bently Nevada proprietary protocol, Baud rate 38.4 k baud maximum, Cable length varies (RS232: 30 meters maximum, RS422: 1200 meters maximum)
- Modem I/O Module Communications: Hayes AT-compatible, Bently Nevada proprietary protocol, Baud rate 14.4 k baud maximum, Cable length 2.1 meters (7 feet) maximum
- Rack Connector Communications: RS422 only, Bently Nevada proprietary protocol, Baud rate 38.4 k baud maximum, Cable length 1200 meters (4000 feet) maximum
- Data Manager I/O Module Communications: Bently Nevada proprietary, Baud rate 9600 baud fixed, Cable length 3 meters (10 feet) maximum
-
Environmental Limits:
- Operating Temperature: -30°C to +65°C (-22°F to +150°F)
- Storage Temperature: -40°C to +85°C (-40°F to +185°F)
- Humidity: 95%, non-condensing
-
Physical:
- RIM Dimensions: 241.3 mm x 24.4 mm x 241.8 mm (9.5 in. x 0.96 in. x 9.52 in.), Weight: 0.91 kg (2.0 lb.)
- I/O Module Dimensions: 241.3 mm x 24.4 mm x 99.1 mm (9.50 in. x 0.96 in. x 3.90 in.), Weight: 0.45 kg (1.0 lb.)
-
Rack Space Requirements:
- RIM Main Board: 1 full-height front slot
- RIM I/O Modules: 1 full-height rear slot
- Data Manager I/O Modules: 1 full-height rear slot
Ordering Information:
| Part Number | Description |
|---|---|
| 125744-02 | Standard Rack Interface Module |
| 125744-01 | TMR Rack Interface Module |
| 135031-01 | RIM I/O Module with Modem Interface |
| 125768-01 | RIM I/O Module with RS232/RS422 Interface |
| 125760-01 | Data Manager I/O Module |
| 04425545 | Grounding Wrist Strap (single use) |
| 00801286 | Real-Time Clock IC |
| 128755-01 | Firmware IC (for PWA 125744-01 Rev P or later, or for PWA 125744-02 Rev N or later) |
| 00580441 | Connector Header, Internal Termination, 3-position, Green |
| 00580436 | Connector Header, Internal Termination, 6-position, Green |
| 129768 | RIM Operation and Maintenance Manual |
| 02290860 | RS232 Modem cable from: 3500 Rack External Modem Host Computer to External Modem |
| 130119-01 | Host Computer to RS232/RS422 Converter Cable RS232 |
| 129386-01 | TDIX - Static Data Cable |
| 129387-01 | DDIX - Static Data Cable |
| 02290160 | DDIX/TDIX - Dynamic Data Cable |
| 02230411 | RS232 to RS422 Converter 110 Vac |
| 02230412 | RS232 to RS422 Converter 220 Vac |
- E-mail: sales6@5gplc.com
- Business Hours: 24h/7d
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like
Blog Posts
Industrial automation news, technical guides, and product updates.