Your Trusted PLC & DCS Supplier!
100% Original, Ready to Ship!

General Electric/

GE L90-W00-HQH-F8L-H6A-L6C-NXX-SXX-UXX-W7D Line Differential Relay

Manufacturer:GE General Electric

Part Number:L90-W00-HQH-F8L-H6A-L6C-NXX-SXX-UXX-W7D

Product Type:Line Differential Relay

Stock:IN STOCK

Repair:3-7 Day

Warranty:1 Year

Dimensions:28.6 cm × 19.5 cm × 17.1 cm

Weight:32.0 lbs

  • Product Details

Overview

The GE Multilin L90-W00-HQH-F8L-H6A-L6C-NXX-SXX-UXX-W7D is a high-performance line differential relay. It protects transmission lines with secure, fast fault detection. The relay supports dual-breaker and complex power system applications. It provides advanced distance protection and phase-segregated differential protection. Users benefit from integrated PMU, flexible communications, and real-time bay visualization. The L90 series ensures reliability under harsh industrial conditions.

Technical Specifications

Core Features

  • Phase-segregated differential protection for single-pole tripping.
  • High-speed phase and ground distance protection with five zones.
  • Dynamic charging current compensation and channel asymmetry adjustment.
  • Phasor Measurement Unit support per IEEE C37.118 and IEC 61850-90-5.
  • CyberSentry™ cybersecurity for secure relay operation.
  • IEC 61850 Ed.1 and Ed.2 certified with process bus support.
  • Routable GOOSE (R-GOOSE) for wide-area protection.
  • Integrated full-color display for real-time monitoring and control.

Electrical & Communication

  • Input Voltage: 24V DC.
  • Communication Protocol: Modbus TCP/IP.
  • Three independent Ethernet ports, fiber or copper.
  • Time synchronization supported via IEEE 1588.
  • AC voltage withstand: continuous 260 V to neutral, 1 min/hr at 420 V.
  • DCMA input impedance: 379 Ω ±10%.
  • IRIG-B input amplitude modulation: 1–10 V pk-pk.
  • LED test duration approximately three minutes.

Environmental & Physical

  • Operating Temperature: –40°C to +70°C.
  • Rugged design suitable for harsh industrial environments.
  • Supports 1 to 16 data logging channels.

Prev:

Next:

Leave a message