The Honeywell 10101/2/1, also cataloged as the 10101/2/1 FSC Fail-safe Digital Input Module, provides sixteen 24 VDC digital input channels with fail-to-safe input-stage behavior. It monitors logic 0, logic 1, and input-to-input crosstalk within the configured process safety time.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 10101/2/1 |
| General Type Number | 10101/2/1 11000 |
| Brand | Honeywell |
| Product Type | FSC fail-safe digital input module |
| System | Honeywell FSC |
| Input Channels | 16 digital inputs |
| Nominal Input Voltage | 24 VDC |
| Maximum Input Voltage | 36 VDC |
| Input Current | 7 mA at 24 VDC |
| Input HIGH | > 15 VDC |
| Input LOW | < 9 VDC, I < 2 mA |
| Typical Input Delay | 10 ms |
| 5 VDC Power Requirement | 8 mA |
| 24 VDC Internal Power | 110 mA |
| 24 VDC External Power | 110 mA, input currents |
| 5 VDC Ripple Content | < 0.5 Vp-p, 0-360 Hz |
| Space Requirement | 4 TE, 3 HE = 4 HP, 3U |
| Software Version | >= 3.00 |
| Approvals | CE, TUV, UL |
| Module Connector Coding | Holes A5, C5 |
| Rack Connector Coding | Large pins A5, C5 |
| Weight | 0.22 lb |
| Dimensions | 2.5 cm x 12.7 cm x 20.3 cm |
Fail-safe Digital Input Monitoring
The input stage operates in a fail-to-safe configuration. A component failure is designed to result in a de-energized input signal at the processor, corresponding to the specified safe condition for a typically energized system.
The system self-test functions cover the remaining module logic circuitry. Within the configured process safety time, diagnostic testing includes:
- Reception of logic level 0 signals
- Reception of logic level 1 signals
- Detection of crosstalk between input channels
The 16 input channels accept 24 VDC field signals. The specified HIGH threshold is above 15 VDC, while the LOW condition is below 9 VDC with input current below 2 mA.
Frequently Asked Questions (FAQ)
Q: How many digital input channels does the 10101/2/1 provide?
A: It provides 16 digital input channels rated for 24 VDC operation.
Q: What happens to the processor input signal under an input-stage component failure?
A: The fail-to-safe input stage causes the processor-side input signal to become de-energized, which is the defined safe condition for a typically energized system.
Q: What electrical supply does the module require?
A: The specified requirements are 5 VDC at 8 mA, 24 VDC internal supply at 110 mA, and 24 VDC external supply at 110 mA for input currents.
Field Installation Guidelines
- Install the module in the designated FSC rack position according to the applicable rack configuration.
- Verify the module and rack connector coding before insertion. The specified coding is A5 and C5.
- Confirm that field digital signals remain within the stated 36 VDC maximum input voltage.
- Maintain correct polarity and wiring identification for all 16 input channels.
- Separate digital input wiring from high-current and high-noise conductors where practical.
- Use appropriate cable shielding and grounding practices according to the FSC installation documentation and site grounding design.
- Verify the 5 VDC and 24 VDC supply wiring before energizing the rack.
- Check the specified input HIGH and LOW thresholds during commissioning where signal verification is required.
- Confirm that the installed software version meets the stated requirement of >= 3.00.
- Do not substitute connector or rack coding arrangements without confirming system compatibility.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like
Blog Posts
Industrial automation news, technical guides, and product updates.