Notified by email when this product becomes available
- Description
- Reviews
- Shipping & Payment
The Honeywell FC-TSGAS-1624 is a Field Termination Assembly (FTA) designed to interface gas and flame detector signals with the SAI-1620m analog input module in Honeywell Safety Manager systems. It provides 16 analog input channels, linear signal conversion from field current to a 0-4 VDC module input level, and fused 24 VDC field power distribution. The assembly uses screw terminals and supports DIN rail mounting.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | FC-TSGAS-1624 |
| Brand | Honeywell |
| Product Type | Safe Analog Input Field Termination Assembly |
| Input Channels | 16 |
| Input Signal | 0(4)-20 mA DC |
| Stated Input Current Range | 0-25 mA |
| Input Resistance | 500 ohm, +/-5% |
| Output Signal to SAI-1620m | 0-4 VDC |
| Stated Conversion Accuracy | 0.1% |
| External Power Supply | 24 VDC |
| Quiescent Current | 3 mA, without field loads |
| Channel Fuse Rating | 500 mA per channel |
| Fuse Type | 5 x 20 mm cartridge fuse |
| Fuse Manufacturer / Part Number | Schurter 0001.2501 |
| Fuse Voltage Rating | 250 VAC / 300 VDC |
| Fuse Derating | 0.5 A at 25 deg C; 0.35 A at 70 deg C |
| Signal Termination | Screw terminals |
| Maximum Signal Wire Size | 2.5 mm2 (AWG 14) |
| Maximum Power Wire Size | 16 mm2 (AWG 8) |
| Wire Strip Length | 7 mm |
| Signal Terminal Torque | 0.5 Nm |
| Power Terminal Torque | 1.2 Nm |
| DIN Rail Compatibility | TS32 / TS35 x 7.5 |
| Required Rail Length | 226 mm |
| Dimensions (L x W x H) | 225 x 70 x 60 mm |
| Weight | 0.63 kg |
Signal Conversion and Field Interface
The FC-TSGAS-1624 accepts current signals from field transmitters and converts them into voltage signals for the SAI-1620m analog input module. The stated 0-4 VDC output range is the interface signal level presented to the receiving module; it should not be confused with the external 24 VDC supply used for field power distribution.
The 16 channels share a common 0 V reference. When planning detector connections, confirm that the field device output type, signal range, and grounding arrangement match the system wiring design.
Field Power Distribution and Protection
The assembly distributes externally supplied 24 VDC power to field transmitters, with a stated 500 mA fuse rating for each channel. The specified Schurter 5 x 20 mm cartridge fuse provides individual branch overcurrent protection. Fuse selection and replacement should follow the applicable assembly documentation, including the stated current derating at elevated temperatures.
The listed quiescent current of 3 mA applies without field loads. It does not represent the total supply current when transmitters are connected; the external supply must also accommodate the connected field devices and their operating current.
Installation and Wiring
The FC-TSGAS-1624 is designed for TS32 or TS35 x 7.5 DIN rail mounting, with a stated rail length requirement of 226 mm. Signal wiring and power wiring have different terminal capacities and tightening torques, so the applicable values should be followed separately during installation.
- Signal terminals: maximum 2.5 mm2 (AWG 14), 7 mm strip length, 0.5 Nm torque.
- Power terminals A and B: maximum 16 mm2 (AWG 8), 7 mm strip length, 1.2 Nm torque.
System Integration
The supplied technical information identifies the SAI-1620m analog input module and SICC-0001/Lx system cables as associated components. Verify the required cable variant, module configuration, and system wiring before ordering or replacing an existing assembly.
The source material also mentions redundant module configurations, but does not specify the redundancy architecture or configuration restrictions for this exact assembly. These details should be confirmed against the applicable Safety Manager system documentation.
Frequently Asked Questions
Q: How many field detector signals can the FC-TSGAS-1624 terminate?
A: It provides 16 analog input channels for field current signals. The number of detectors that can be connected depends on the channel allocation and the approved system configuration.
Q: What is the difference between the field input and the module output signal?
A: The assembly accepts 0(4)-20 mA DC field signals and provides a stated 0-4 VDC signal to the SAI-1620m. The two ranges describe different sides of the signal interface.
Q: What should be checked when replacing an existing FC-TSGAS-1624?
A: Confirm the complete model number, field wiring, fuse specifications, SAI-1620m interface, and required SICC-0001/Lx cable configuration. Also verify the terminal assignments and system configuration against the applicable documentation before energizing the replacement.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like
Blog Posts
Industrial automation news, technical guides, and product updates.