The Honeywell FS-TPSU-2430 is a DC/DC power converter designed for the Honeywell Safety Manager system. It converts a nominal 24 VDC input into an isolated 30 VDC output rated at 1 A. The converter supplies external power to Field Termination Assemblies (FTAs), including analog input assemblies, and provides local voltage indication and relay-based output status monitoring.
Power Conversion and Output Monitoring
The FS-TPSU-2430 provides regulated 30 VDC power from a 24 VDC supply. Its galvanically isolated output separates the incoming supply from the field-side power circuit, supporting the external power requirements of compatible FTA configurations.
The module includes output voltage monitoring, a local LED indicator, and a readback relay contact. When the DC/DC output voltage is within the acceptable range, the LED illuminates and the readback relay contact closes. This allows the system to monitor the availability of the field-side power supply.
FTA Power Distribution
The converter provides six pairs of output terminals for distributing 30 VDC and 0 VDC to external circuits. It is intended for use with Safety Manager FTAs, including the TSAI-1620m and TSHART-1620m analog input assemblies.
The six output connections provide multiple field power termination points. The total output current remains limited to 1 A; the rating is not 1 A per terminal pair.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | FS-TPSU-2430 |
| Brand | Honeywell |
| Product Type | DC/DC Converter |
| System | Safety Manager |
| Nominal Input Voltage | 24 VDC |
| Input Voltage Range | 18-36 VDC |
| Inrush Current | 75% |
| Switching Frequency | > 25 kHz |
| Galvanic Isolation | Input to output |
| Isolation Voltage | 2000 VAC (1 min) |
| Readback Relay Contact Rating | 36 VDC / 40 mA; 30 VAC / 40 mA |
| Approvals | CE, TUV, UL, CSA, FM |
| Safety Class | Up to and including SIL 3 |
| MTBF | Approximately 400,000 hours |
| Mounting | DIN EN rail TS32 / TS35 x 7.5 |
| Dimensions | 150 x 70 x 62.3 mm (L x W x H) |
| Used Rail Length | 151 mm |
| Fuse Rating | 3.15 A |
| Fuse Dimensions | 5 x 20 mm |
| Maximum Wire Size | 2.5 mm2 (AWG 14) |
| Wire Strip Length | 7 mm |
| Terminal Tightening Torque | 0.5 Nm |
| Operating Temperature | -5 to +70 deg C |
| Storage Temperature | -40 to +85 deg C |
| Cooling | Natural convection |
| Weight | 1.18 lbs |
Electrical Connections
The FS-TPSU-2430 uses screw terminals for incoming power, output distribution, and voltage-status feedback.
- Input terminals 3 and 4: 24 VDC IN+ and 24 VDC IN-.
- Readback terminals 1 and 2: Relay status contact.
- Output terminals 1A-6A: 30 VDC OUT.
- Output terminals 1B-6B: 0 VDC OUT, with terminal 6B also designated for the grounding arrangement.
The output-side grounding arrangement must follow the Safety Manager installation requirements. For predictable system behavior under a field-side short-to-earth condition, the 0 VDC output must be connected to ground or a dedicated Earth Leakage Detector (ELD) must be provided for the converter.
Frequently Asked Questions
Q: What is the output voltage and current capacity of the FS-TPSU-2430?
A: It provides a regulated 30 VDC output with a rated current of 1 A. The total current capacity is shared across its six output terminal pairs.
Q: Which Honeywell modules can receive power from the FS-TPSU-2430?
A: The converter is designed to supply other Safety Manager FTAs, including the TSAI-1620m and TSHART-1620m analog input assemblies. The actual power configuration must account for the connected field-device load.
Q: How can the output power status be monitored?
A: The module provides a local LED and a readback relay contact. The LED illuminates and the relay contact closes when the output voltage is OK. The relay contact can be used for external power-status monitoring.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like
Blog Posts
Industrial automation news, technical guides, and product updates.