Notified by email when this product becomes available
- Description
- Reviews
- Shipping & Payment
The Schneider BMXCPS4002H is a ruggedized power supply module in the Modicon X80 range, designed for redundant power architectures in industrial control systems. It accepts a 100-240 V AC primary supply and provides separate 3.3 V DC and 24 V DC outputs for I/O module logic and module or processor power. Its extended operating temperature range of -25 to 70 deg C supports installations exposed to demanding environmental conditions.
Power Supply Architecture and Output Capacity
The BMXCPS4002H provides two secondary power outputs for the Modicon X80 backplane:
- 3.3 V DC: 5.5 A, with an output power of 18 W for I/O module logic.
- 24 V DC: 1.67 A, with an output power of 40 W for I/O module power and processor supply, with the 3.3 V output unloaded.
These outputs serve different power requirements within the control rack. The available output capacity must be considered when calculating the total power demand of installed modules, particularly when the 24 V DC output and processor supply are used together.
The module supports redundant power architectures and includes redundancy monitoring. Its diagnostic functions include remaining operating life information, temperature monitoring, redundancy testing and operating-time information, with extended diagnostics available over the network.
Input Protection and Electrical Characteristics
The primary input accepts a nominal voltage range of 100-240 V AC, with an allowable input range of 85-264 V AC. It operates at 50/60 Hz, with an acceptable frequency range of 47-63 Hz.
The secondary circuits include overload, overvoltage and short-circuit protection. The primary circuit also has internal protection that is not accessible to the user. These protection functions address different fault conditions on the input and output sides of the power supply.
The module has a maximum power dissipation of 8.5 W. Its inrush current reaches 30 A at 120 V and 60 A at 240 V, which should be considered when evaluating upstream circuit protection and power distribution.
Connections, Indicators and Reset
The BMXCPS4002H uses separate removable terminal blocks for power input and alarm relay connections:
- One 5-pin connector for AC power supply and protective earth.
- One 2-pin connector for the alarm relay.
- Two removable cage-type terminal blocks, with 5-way and 2-way configurations, included with the module.
Three green LEDs indicate voltage availability, redundancy status and power supply status. A RESET button provides a cold-start function.
The primary-to-ground and primary-to-secondary insulation resistance is at least 100 MOhm. The specified interruption immunity is 1 ms, and the insulation withstand voltage varies according to the relevant circuit pair.
Installation and Environmental Conditions
The power supply is designed for installation in a Modicon X80 module rack and is secured with two screws. Its IP20 protection rating applies to the specified enclosure protection level and does not indicate suitability for direct exposure to water or dust.
The ruggedized construction includes a protective coating and environmental resistance characteristics:
- Operating temperature: -25 to 70 deg C.
- Storage temperature: -40 to 85 deg C.
- Relative humidity: 5-95% at 55 deg C, without condensation.
- Operating altitude: 0-2,000 m; derating applies from 2,000 to 5,000 m.
- Vibration resistance: 3 Gn.
- Shock resistance: 30 Gn.
- Gas resistance: Class Gx according to ISA S71.04 and Class 3C4 according to IEC 60721-3-3.
- Dust and sand resistance: Class 3S4 according to IEC 60721-3-3.
The specified environmental characteristics make this version suitable for installations requiring a wider operating temperature range and additional environmental resistance compared with standard indoor power supply configurations.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXCPS4002H |
| Brand | Schneider Electric |
| Product Type | Modicon X80 Power Supply Module |
| Product Range | Modicon X80 |
| Application | Ruggedized power supply for redundant architectures |
| Backplane Compatibility | All module racks |
| Primary Supply Voltage | 100-240 V AC |
| Allowable Input Voltage | 85-264 V AC |
| Supply Frequency | 50/60 Hz |
| Frequency Limits | 47-63 Hz |
| Apparent Power | 0.13 kVA |
| Input Current | 0.55 A at 240 V; 1.01 A at 115 V |
| Inrush Current | 30 A at 120 V; 60 A at 240 V |
| 3.3 V DC Output | 5.5 A, 18 W |
| 24 V DC Output | 1.67 A, 40 W |
| Maximum Power Dissipation | 8.5 W |
| Protection | Secondary overload, overvoltage and short-circuit protection |
| Redundancy | Redundant power architecture support |
| Diagnostics | Network diagnostics, temperature monitoring and redundancy testing |
| Status Indicators | 3 green LEDs |
| Reset | Cold-start RESET button |
| Electrical Connections | 1 x 5-pin power connector; 1 x 2-pin alarm relay connector |
| Insulation Resistance | At least 100 MOhm |
| Dielectric Strength | 1,500 V primary/secondary; 1,500 V primary/earth; 2,300 V sensor supply circuit |
| MTBF | 792,000 h |
| Interruption Immunity | 1 ms |
| Mounting | Modicon X80 module rack, secured with 2 screws |
| Protection Rating | IP20 |
| Operating Temperature | -25 to 70 deg C |
| Storage Temperature | -40 to 85 deg C |
| Relative Humidity | 5-95% at 55 deg C, non-condensing |
| Vibration Resistance | 3 Gn |
| Shock Resistance | 30 Gn |
| Protective Coating | Conformal protective coating |
| Operating Altitude | 0-2,000 m; derating from 2,000 to 5,000 m |
| Hazardous Area Classification | Class I, Division 2 |
| Product Certifications Listed | CE, UL, CSA, RCM, EAC, Merchant Navy |
| Standards | IEC 61131-2, IEC 61010-2-201, UL 61010-2-201, CSA C22.2 No. 61010-2-201, IACS E10, EN/IEC 61000-6-5, EN/IEC 61850-3 |
| Weight | 0.51 kg |
| EAN | 3606480927577 |
| Environmental Carbon Footprint | 495 kg CO2 eq. |
Frequently Asked Questions
Q: What is the difference between BMXCPS4002H and a standard Modicon X80 power supply?
A: The BMXCPS4002H is the ruggedized version intended for demanding environmental conditions and redundant power architectures. Its specified operating temperature range is -25 to 70 deg C, and it includes environmental resistance characteristics for industrial installations.
Q: Can the BMXCPS4002H supply both the I/O logic and processor power?
A: Yes. It provides separate 3.3 V DC and 24 V DC outputs. The 3.3 V output supplies I/O module logic, while the 24 V output supplies I/O modules and the processor. The specified 40 W capacity at 24 V DC assumes the 3.3 V output is unloaded.
Q: What connections are provided for the power supply and alarm relay?
A: The module has a 5-pin connector for the AC supply and protective earth, together with a 2-pin connector for the alarm relay. Both removable cage-type terminal blocks are included with the power supply.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.