Notified by email when this product becomes available
- Description
- Reviews
- Shipping & Payment
The Schneider Electric BMXCPS4022 is a Modicon X80 power supply module designed for 24-48 VDC input and redundant power supply architectures. It provides separate 3.3 VDC and 24 VDC secondary outputs for I/O module logic and rack power requirements. The module includes secondary-circuit overload, overvoltage and short-circuit protection, network-accessible diagnostic functions, and dedicated redundancy status monitoring.
Power Supply Function and Redundancy
The BMXCPS4022 converts the DC primary supply into the secondary voltages required by the Modicon X80 rack. Its output configuration supports both I/O module logic and the 24 VDC supply requirements of the I/O modules and processor.
The module supports redundant power supply architectures. Its diagnostic functions include redundancy testing, temperature monitoring, operating time and remaining operating time. These functions provide maintenance personnel with information about the power supply condition and redundancy status.
Secondary Output Configuration
The power supply provides two secondary output circuits:
- 3.3 VDC output: 5.5 A, with an 18 W secondary power rating for I/O module logic at 0 to 60 deg C.
- 24 VDC output: 1.67 A, with a 40 W secondary power rating for I/O module power supply and processor operation at 3.3 V without load, at 0 to 60 deg C.
The secondary circuits incorporate overload, overvoltage and short-circuit protection. Maximum power dissipation is 8.5 W. These output ratings should be considered when checking the total rack power requirements and the connected module configuration.
Electrical Characteristics and Protection
The specified primary input range is 24-48 VDC, with an allowable primary voltage range of 18-62.4 VDC. Input current is 1.9 A at 24 V and 1 A at 48 V. The specified inrush current is 60 A at both input voltages, with corresponding I2t values of 0.4 A2.s at 24 V and 1.9 A2.s at 48 V.
Primary-circuit protection is internal and not accessible. The module also provides primary-to-ground and primary-to-secondary insulation resistance of at least 100 Mohm, with a dielectric strength of 1500 V for both insulation paths.
Indicators and Electrical Connections
Three green LED indicators provide operating information:
- Voltage presence (OK).
- Redundancy OK.
- Power supply status.
A RESET push button provides a cold-start reset function. Electrical connections consist of one 5-pin connector for the power supply and protective earth, and one 2-pin connector for the alarm relay. Two removable terminal blocks, with 5-way and 2-way connections, are included.
Installation and Environmental Conditions
The BMXCPS4022 is designed for installation in a Modicon X80 module rack and is secured with two screws. It has an IP20 protection rating and an operating temperature range of 0 to 60 deg C. The specified storage temperature range is -40 to 85 deg C.
The module supports relative humidity of 10-95%, without condensation. Its environmental specifications include 3C3 and 3C4 classifications according to IEC 60721-3-3. The specified immunity to interruptions is 1 ms.
Parameter | Specification
| Parameter | Specification |
|---|---|
| Model | BMXCPS4022 |
| Brand | Schneider Electric |
| Product Type | Redundant DC Power Supply Module |
| Product Range | Modicon X80 |
| Primary Input Voltage | 24-48 VDC |
| Primary Voltage Range | 18-62.4 VDC |
| Input Current | 1.9 A at 24 V; 1 A at 48 V |
| Inrush Current | 60 A at 24 V and 48 V |
| I2t at Switch-On | 0.4 A2.s at 24 V; 1.9 A2.s at 48 V |
| Secondary Output 1 | 3.3 VDC, 5.5 A, 18 W |
| Secondary Output 2 | 24 VDC, 1.67 A, 40 W |
| Operating Temperature for Rated Output | 0 to 60 deg C |
| Maximum Power Dissipation | 8.5 W |
| Redundancy | Supported |
| Diagnostic Functions | Redundancy test, temperature sensor, operating time and remaining operating time |
| Protection | Secondary overload, overvoltage and short-circuit protection |
| Status Indicators | 3 green LEDs |
| Reset Function | Cold-start RESET button |
| Alarm Connection | 1 x 2-pin connector |
| Power Connection | 1 x 5-pin connector, including protective earth |
| Insulation Resistance | >= 100 Mohm, primary/ground and primary/secondary |
| Dielectric Strength | 1500 V, primary/ground and primary/secondary |
| Interruption Immunity | 1 ms |
| Maximum Cable Distance Between Devices | 10 m / 15 m (connection-dependent values) |
| MTBF | 752,000 h |
| Mounting | Modicon X80 module rack, secured with 2 screws |
| Rack Compatibility | All module racks |
| Protection Rating | IP20 |
| Environmental Classification | 3C3 and 3C4 according to IEC 60721-3-3 |
| Storage Temperature | -40 to 85 deg C |
| Relative Humidity | 10-95%, non-condensing |
| Standards | EN 61131-2, EN 61000-6-4, EN 61000-6-2, EN 61010-2-201 |
| Product Directives | 2014/35/EU, 2014/30/EU |
| Product Weight | 0.81 kg |
| EAN | 3606481179074 |
| Lifecycle Carbon Footprint | 496 kg CO2 eq. |
Frequently Asked Questions
Q: Can the BMXCPS4022 be used in a redundant power supply architecture?
A: Yes. The BMXCPS4022 is designed for redundant power supply architectures. It includes redundancy monitoring and a dedicated green redundancy status LED. The actual redundant arrangement must follow the applicable Modicon X80 system configuration requirements.
Q: What is the difference between the 3.3 VDC and 24 VDC outputs?
A: The 3.3 VDC output supplies I/O module logic, while the 24 VDC output supplies the I/O module power circuit and supports processor operation under the specified no-load condition. Both outputs have separate current and power ratings that must be considered when checking rack power consumption.
Q: What should be checked when replacing an existing BMXCPS4022?
A: Verify the complete model number, 24-48 VDC input supply, secondary output requirements, rack configuration and redundant power arrangement. Also check the connector configuration and the power demand of the installed modules before replacement.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like