Schneider Electric 170ADM35011 Discrete Solid State I/O Base
The Schneider Electric 170ADM35011, also cataloged as the 170ADM35011 discrete solid state I/O base, operates as a dedicated hardware component for 24 VDC discrete signal acquisition and transistor output switching within Modicon Momentum automation platform networks.
Suffix Breakdown & Model Matrix
The supplied documentation identifies 170ADM35011 as a fixed single catalog model within the Modicon Momentum distributed I/O platform. No official suffix segmentation or configurable ordering matrix is specified in the provided technical material.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 170ADM35011 |
| Brand | Schneider Electric |
| Product Series | Modicon Momentum |
| Product Type | Discrete solid state I/O base DC |
| Origin | Indonesia |
| Discrete Inputs | 16 |
| Discrete Outputs | 16 |
| Input Channel Grouping | 1 group of 16 inputs |
| Output Channel Grouping | 2 groups of 8 outputs |
| Input Logic | Positive |
| Output Logic | Positive |
| Rated Input Voltage | 24 VDC |
| Input Resistance | 4 kOhm |
| Peak Output Current | 5 A |
| Fault Detection | Output overload detection |
| Isolation Between Channels and Bus | 500 V AC |
| Communication Interface | Internal communications connector |
| Mounting Method | Panel mount or DIN-rail mount |
| Terminal Style | Plug-in terminal strips |
| Certifications | CSA, UL, CE |
| Protective Treatment | TC |
| Dimensions | 141.5 x 125 x 47.5 mm |
| Weight | 0.2 kg |
I/O Density Scaling and Backplane Integration
The module integrates 16 DC inputs and 16 transistor outputs within a single Momentum base assembly to increase I/O density without additional expansion wiring. Internal communication coupling is executed through the Momentum backplane interface using the integrated communication connector mounted between the processor or communication adapter and the I/O base.
Output sections are arranged in two isolated 8-channel groups to simplify segmented field power distribution. Positive logic transistor outputs permit direct switching of compatible DC field devices while overload fault detection monitors output channel stress conditions.
The 500 V AC isolation barrier between field channels and the internal bus structure limits conducted electrical transfer from external wiring disturbances into the control backplane during inductive switching events.
Frequently Asked Questions
Q: Does the 170ADM35011 support hot-swapping during controller operation? A: The supplied documentation does not define energized insertion or removal capability. Standard maintenance practice requires de-energizing field and bus power before module replacement.
Q: Can separate field power supplies be connected to the two output groups? A: Yes. The output architecture is divided into two groups of 8 outputs with separate positive supply terminals, allowing segmented DC distribution according to cabinet design requirements.
Q: What wiring practice is recommended for transistor output circuits? A: Output wiring should be routed separately from analog instrumentation and network communication cables. Inductive loads should use external suppression devices where required by the field device manufacturer.
Field Installation Guidelines
Mount the I/O base on a rigid panel surface or DIN rail with adequate clearance for connector insertion and terminal servicing. Verify mechanical locking engagement before energizing the assembly.
Maintain dedicated DC common return routing for input and output circuits to reduce conducted noise coupling. Shielded cable grounding should terminate at a single protective earth reference point inside the control cabinet.
Do not bundle transistor output wiring in parallel with motor feeder conductors or variable frequency drive output cables over extended cable runs. Confirm field polarity before applying 24 VDC supply power to prevent output stage damage.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like
Blog Posts
Industrial automation news, technical guides, and product updates.