Notified by email when this product becomes available
- Description
- Reviews
- Shipping & Payment
Configured for redundant PAC control in the Modicon M580 platform, the Schneider Electric BMEH586040C (BMEH586040C Redundant Processor Module) provides processor-level hot standby execution with Ethernet communication and rack-based power.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMEH586040C |
| Brand | Schneider Electric |
| Product Range | Modicon M580 |
| Product Type | Redundant Processor Module |
| Weight | 0.849 kg |
| Operating Temp | -25 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Power Consumption | 365 mA at 24 VDC |
| Power Source | Internal rack power |
| Redundancy Level | HSBY Level 6 |
| Remote I/O Stations | Up to 31 |
| Distributed Devices | Up to 64 |
| Discrete I/O Capacity | Up to 31744 channels |
| Analog I/O Capacity | Up to 7936 channels |
| Ethernet Interfaces | 1 Ethernet TCP/IP service port, 2 Ethernet TCP/IP device network ports, 1 Ethernet hot standby port |
| USB Interface | Mini-B USB |
| Ethernet Communication Modules | 6 |
| Interface Modules | 16 |
| RIO Services | RIO scanner, DIO scanner |
| Program and Data RAM | 64 MB |
| System RAM | 10 kB |
| Hot Standby System Data RAM | 4096 kB |
| Data Storage | 4 GB expandable flash |
| Instruction Processing | 40 Kinst/ms at 100% Boolean; 50 Kinst/ms at 65% Boolean and 35% fixed-point arithmetic |
| Application Tasks | 1 fast task; 1 cyclic/periodic main task |
| Protection Rating | IP20 |
| Conformal Coating | Yes |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| Vibration Resistance | 3 gn |
| Shock Resistance | 30 gn |
| Installation Altitude | 0 to 2000 m; derating above 2000 m |
| Certifications | CE, UL, CSA, RCM, EAC, Marine, ATEX Zone 2/22, IECEx Zone 2/22 |
| Standards | IEC 61131-2, IEC 61010-2-201, UL 61010-2-201, CSA C22.2 No 61010-2-201, IACS E10, EN/IEC 61000-6-5, EN/IEC 61850-3, IEC 60079-0 |
Modicon M580 Redundant Processor and Ethernet Architecture
The BMEH586040C implements Level 6 hot standby processing within a Modicon M580 controller architecture. The module provides dedicated Ethernet interfaces for service, device networking, and processor redundancy.
The processor supports RIO and DIO scanner services and can manage up to 31 remote I/O stations. The supplied specifications also define support for application-specific functions including serial communication, precise time stamping, SSI encoders, motion control, HART, and counters.
The processor includes separate status indicators for RUN, ERR, I/O, download, backup, Ethernet network status, remote processor operation, processor identity, primary or standby state, forced I/O, and hot standby diagnostics.
The conformal-coated circuit board supports specified gas, dust, sand, salt, mold, and fungal-spore resistance classifications. Environmental compliance includes ISA S71.04 Gas Resistant Class Gx and IEC 60721-3-3 classifications.
Frequently Asked Questions
Q: Does the BMEH586040C obtain its operating power from an external 24 VDC supply?
A: No. The supplied specifications identify internal rack power as the processor power source, with a consumption of 365 mA at 24 VDC.
Q: Which communication interfaces are provided on the processor?
A: The module provides Ethernet TCP/IP service and device-network interfaces, a dedicated Ethernet hot standby interface, and a Mini-B USB interface.
Q: What environmental operating temperature is specified for this processor?
A: The specified operating range is -25 to 60 deg C, while the storage range is -40 to 85 deg C.
Field Installation Guidelines
Install the processor in the specified Modicon M580 rack position and verify mechanical engagement before energizing the rack.
Use the rack power architecture specified for the M580 system and confirm the available current capacity against the processor load.
Route Ethernet, USB, and other communication cables separately from high-current switching conductors where practical to reduce electromagnetic coupling.
Maintain appropriate cable shielding and bonding practices according to the M580 installation documentation and the applicable EMC requirements.
For redundant processor installations, verify processor identification, Primary/Standby status, and the hot standby link before placing the control system into service.
Check the RUN, ERR, I/O, ETH MS, ETH NS, PRIM, STBY, and Hsby Diag indicators during commissioning to confirm processor and network states.
Do not remove or insert the processor unless the applicable M580 hot-swap and energized-rack procedures explicitly permit the operation.
For installations in classified environments, verify that the complete system configuration satisfies the applicable ATEX or IECEx installation requirements.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like
Blog Posts
Industrial automation news, technical guides, and product updates.