The BMXDAO1605 is a 16-channel AC triac discrete output module in the Schneider Electric Modicon X80 range. It switches AC loads through solid-state outputs, with a rated operating voltage range of 100 to 240 V AC. The module provides individual channel switching, resistive-load response specifications, and external fast-blow fuse protection.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXDAO1605 |
| Brand | Schneider Electric |
| Product Range | Modicon X80 |
| Product Type | Discrete Output Module |
| Number of Outputs | 16 |
| Output Technology | Triac |
| Rated Output Voltage | 100 to 240 V AC |
| Output Voltage Range | 85 to 288 V AC |
| Current per Channel | 0.6 A |
| Output Current Limits | 0.025 to 4.8 A |
| Inrush Current | 20 A |
| Typical Current Consumption | 100 mA at 3.3 V DC |
| Output Response Time | 10 MOhm at 500 V DC |
| Dielectric Strength | 2830 V AC, 50/60 Hz, 1 min |
| Protection | 1 external fast-blow fuse |
| Protection Rating | IP20 |
| Protective Treatment | Standard version |
| MTBF | 1,800,000 h |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| Package Weight | 203 g |
| GTIN | 3595863966954 |
Output Operation and Protection
The BMXDAO1605 uses triac switching devices to control AC loads. Unlike electromechanical relay outputs, triac outputs have no mechanical contacts. Their solid-state switching characteristics make the module suitable for AC discrete control circuits where the load current and voltage remain within the specified operating limits.
The specified output response time of 1.011 ms applies to resistive-load activation and deactivation. Actual switching behavior with inductive or other non-resistive loads may differ and should be checked against the applicable load requirements.
Electrical Protection and Isolation
The module specifies one external fast-blow fuse as its output protection arrangement. Fuse selection and installation must account for the connected load and the applicable channel current limits. The 20 A inrush current specification should also be considered when evaluating loads with high starting currents.
The insulation resistance and dielectric strength ratings describe electrical isolation performance under the stated test conditions. They should not be interpreted as permission to exceed the rated operating voltage.
Modicon X80 Platform
The BMXDAO1605 belongs to the Modicon X80 common module platform, which is used with Modicon M340 and M580 Programmable Automation Controllers. Its platform classification identifies the product family; the actual rack configuration and controller compatibility should be checked against the relevant hardware configuration documentation.
Operating Conditions and Load Distribution
The output current must be assessed at both channel and group level. The module's total permissible load depends on the number of energized channels and ambient temperature; the individual channel rating should not be treated as an allowance to operate all 16 outputs simultaneously at maximum current.
For a 220 V AC resistive-load example, Schneider Electric's X80 module documentation specifies the following load conditions:
- At 0 to 40 deg C, 16 channels at 0.3 A each correspond to a total load of 4.8 A.
- Above 40 deg C, output loading must follow the specified temperature derating curve.
- At 60 deg C, the maximum total current is reduced to approximately 2.9 A, corresponding to 10 channels at 0.3 A or 16 channels at approximately 0.18 A.
These limits are important when distributing loads across the output groups and checking cabinet operating temperature.
Frequently Asked Questions
Q: What type of loads can the BMXDAO1605 switch?
A: It uses triac outputs for AC switching within the specified 100 to 240 V AC operating range. It is not a DC transistor output module.
Q: Does each output support 0.6 A continuously?
A: The 0.6 A figure is listed in Schneider Electric's product information, but it should not be interpreted as 0.6 A simultaneously on all 16 channels. Total current and channel loading are subject to group limits and temperature derating.
Q: What external protection is required?
A: The module specifies external fast-blow fuse protection. Schneider's connection documentation identifies a 3 A fast-blow fuse for each four-channel group; confirm the applicable wiring diagram and load requirements before installation.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like
Blog Posts
Industrial automation news, technical guides, and product updates.