The BMXSAI0410 is a safety analog input module for the Schneider Electric Modicon X80 I/O platform, engineered specifically for Modicon M580 safety systems. It provides 4 isolated 4-20 mA current inputs with 16-bit A/D conversion, internal recalibration, and out-of-range current detection. Featuring a red housing coating designated for safety components, it supports functional safety architectures up to SIL 3, Category 4, and PLd, and operates exclusively with a Modicon M580 Safety CPU.

Technical Specifications

Parameter Specification
Model BMXSAI0410
Brand Schneider Electric
Product Range Modicon X80
Product Type Safety Analog Input Module
Number of Inputs 4 isolated channels
Input Type Current, 4-20 mA (high level)
Analog/Digital Conversion 16-bit
Input Resolution 13-bit (0 to 12,500 counts; 2 uA measurement resolution)
Digital Value Format +/- 10,000 (default); +/- 32,000 (user scale)
Nominal Read Cycle Time 6 ms for 4 channels
Measurement Error Less than or equal to 0.3% of full scale at -25 to 60 deg C
Temperature Drift 30 ppm/deg C
Input Impedance 286 Ohm (0.1% internal resistor precision, 15 ppm/deg C)
Permitted Input Overload 25 mA (maximum conversion range: 0-25 mA)
Digital Filtering Second-order digital filter
Crosstalk Attenuation Minimum 120 dB
Electrical Connection 20-way removable terminal block (1 connector)
Isolation Voltage 500 VDC (channel-to-channel); 1500 VDC (channel-to-ground and channel-to-bus)
Current Consumption 200 mA at 3.3 VDC; 115 mA at 24 VDC
Status Indicators 1 green RUN LED, 1 red ERR LED, 1 red I/O LED, 4 green channel diagnostic LEDs
Safety Ratings Up to SIL 3, Category 4, PLd; CIP Safety compliant
Certifications TUV Rheinland, CE, UL, CSA, ATEX, IECEx, EAC, RCM, Merchant Navy
Compliance Standards IEC 61131-2, IEC 61010-2-201, UL 61010-2-201, CSA C22.2 No 61010-2-201
Operating Temperature -25 to 60 deg C
Storage Temperature -40 to 85 deg C
Relative Humidity 5 to 95% at 55 deg C (without condensation)
Operating Altitude 0 to 2,000 m (2,000 to 5,000 m with derating factor)
Environmental Resistance Gas class Gx / 3C4; Dust and sand class 3S4; Salt level 2; Mold and fungal spore class 3B2 (IEC 60721-3-3)
Mechanical Resistance Vibration: 3 gn; Shock: 15 gn
Protection Rating IP20
MTBF 463,000 hours
Net Weight 0.143 kg
Dimensions (H x W x L) 5.5 cm x 18.0 cm x 26.0 cm

Signal Processing and Isolation Architecture

Each of the four channels measures 4-20 mA process signals across an internal 286 Ohm precision resistor (0.1% tolerance) and converts the signal via a 16-bit A/D converter with second-order digital filtering. The module scans all 4 channels within a nominal read cycle time of 6 ms, maintaining a measurement resolution of 2 uA and an accuracy within 0.3% of full scale across the -25 to 60 deg C operating range.

Galvanic isolation is rated at 500 VDC between individual channels and 1500 VDC from channels to ground and backplane bus, preventing ground loops and cross-channel interference (minimum 120 dB crosstalk attenuation). Built-in diagnostics monitor for out-of-range current conditions up to the 25 mA overload limit and report status via dedicated green channel LEDs alongside module-level RUN, ERR, and I/O indicators.

Compatibility and Installation Considerations

  • Controller Requirement: Although part of the common Modicon X80 I/O family, the BMXSAI0410 is dedicated to Modicon M580 safety architectures and can only operate with a Modicon M580 Safety CPU. It cannot be used in standard non-safety M340 or standard M580 configurations.
  • Rack Placement and Clearance: The module can be installed in either a local main rack or a remote drop rack (Ethernet or X-bus). Note that the physical height of this safety I/O module exceeds the standard Modicon X80 rack height; cabinet layouts must account for the extra vertical clearance before mounting the rack.
  • Field Wiring: Field signals connect via a single 20-way removable terminal block, allowing module replacement without disturbing field wiring.

Frequently Asked Questions

Q: Can the BMXSAI0410 be used with a standard Modicon M340 or non-safety M580 CPU?A: No. While it uses the Modicon X80 form factor, the BMXSAI0410 is strictly dedicated to Modicon M580 safety systems and requires a Safety CPU to function.

Q: What physical clearance is needed when mounting the BMXSAI0410 in a rack?A: The height of the BMXSAI0410 module is greater than the height of a standard Modicon X80 Ethernet or X-bus rack. Ensure sufficient vertical space above or below the rack in the enclosure prior to installation.

Q: How are channel faults and out-of-range signals indicated on the module?A: The module features continuous current out-of-range detection up to 25 mA, displaying channel-specific diagnostics on 4 individual green LEDs along with module-level red ERR and I/O fault LEDs.

Payment: T/T, Western Union.

Shipping port: Xiamen.

Lead time: Typically 1–3 working days after payment confirmation (subject to stock).

Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.

F.A.Q.

Common questions about quotes, shipping, warranty and returns

Click Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.

In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.

Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.

We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.

Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.

Products FAQs

You may also like