Skip to product information
1 of 3

Yokogawa ADV151-E60 32-Channel Digital Input Module

13 in stock
  • Manufacturer: 6G Controls
  • Product No.: ADV151-E60
  • Product Type: 32-Channel Digital Input Module
  • Condition: Brand New
  • Payment: T/T, Western Union
  • Weight: 0.3 kg
  • Shipping port: Xiamen
  • Warranty: 12 months
  • Description
  • Reviews
  • Shipping & Payment

The Yokogawa ADV151-E60 is a 32-channel digital input module designed for the FIO (Fieldbus Independent I/O) system. It accepts 24 V DC discrete signals in sink or source configurations and provides separate input characteristics for status and pushbutton signals. The module supports pressure clamp terminals and dedicated cable connections for field signal wiring.

Input Configuration and Signal Characteristics

The ADV151-E60 provides 32 digital input channels with a rated input voltage of 24 V DC. Its ON and OFF voltage thresholds define the signal recognition range, while the 30.0 V DC maximum allowable input voltage specifies the upper limit for the applied input signal.

The module supports both sink and source input configurations. Each channel draws 4.1 mA +/-20% at the rated input voltage, which is relevant when checking field contact ratings and the electrical loading of connected devices.

Signal Response and Input Functions

The module supports status input and pushbutton input functions, with different timing characteristics for each:

  • Status input: Input response time of 8 ms or less.
  • Pushbutton input: Minimum ON detection time of 20 ms.
  • Pushbutton input: Maximum ON/OFF cycle frequency of 25 Hz.

These timing specifications should be considered when selecting the module for discrete signal acquisition. In particular, the 20 ms minimum ON detection time applies to pushbutton input and should not be confused with the status input response time.

Electrical Isolation and Power Consumption

The input signal circuits have a withstand voltage of 2 kV AC for 1 minute between the input signal and the system. The withstand voltage between commons is 500 V AC for 1 minute, with a separate common for every 16 input channels.

Maximum current consumption is 500 mA from the 5 V DC supply. This value should be included when checking the power capacity available for the installed I/O configuration.

Technical Specifications

Parameter Specification
Model ADV151-E60
Brand Yokogawa
Product Type Digital Input Module
System FIO (Fieldbus Independent I/O)
Number of Input Channels 32
Rated Input Voltage 24 V DC (sink/source)
Input ON Voltage 18 to 26.4 V DC
Input OFF Voltage 5.0 V DC or less
Input Current 4.1 mA +/-20% / channel
Maximum Allowable Input Voltage 30.0 V DC
Withstanding Voltage (Signal to System) 2 kV AC, 1 minute
Withstanding Voltage (Between Commons) 500 V AC, 1 minute
Common Configuration Common every 16 channels
Input Response Time 8 ms or less (status input)
Maximum Current Consumption 500 mA (5 V DC)
External Connection Pressure clamp terminal, dedicated cable (AKB331), MIL connector cable
Weight 0.3 kg

External Connections and Installation Considerations

The ADV151-E60 supports three external connection options: pressure clamp terminals, the dedicated AKB331 cable, and MIL connector cables. The selected connection method affects the applicable wiring arrangement and electrical isolation conditions.

When using a dedicated cable, the withstand voltage between the input signal and system is limited to 500 V AC. For MIL connector cables, the applicable withstand voltage depends on the electrical specifications of the cable.

Frequently Asked Questions

Q: Does the ADV151-E60 support Sequence of Events (SOE) input?

A: Yes. The ADV151-E variant supports SOE data capture. This function allows the system to record discrete input events for sequence analysis and event monitoring.

Q: Can the ADV151-E60 be used for pushbutton input?

A: The ADV151-E and ADV151-P variants have different function allocations. The manufacturer's specification identifies SOE input for ADV151-E and pushbutton edge counting for ADV151-P. These functions should not be treated as interchangeable.

Q: What should be checked when connecting the 32 input channels?

A: The module uses a common connection for every 16 channels. All 24 V DC input signals connected to the module must have the same polarity. The selected cable type should also be checked against the applicable withstand-voltage requirements.

Payment: T/T, Western Union.

Shipping port: Xiamen.

Lead time: Typically 1–3 working days after payment confirmation (subject to stock).

Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.

F.A.Q.

Common questions about quotes, shipping, warranty and returns

Click Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.

In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.

Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.

We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.

Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.

Products FAQs

You may also like