Notified by email when this product becomes available
- Description
- Reviews
- Shipping & Payment
Overview
The Yokogawa ADV151-E63-S2 is a high-density 32-channel digital input module designed for Yokogawa’s Field I/O (FIO) system. It captures discrete ON/OFF signals from field devices such as switches, push buttons, and alarms, converting them into precise digital data for process monitoring and control. Engineered for demanding industrial environments, this module provides excellent noise immunity and supports millisecond-resolution Sequence of Events (SOE) logging for critical event analysis.
Technical Specifications
| Specification | Details |
|---|---|
| Model | ADV151-E63-S2 |
| Module Type | Digital Input Module |
| Input Channels | 32 isolated channels |
| Rated Input Voltage | 24 V DC |
| Input ON Voltage | 18 – 26.4 V DC |
| Input OFF Voltage | ≤ 5.0 V DC |
| Input Current | ~4.1 mA ±20% per channel |
| Maximum Allowable Voltage | 30 V DC |
| Response Time | Typical 10 ms |
| SOE Capture | Supported, millisecond resolution |
| Mounting | DIN rail or module rack |
| Dimensions | 107.5 × 130 × 32.8 mm |
| Weight | 0.3 kg |
| Operating Temperature | -10 °C to +60 °C |
| Humidity Range | 5% – 95% RH, non-condensing |
Key Features
- High-density input: 32 channels in one compact module
- Noise immunity for reliable operation in electrically harsh environments
- SOE logging for precise event tracking and troubleshooting
- Compatible with ESB Bus Node Units, Optical ESB Bus Node Units, and Field Control Units
- Compact and space-saving design for simplified installation
Typical Applications
- Monitoring switches, sensors, and alarms in industrial facilities
- Safety Instrumented Systems (SIS) requiring event logging
- Process automation in chemical, oil & gas, power generation, and manufacturing
- Sequence monitoring for troubleshooting, diagnostics, and compliance reporting
FAQ
Q: Can this module operate in high-humidity conditions? A: Yes, the ADV151-E63-S2 supports 5%–95% non-condensing humidity.
Q: Does it support Sequence of Events (SOE) logging? A: Yes, SOE capture is supported with millisecond resolution for critical event tracking.
Q: What bus systems is it compatible with? A: Compatible with Yokogawa ESB Bus Node Units, Optical ESB Bus Node Units, and Field Control Units.
Payment: T/T, Western Union.
Shipping port: Xiamen.
Lead time: Typically 1–3 working days after payment confirmation (subject to stock).
Worldwide delivery: We ship industrial automation parts to customers around the world. Freight is quoted with your RFQ.
F.A.Q.
Common questions about quotes, shipping, warranty and returnsClick Request a Quote on the product page and send us the part number, required quantity, and destination country. Our sales team will reply with current availability, pricing, and estimated delivery time.
In-stock items are normally prepared after payment and order confirmation. Most orders are dispatched from our warehouse in China, although the shipping location may vary depending on current stock.
Yes. We ship industrial automation parts to customers worldwide. Shipping cost and transit time depend on the destination, package weight, product size, and local import requirements.
We commonly use DHL, FedEx, UPS, and other international courier services. The carrier can be selected according to the destination, delivery speed, shipment size, and customer requirements.
Our products are generally covered by a 12-month warranty. Eligible products may also be returned under our 30-day refund policy. Please contact our team before returning any item to confirm the applicable terms and return instructions.
You may also like
Blog Posts
Industrial automation news, technical guides, and product updates.