The Schneider BMXCPS4002 is a Modicon X80 power supply module designed for redundant power architectures in PLC and PAC systems. It accepts a 100-240 V AC primary supply and provides separate 3.3 V DC and 24 V DC secondary outputs for module logic and I/O power distribution. Network-based diagnostics and redundancy monitoring support power supply status supervision in the control system.
Power Supply Function and Redundant Architecture
The BMXCPS4002 supplies the internal power requirements of an X80 module rack. Its 3.3 V DC output powers I/O module logic, while the 24 V DC output supplies I/O module power and the processor, subject to the specified load conditions.
The module supports redundant power architecture and provides redundancy status information. Its diagnostic functions include temperature monitoring, redundancy testing, operating time and remaining service-life information. These diagnostics can be accessed over the network.
Electrical Protection and Status Monitoring
The secondary circuits incorporate overload, overvoltage and short-circuit protection. These functions protect the downstream power distribution circuits against specified electrical fault conditions. The primary circuit also has internal protection.
Three green LEDs indicate voltage availability, redundancy status and overall power supply status. A RESET button provides a cold-start reset function.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXCPS4002 |
| Brand | Schneider Electric |
| Product Series | Modicon X80 |
| Product Type | Redundant Power Supply Module |
| Primary Voltage | 100-240 V AC |
| Primary Voltage Limits | 85-264 V |
| Supply Frequency | 50/60 Hz |
| Frequency Limits | 47-63 Hz |
| Apparent Power | 0.13 kVA |
| Input Current | 0.55 A at 240 V; 1.01 A at 115 V |
| Inrush Current | 30 A at 120 V; 60 A at 240 V |
| Secondary Output | 3.3 V DC and 24 V DC |
| Secondary Power | 18 W at 3.3 V DC; 40 W at 24 V DC |
| Secondary Current | 5.5 A at 3.3 V DC; 1.67 A at 24 V DC |
| Maximum Power Dissipation | 8.5 W |
| Power Interruption Immunity | 1 ms |
| Protection | Secondary overload, overvoltage and short-circuit protection |
| Diagnostics | Temperature monitoring, redundancy test, operating time and remaining operating life |
| Status Indicators | 3 green LEDs |
| Reset Function | Cold-start RESET button |
| Electrical Connections | 2-pin alarm relay connector; 5-pin power supply and protective earth connector |
| Insulation Resistance | >= 100 MOhm, primary/earth and primary/secondary |
| Dielectric Strength | 1500 V primary/secondary; 1500 V primary/earth; 2300 V sensor supply/secondary; 500 V sensor output/ground |
| Protection Rating | IP20 |
| Operating Temperature | 0 to 60 deg C |
| Storage Temperature | -40 to 85 deg C |
| Relative Humidity | 5-95% at 55 deg C, non-condensing |
| Operating Altitude | 0-2,000 m; derating required from 2,000 to 5,000 m |
| Coating | TC, Humiseal 1A33 |
| Environmental Classification | 3C3 and 3C4 according to IEC 60721-3-3 |
| Vibration Resistance | 3 Gn |
| Shock Resistance | 30 gn |
| MTBF | 792,000 h |
| Weight | 0.51 kg |
| EAN | 3606480927560 |
| Lifecycle Carbon Footprint | 496 kg CO2 eq. |
Electrical Connections and Installation
The BMXCPS4002 has separate connectors for the alarm relay and incoming power supply. The 5-pin connector provides the power supply and protective earth connections, while the 2-pin connector is used for the alarm relay.
Installation requirements include:
- Mount the module in a Modicon X80 module rack.
- Secure the power supply using two screws.
- Use the supplied removable 5-way and 2-way terminal blocks.
- Observe the specified operating temperature and altitude derating conditions.
The module has an IP20 protection rating and is intended for installation within an appropriate equipment enclosure.
Certifications and Standards
The product documentation identifies the following certifications and standards:
- Certifications: CE, RCM, Merchant Navy, CSA, EAC and UL.
- EN 61131-2
- EN 61000-6-4
- EN 61000-6-2
- EN 61010-2-201
- EU Low Voltage Directive 2014/35/EU
- EU EMC Directive 2014/30/EU
Frequently Asked Questions
Q: Can the BMXCPS4002 be used in a redundant power supply architecture?
A: Yes. The BMXCPS4002 is specified for redundant power architectures. Its redundancy monitoring functions provide status information for system-level supervision. The actual redundant configuration must follow the applicable Modicon X80 system design requirements.
Q: What are the two secondary output voltages used for?
A: The 3.3 V DC output supplies I/O module logic, while the 24 V DC output supplies I/O module power and the processor under the specified load conditions. The rated output powers are 18 W and 40 W respectively.
Q: Does the BMXCPS4002 provide network diagnostics?
A: Yes. Available diagnostic information includes temperature sensor data, redundancy test results, operating time and remaining operating life. These functions support remote monitoring of the power supply condition.
Thanh toán: T/T, Western Union.
Cảng vận chuyển: Hạ Môn.
Thời gian giao hàng: Thông thường từ 1–3 ngày làm việc sau khi xác nhận thanh toán (tùy tình trạng hàng tồn kho).
Giao hàng toàn cầu: Chúng tôi vận chuyển các linh kiện tự động hóa công nghiệp đến khách hàng trên toàn thế giới. Cước phí sẽ được báo cùng với yêu cầu báo giá của bạn.
Câu hỏi thường gặp
Các câu hỏi thường gặp về báo giá, vận chuyển, bảo hành và đổi trảNhấp vào Yêu cầu báo giá trên trang sản phẩm và gửi cho chúng tôi mã linh kiện, số lượng cần thiết và quốc gia nhận hàng. Đội ngũ bán hàng của chúng tôi sẽ phản hồi về tình trạng còn hàng, giá cả hiện tại và thời gian giao hàng dự kiến.
Các mặt hàng có sẵn thường được chuẩn bị sau khi thanh toán và xác nhận đơn hàng. Hầu hết đơn hàng được gửi đi từ kho của chúng tôi tại Trung Quốc, mặc dù địa điểm gửi hàng có thể thay đổi tùy theo tình trạng hàng tồn kho hiện tại.
Có. Chúng tôi vận chuyển linh kiện tự động hóa công nghiệp đến khách hàng trên toàn thế giới. Chi phí vận chuyển và thời gian giao hàng phụ thuộc vào điểm đến, trọng lượng kiện hàng, kích thước sản phẩm và các yêu cầu nhập khẩu tại địa phương.
Chúng tôi thường sử dụng DHL, FedEx, UPS và các dịch vụ chuyển phát quốc tế khác. Có thể lựa chọn đơn vị vận chuyển tùy theo điểm đến, tốc độ giao hàng, kích thước lô hàng và yêu cầu của khách hàng.
Các sản phẩm của chúng tôi thường được bảo hành 12 tháng. Các sản phẩm đủ điều kiện cũng có thể được trả lại theo chính sách hoàn tiền trong 30 ngày. Vui lòng liên hệ với đội ngũ của chúng tôi trước khi trả lại bất kỳ sản phẩm nào để xác nhận các điều khoản áp dụng và hướng dẫn trả hàng.
Bạn cũng có thể thích
Bài đăng blog
Tin tức về tự động hóa công nghiệp, hướng dẫn kỹ thuật và cập nhật sản phẩm.