The Honeywell FC-TDOL-0724P is a field termination assembly for 24 VDC line-monitored digital outputs in the Safety Manager system. It provides seven fused relay contact outputs, each rated at 2 A, for non-safety-related resistive or inductive loads up to 50 W. Dedicated monitoring circuits detect short circuits and lead breakages when outputs are energized or de-energized, in conjunction with compatible Safety Manager digital input and output modules and the required application software.
Output Configuration and Line Monitoring
The FC-TDOL-0724P provides seven individually fused relay contact outputs. Each channel supports a maximum output current of 2 A, subject to the load rating, fuse protection, and temperature-dependent derating limits. The specified field supply is 24 VDC +/- 20%.
Each channel includes a dedicated line-monitoring circuit for detecting wiring faults in both the energized and de-energized states. The short-circuit detection load threshold is specified as 200 ohm to 400 ohm. The diagnostic function requires coordinated operation with standard Safety Manager DI and DO modules configured for redundant or non-redundant I/O, together with the applicable software from the Safety Manager Function Library.
Electrical Ratings
| Parameter | Specification |
|---|---|
| Model | FC-TDOL-0724P |
| Brand | Honeywell |
| Product Type | Line-Monitored Relay Contact Digital Output Field Termination Assembly |
| Number of Output Channels | 7 |
| Output Supply Voltage | 24 VDC +/- 20% |
| Maximum Output Current | 2 A per channel |
| Supported Load | Non-safety-related resistive or inductive loads |
| Maximum Field Load | 50 W per output, as specified in the product description |
| Maximum Load Resistance | 2200 ohm |
| Load Leakage Current | Approx. 1.1 mA at 24 V |
| Output Voltage, OFF State | 90% of output supply voltage, as specified |
| Output Voltage, ON State | 100% of output supply voltage, as specified |
| Short-Circuit Detection Threshold | 200 ohm < RTh < 400 ohm |
| Inductive Load Suppression | Spark suppression diode specified |
| Relay Maximum Switched Power | 150 W |
| Electrical Relay Life | 100,000 switching operations |
| Mechanical Relay Life | 30,000,000 switching operations |
Fuse Protection and Derating
Each output uses a 2 A fuse with the following specifications.
| Parameter | Specification |
|---|---|
| Fuse Manufacturer | Littelfuse |
| Fuse Part Number | 0213002 |
| Fuse Dimensions | 5 x 20 mm |
| AC Voltage Rating | 250 V |
| DC Voltage Rating | 300 V |
| Current Derating | Linear from 2 A at 25 deg C to 1.9 A at 70 deg C |
The fuse rating defines the specified protection component, not an unrestricted continuous load rating under all conditions. The stated current derating should be considered when evaluating operation at elevated temperatures. The product description limits field loads to 50 W, even though the relay contact specification lists a maximum switched power of 150 W; these figures describe different stated limits and should not be treated as interchangeable.
Power Consumption
The assembly uses the 24 VDC field supply and associated Safety Manager I/O modules for its output and read-back functions. The listed consumption values distinguish the field supply from current drawn through the associated I/O modules.
| Parameter | Specification |
|---|---|
| Field Supply Consumption | Less than 9 mA with all channels OFF |
| Relay and Channel 8 Consumption | Approx. 200 mA from TSDO-0824; maximum 250 mA at Vmax |
| Read-Back Circuit Consumption | Less than 110 mA with a single SDI-1624 |
| Read-Back Circuit Consumption, Redundant Configuration | Less than 210 mA with redundant SDI-1624 |
| Maximum Read-Back Consumption | 275 mA at Vmax |
The listed values apply to different supply paths and circuit configurations. They should not be added together as a single power-consumption figure without confirming the applicable wiring and system configuration.
Mechanical Design and Field Termination
The assembly mounts on standard TS32 or TS35 x 7.5 DIN EN rails. Seven pairs of screw terminals provide the field wiring connections, while a keyed two-pole connector provides the common supply connection.
| Parameter | Specification |
|---|---|
| Dimensions (L x W x H) | 240 x 109 x 80 mm |
| Dimensions (L x W x H) | 9.45 x 4.29 x 3.15 in |
| Required DIN Rail Length | 241 mm (9.49 in) |
| Supported DIN Rails | TS32 / TS35 x 7.5 |
| Field Wiring Terminals | 7 pairs of screw terminals |
| Maximum Field Wire Diameter | 2.5 mm (AWG 14) |
| Field Wire Strip Length | 7 mm (0.28 in) |
| Field Terminal Tightening Torque | 0.5 Nm (0.37 ft-lb) |
| Power Connector | Keyed two-pole header |
| Power Connector Manufacturer and Type | Weidmuller BVZ 7.62HP/02/180F SN |
| Power Connector Key | Weidmuller BV/SV7.62HP KO |
| Power Connector Wire Strip Length | 8 mm, as specified in the source data |
| Connectable Power Conductor Range | 0.5-6 mm, as specified in the source data |
The field terminals and common supply connector have separate wiring requirements. Confirm conductor size, stripping length, terminal torque, and connector keying before installation. The supplied dimensions and rail length should also be checked against the available cabinet space.
Frequently Asked Questions
Q: Can the FC-TDOL-0724P be used for safety-related field loads?
A: The specified application is for non-safety-related resistive or inductive loads up to 50 W per output. Its line-monitoring capability does not, by itself, establish a safety integrity rating for the field termination assembly.
Q: Which Safety Manager I/O modules are required for line monitoring?
A: The documented configuration uses the SDI-1624 digital input module and SDO-0824 digital output module. Both are required for the stated line-monitoring arrangement, with the overall configuration and application software selected for redundant or non-redundant I/O.
Q: What load conditions must be checked before connecting a field device?
A: Verify the 24 VDC +/- 20% supply, 2 A channel fuse, 50 W field-load limit, relay contact rating, and temperature-dependent current derating. Inductive loads must also meet the specified spark-suppression diode requirement.
Zahlung: T/T, Western Union.
Versandhafen: Xiamen.
Lieferzeit: In der Regel 1–3 Werktage nach Bestätigung der Zahlung (je nach Lagerbestand).
Weltweiter Versand: Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Die Frachtkosten werden mit Ihrem RFQ angegeben.
Häufig gestellte Fragen
Häufige Fragen zu Angeboten, Versand, Garantie und RückgabenKlicken Sie auf der Produktseite auf Angebot anfordern und teilen Sie uns die Teilenummer, die benötigte Menge und das Zielland mit. Unser Vertriebsteam antwortet mit der aktuellen Verfügbarkeit, dem Preis und der voraussichtlichen Lieferzeit.
Vorrätige Artikel werden normalerweise nach Zahlung und Auftragsbestätigung vorbereitet. Die meisten Bestellungen werden von unserem Lager in China versandt, wobei der Versandort je nach aktuellem Lagerbestand variieren kann.
Ja. Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Versandkosten und Lieferzeit hängen vom Bestimmungsort, dem Paketgewicht, der Produktgröße und den örtlichen Einfuhrbestimmungen ab.
Wir nutzen in der Regel DHL, FedEx, UPS und andere internationale Kurierdienste. Der Versanddienstleister kann je nach Zielort, Liefergeschwindigkeit, Sendungsgröße und Kundenanforderungen ausgewählt werden.
Unsere Produkte sind grundsätzlich durch eine 12-monatige Garantie abgedeckt. Für berechtigte Produkte ist außerdem eine Rückgabe gemäß unserer 30-Tage-Erstattungsrichtlinie möglich. Bitte kontaktieren Sie unser Team, bevor Sie einen Artikel zurücksenden, um die geltenden Bedingungen und Rücksendeanweisungen zu bestätigen.
Das könnte Ihnen auch gefallen
Blogbeiträge
Neuigkeiten zur industriellen Automatisierung, technische Anleitungen und Produktneuheiten.