Zu den Produktinformationen springen
1 von 3

Schneider Electric BMEP583040 Modicon M580 Processor Module

18 auf Lager
  • Manufacturer: Schneider
  • Product No.: BMEP583040
  • Country of origin: France
  • Product Type: Modicon M580 Processor Module
  • Condition: Brandneu
  • Payment: T/T, Western Union
  • Weight: 0.849 kg
  • Shipping port: Xiamen
  • Warranty: 12 Monate
  • Beschreibung
  • Reviews
  • Versand & Zahlung

Configured for processor execution, local I/O management, and Ethernet TCP/IP communication in the Modicon M580 PAC platform, the Schneider Electric BMEP583040 (BMEP583040 Processor Module) provides rack-based control processing with integrated Ethernet service and device-network interfaces. It supports up to 8 racks, 3072 discrete local I/O, 768 analog local I/O, 16 remote I/O stations, and 64 distributed devices.

Hardware Specifications

Parameter Specification
Model BMEP583040
Brand Schneider Electric
Series Modicon M580
Product Type Processor Module
Origin US
Weight 0.849 kg
Operating Temp 0 to 60 deg C
Power Consumption 295 mA at 24 VDC
Rack Capacity 8 racks
Local Discrete I/O 3072 I/O
Local Analog I/O 768 I/O
Application-Specific Channels 108
Remote I/O Stations 16, 2 remote drops per I/O station
Distributed Equipment 64
Ethernet Interfaces 1 Ethernet TCP/IP service port; 2 Ethernet TCP/IP device-network ports
USB Interface USB type Mini-B
Program Memory 12 MB integrated RAM
Data Memory 1024 kB integrated RAM
System Memory 10 kB integrated RAM
Flash Storage 4 GB expandable flash
Communication Services RIO scanner, DIO scanner
Processing Capacity 30 Kinst/ms at 65% Boolean + 35% fixed arithmetic; 40 Kinst/ms at 100% Boolean
MTBF 775000 h
Protection Rating IP20
Storage Temp -40 to 85 deg C
Vibration Resistance 3 gn
Shock Resistance 30 gn
Relative Humidity 5 to 95% at 55 deg C, non-condensing
Operating Altitude 0 to 2000 m; 2000 to 5000 m with derating
Certifications CE, UL, CSA, RCM, EAC, Merchant Navy, UKCA
Standards IEC 61131-2, IEC 61010-2-201, UL 61010-2-201, CSA C22.2 No 61010-2-201, IACS E10, EN/IEC 61000-6-5, EN/IEC 61850-3

Ethernet and I/O Processing

The BMEP583040 separates Ethernet service communication from device-network communication through dedicated TCP/IP interfaces. The processor provides RIO and DIO scanner functions for remote and distributed I/O management. The rack-based architecture supplies internal power to the processor and connected modules, while the processor manages local I/O resources and application execution.

The module supports application-specific functions including serial link, motion control, counter, SSI encoder, HART, and accurate time stamping. Its application structure includes auxiliary tasks, cyclic or periodic master tasks, event tasks, and a periodic fast task.

Frequently Asked Questions

Q: What power connection is used by the BMEP583040?

A: The processor receives its operating power internally through the rack. The specified processor current consumption is 295 mA at 24 VDC.

Q: How many Ethernet interfaces are integrated into the processor?

A: The module provides one Ethernet TCP/IP service port and two Ethernet TCP/IP device-network ports. A USB type Mini-B interface is also provided.

Q: What local and remote I/O capacity is specified?

A: The processor supports up to 3072 discrete local I/O, 768 analog local I/O, and 16 remote I/O stations. The specified distributed equipment capacity is 64 devices.

Field Installation Guidelines

Install the processor in the designated Modicon M580 rack position and ensure that the rack power and backplane connections are correctly seated before energizing the system. Confirm that the processor is mechanically secured and that adjacent modules do not obstruct ventilation or access to status indicators.

Route Ethernet communication cables separately from high-current power conductors and switching circuits where practical. Maintain proper cable shielding and grounding practices according to the installation design and applicable M580 documentation.

Before commissioning, verify the Ethernet port assignment, device-network topology, rack configuration, and I/O addressing against the application configuration. Check the RUN, ERR, I/O, DL, BACKUP, and Ethernet status indicators after startup to identify processor, I/O, memory, or network conditions.

Zahlung: T/T, Western Union.

Versandhafen: Xiamen.

Lieferzeit: In der Regel 1–3 Werktage nach Bestätigung der Zahlung (je nach Lagerbestand).

Weltweiter Versand: Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Die Frachtkosten werden mit Ihrem RFQ angegeben.

Häufig gestellte Fragen

Häufige Fragen zu Angeboten, Versand, Garantie und Rückgaben

Klicken Sie auf der Produktseite auf Angebot anfordern und teilen Sie uns die Teilenummer, die benötigte Menge und das Zielland mit. Unser Vertriebsteam antwortet mit der aktuellen Verfügbarkeit, dem Preis und der voraussichtlichen Lieferzeit.

Vorrätige Artikel werden normalerweise nach Zahlung und Auftragsbestätigung vorbereitet. Die meisten Bestellungen werden von unserem Lager in China versandt, wobei der Versandort je nach aktuellem Lagerbestand variieren kann.

Ja. Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Versandkosten und Lieferzeit hängen vom Bestimmungsort, dem Paketgewicht, der Produktgröße und den örtlichen Einfuhrbestimmungen ab.

Wir nutzen in der Regel DHL, FedEx, UPS und andere internationale Kurierdienste. Der Versanddienstleister kann je nach Zielort, Liefergeschwindigkeit, Sendungsgröße und Kundenanforderungen ausgewählt werden.

Unsere Produkte sind grundsätzlich durch eine 12-monatige Garantie abgedeckt. Für berechtigte Produkte ist außerdem eine Rückgabe gemäß unserer 30-Tage-Erstattungsrichtlinie möglich. Bitte kontaktieren Sie unser Team, bevor Sie einen Artikel zurücksenden, um die geltenden Bedingungen und Rücksendeanweisungen zu bestätigen.

Products FAQs

Das könnte Ihnen auch gefallen