
Per E-Mail benachrichtigen, sobald dieses Produkt verfügbar ist
- Beschreibung
- Reviews
- Versand & Zahlung
Configured for safety and process control in the Modicon M580 platform, the Schneider Electric BMEP584040S (BMEP584040S processor module) provides processor execution, Ethernet device communication, local and remote I/O management, and CIP Safety device processing. It supports up to 8 racks, 16 remote I/O stations, 64 distributed devices, and 64 CIP Safety I/O devices.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMEP584040S |
| Brand | Schneider Electric |
| Series | Modicon M580 |
| Product Type | Processor module |
| Origin | US |
| Weight | 0.849 kg |
| Dimensions | 9.921 x 7.008 x 3.504 in (package dimensions) |
| Operating Temp | -25 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Power Consumption | 295 mA at 24 VDC |
| Supply | Internal power supply via rack |
| Rack Capacity | 8 racks |
| Local Discrete I/O | 4096 I/O |
| Local Analog I/O | 1024 I/O |
| Local Application-Specific Channels | 144 |
| Remote I/O Stations | 16 |
| Distributed Equipment | 64 |
| CIP Safety I/O Devices | 64 |
| Ethernet Connections | 1 service port + 2 device network ports |
| USB Connection | 1 USB mini-B |
| Program Memory | 16 MB |
| Data Memory | 2048 kB |
| Safety Program Memory | 4 MB |
| Safety Data Memory | 1024 kB |
| Flash Storage | 4 GB |
| Instruction Processing | 30 Kinst/ms at 65% Boolean + 35% fixed arithmetic; 40 Kinst/ms at 100% Boolean |
| Communication Services | RIO scanner, DIO scanner |
| Communication Module Capacity | 16 AS-Interface modules, 4 Ethernet communication modules |
| Protection Rating | IP20 |
| Protective Treatment | Conformal coated |
| Vibration Resistance | 3 gn |
| Shock Resistance | 15 gn |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| Operating Altitude | 0 to 2000 m; 2000 to 5000 m with derating |
| Safety Level | SIL 3 IEC 61508/IEC 61511; SILCL 3 IEC 62061 and ISO 13849-1 Category 4; SIL 4 EN 50126/EN 50128/EN 50129 |
| Certifications | CE, UL, CSA, RCM, EAC, ATEX Zone 2/22, IECEx Zone 2/22, TÜV, UKCA |
| Cybersecurity Functions | DoS prevention, IPSec, SNMP logging, Syslog, audit trail, embedded firewall, firmware signature, password protection, port hardening |
M580 Ethernet and I/O Processing
The BMEP584040S uses Ethernet TCP/IP interfaces for service and device-network communication. The processor manages RIO and DIO scanning and supports distributed equipment and CIP Safety I/O devices. Local processing capacity is specified at 4096 discrete I/O and 1024 analog I/O, with up to 144 application-specific local channels.
Application-specific functions include counter processing, motion control, SSI encoder interfaces, accurate time stamping, serial links, and HART communication. The processor provides separate program, process data, safety program, and safety data memory areas.
Frequently Asked Questions
Q: How is the BMEP584040S powered?
A: The module receives its operating power through the Modicon M580 rack backplane. The specified current consumption is 295 mA at 24 VDC.
Q: What Ethernet connections are provided?
A: The processor has one Ethernet TCP/IP service port and two Ethernet TCP/IP device-network ports. A USB mini-B interface is also provided for integrated connections.
Q: What I/O and safety device capacity is specified?
A: The processor supports up to 4096 local discrete I/O, 1024 local analog I/O, 16 remote I/O stations, 64 distributed devices, and 64 CIP Safety I/O devices.
Field Installation Guidelines
- Install the processor in the specified Modicon M580 rack position and verify correct mechanical engagement with the backplane.
- Confirm that the rack power system can supply the processor and all connected modules within the applicable load limits.
- Route Ethernet communication wiring separately from high-current switching and power conductors where practical to reduce electromagnetic coupling.
- Terminate cable shields according to the applicable M580 installation and plant grounding design. Avoid creating unintended shield current paths.
- Verify Ethernet port assignment before connecting service and device-network cables.
- Check RUN, ERR, I/O, DL, BACKUP, Ethernet, SRUN, SMOD, and FORCED IO indicators during commissioning.
- Use the specified environmental limits when locating the rack. The module is IP20 and requires an enclosure providing the required environmental protection.
- For safety applications, verify the configured safety architecture, firmware compatibility, wiring, diagnostics, and safety validation procedure against the applicable M580 safety documentation before placing the system into service.
Zahlung: T/T, Western Union.
Versandhafen: Xiamen.
Lieferzeit: In der Regel 1–3 Werktage nach Bestätigung der Zahlung (je nach Lagerbestand).
Weltweiter Versand: Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Die Frachtkosten werden mit Ihrem RFQ angegeben.
Häufig gestellte Fragen
Häufige Fragen zu Angeboten, Versand, Garantie und RückgabenKlicken Sie auf der Produktseite auf Angebot anfordern und teilen Sie uns die Teilenummer, die benötigte Menge und das Zielland mit. Unser Vertriebsteam antwortet mit der aktuellen Verfügbarkeit, dem Preis und der voraussichtlichen Lieferzeit.
Vorrätige Artikel werden normalerweise nach Zahlung und Auftragsbestätigung vorbereitet. Die meisten Bestellungen werden von unserem Lager in China versandt, wobei der Versandort je nach aktuellem Lagerbestand variieren kann.
Ja. Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Versandkosten und Lieferzeit hängen vom Bestimmungsort, dem Paketgewicht, der Produktgröße und den örtlichen Einfuhrbestimmungen ab.
Wir nutzen in der Regel DHL, FedEx, UPS und andere internationale Kurierdienste. Der Versanddienstleister kann je nach Zielort, Liefergeschwindigkeit, Sendungsgröße und Kundenanforderungen ausgewählt werden.
Unsere Produkte sind grundsätzlich durch eine 12-monatige Garantie abgedeckt. Für berechtigte Produkte ist außerdem eine Rückgabe gemäß unserer 30-Tage-Erstattungsrichtlinie möglich. Bitte kontaktieren Sie unser Team, bevor Sie einen Artikel zurücksenden, um die geltenden Bedingungen und Rücksendeanweisungen zu bestätigen.
Das könnte Ihnen auch gefallen
Blogbeiträge
Neuigkeiten zur industriellen Automatisierung, technische Anleitungen und Produktneuheiten.
